Plan Review Notes
Plan Review Notes For Permit 07030996
Permit Number 07030996
Review Stop P
Sequence Number 2
Notes
Date Text
2007-12-13 11:26:22DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW: (FIRST REVIEW FOR THE DESIGN
 PROFESSIONL)
  
 1. OK
  
 2. ADDRESS ON THE APPLICATION DOES NOT REFLECT THE
 ADDRESS SHOWN ON THE PLANS, SEE THE PALM BEACH COUNTY
 PROPERTY APPRAISER'S WEB-SITE. PLEASE CORRELATE THE
 INFORMATION AND INDICATE UNIT NUMBER AFFECTED BY THE
 APPLICATION. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED. THE ADDRESS ON OUR
 SYSTEM IS 6901 S DIXIE HWY. THE APPLICATION & PLANS
 SHALL SHOW THE CORRECT ADDRESS ON THE TITLE BLOCK ONCE
 THE CORRECT ADDRESS, INCLUDING SPACE, SUITE OR UNIT
 DESIGNATION, HAS BEEN DETERMINED BY THE ADDRESSING
 REVIEWER.
  
 3. SHT A1 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR
 W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 ****NO RESPONSE, NOT ADDRESSED
 ___FOR LAV:
 A. 11-4.19.2 HEIGHT - SHOWS 2'10" FROM THE BOTTOM OF
 THE SLAB ON ONE SIDE OF THE DETAIL AND 2'11-1/2" FROM
 FINISHED FLOOR ON THE OTHER SIDE OF THE DETAIL. PLEASE
 COMPLY WITH SECTION 11-4.19.2.
 ****RESPONSE NOTED, BUT THE CLEARANCE IS NOT INDICATED.
 (29" REQUIRED).
 B. 11-4.19.5 FAUCETS
 ****NO RESPONSE, NOT ADDRESSED
 C. 11-4.29.6 MIRRORS
 ****NO RESPONSE, NOT ADDRESSED
 ___TOILET ROOM
 A. OK
  
 4. NOT APPLICABLE
  
 5. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE THE LOCATION OF THE DRINKING FOUNTAIN.
 ****NO RESPONSE, NOT ADDRESSED
  
 6. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM SHOWING
 ALL PIPE SIZES, VENTS, TRAPS ETC. SECTION
 106.3.5.1.3(4)(13). --THE SINK IS NOT SHOWN ON THE
 RISER DIAGRAM SUBMITTED, AND THE DRINKING FOUNTAIN
 SHALL BE SHOWN ALSO. IF THE RISER DIAGRAM IS NOT
 DESIGNED BY A DESIGN PROFESSIONAL, THE DESIGNER SHALL
 SIGN HIS OR HER NAME TO THE RISER DIAGRAM AND SHALL
 HAVE HIS OR HER NAME PRINTED ON THE RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THE DRINKING FOUNTAIN SHALL BE
 INCLUDED.
  
 7. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES, WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 & LOCATED NEAR THE FIXTURES, (NOT IN THE
 CEILING), ETC. SECTION 106.3.5.1.3(3)(10)(13).
 ****RESPONSE NOTED, BUT THE DRINKING FOUNTAIN SHALL BE
 INCLUDED.
  
 8. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE SPACE. PLEASE INDICATE IF THE BACKFLOW IS EXISTING,
 OR IF NOT INDICATE ON THE WATER SUPPLY RISER DIAGRAM.
 SECTIONS 106.3.5.1.3(8) & 607.3.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 **********NEW COMMENTS**********
  
 1B. THE APPLICATION REQUIRES THAT THE PROJECT IS
 DESCRIBED IN DETAIL. NO MENTION OF THE NEW ACCESSIBLE
 TOILET ROOM IS IN THE DESCRIPTION OF WORK. PLEASE
 DESCRIBE THE PROJECT IN DETAIL AS REQUIRED.
  
 2B. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 3B. SHT A-3 DETAIL D SHOWS THE W/C 1'9" OFF THE WALL TO
 THE CENTER OF THE FIXTURE. 1'8" REQUIRED PER FIG. 28.
 (SEE DETAIL D-1). PLEASE CORRELATE.
  
 4B. SHT A-3 DETAIL D NOTE FOR LAV PIPING INSULATION IS
 NOT COMPLETE AND LEGIBLE. PLEASE CLARIFY. SECTIONS
 106.1.1 & 11-4.19.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE
 SET OF THEM LOOSELY ON TOP OF THE COLLATED
 PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved