Plan Review Notes
Plan Review Notes For Permit 07030996
Permit Number 07030996
Review Stop M
Sequence Number 1
Notes
Date Text
2007-05-02 13:44:10*** DENIED ***
 1) MECHANICAL PERMIT #07040155 HAS BEEN APPLIED FOR BUT
 NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY
 OF WPB AMEND. 106.3.5.4 (10).
  
 2) PERMIT APPLICATION STATES ADDRESS AS 6901 - 05,
 PLEASE STATE ON PLANS IF FIVE UNITS ARE BEING RENOVATED
 OR JUST ONE.
  
 3) MECHANICAL INFORMATION NEED, A/C EQUIPMENT SCHEDULE,
 AND LOCATION OF MINI SPLIT SYSTEM (A/H & C/U)
  
 4) AS NO WINDOW INFORMATION HAS BEEN PROVIDED BATHROOM
 MAY NEED AN EXHAUST FAN, SEE 2004 FBC/M 403, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.