2007-03-31 14:50:38 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| FBC2004 |
| FACFLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| ***WINDOW OR DOOR PERMIT APPLICATION, ONLY CHECKED |
| ITEMS APPLY*** |
| |
| ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH |
| THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. |
| |
| _XX_2. DESIGN PRESSURES FOR BUILDINGS OVER 60FEET ARE |
| REQUIRED TO BE DESIGNED USING ASCE7, FBC1609.1.1. |
| DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| PUBLIC RECORD ARE TO BE SIGNED SEALED ORIGINALS |
| FAC61G15-23.002. |
| |
| _XX_3.PROVIDE A COPY OF THE CONDO ASSOCIATION |
| APPROVAL. |
| |
| ____4.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R |
| 301.2.1.2.IF LESS THAN 25% OF THE TOTAL GLAZED AREA |
| IS BEING REPLACED, PROVIDE CALCULATIONS FBC EB507.3. |
| |
| ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. |
| |
| ____6.PROVIDE A FLOOR PLAN SHOWING: WINDOW |
| LOCATIONS, SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE |
| EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE |
| FOR BEDROOMS, FBC R310, FBC EB 505.1. |
| |
| _XX_ 7.CIRCLE (USING INK, NOT HIGHLIGHTER) WHICH |
| MULLION PRODUCT YOU ARE USING.NOTE ON YOUR UNSEALED |
| WIND PRESSURE ENGINEERING YOU HAVE A DESIGN PRESSURE OF |
| -83, BUT HAVE HIGHLIGHTED A MULLION PRODUCT WHICH IS |
| LIMITED TO -67PSF. |
| |
| |