2007-12-14 08:50:06BUILDING PLAN REVIEW
 PERMIT: 07030996
 ADD: 6901-05 S DIXIE HWY
 CONT: JHAMTEC
 TEL: (561)512-9341
  
  
  
 12-14-07
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) 2ND REQUEST,PLEASE CONTACT LILY URSA AT 822-1239
 FOR ADDRESSING THE CITY HAS A SITE ADDRESS OF 6901 S.
 DIXIE HWY FOR THE PROPERTY BUT EACH UNIT REQUIRES
 TENANT ADDRESSES, BEFORE THIS PERMIT CAN BE ISSUED
 CONTACT MUST BE MADE WITH OUR ADDRESSING PERSONEL FOR
 TENANT ADDRESSES. THIS PERMIT WILL NOT BE ISSUED UNTIL
 THIS ISSUE HAS BEEN RESOLVED, THANK YOU FOR YOUR
 COOPERATION IN THIS MATTER.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A)SEMI- COMPLIED.
 NOTE 2006 FBC EXISTING BUILDING CODE ALSO PROVIDE LEVEL
 OF ALTERATION.
 B-G) COMPLIED.
  
 6) COMPLIED.
  
 7-10) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
2007-12-14 08:46:23BUILDING PLAN REVIEW
 PERMIT: 07030996
 ADD: 6901-05 S DIXIE HWY
 CONT: JHAMTEC
 TEL: (561)512-9341
  
  
  
 12-14-07
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) 2ND REQUEST,PLEASE CONTACT LILY URSA AT 822-1239
 FOR ADDRESSING THE CITY HAS A SITE ADDRESS OF 6901 S.
 DIXIE HWY FOR THE PROPERTY BUT EACH UNIT REQUIRES
 TENANT ADDRESSES, BEFORE THIS PERMIT CAN BE ISSUED
 CONTACT MUST BE MADE WITH OUR ADDRESSING PERSONEL FOR
 TENANT ADDRESSES. THIS PERMIT WILL NOT BE ISSUED UNTIL
 THIS ISSUE HAS BEEN RESOLVED, THANK YOU FOR YOUR
 COOPERATION IN THIS MATTER.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A)SEMI- COMPLIED.
 NOTE 2006 FBC EXISTING BUILDING CODE ALSO PROVIDE LEVEL
 OF ALTERATION.
 B-G) COMPLIED.
  
 6) COMPLIED.
  
 7-10) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
2007-06-04 17:04:37BUILDING PLAN REVIEW
 PERMIT: 07030996
 ADD: 6901-05 S DIXIE HWY
 CONT: JHAMTEC
 TEL: (561)512-9341
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE SEE ELECTRICAL COMMENT ABOUT A RESIDENTIAL
 DESIGNER AND SCOPE OF WORK. SEE FL SS 481.229 FOR
 REQUIREMENTS OF DESIGN PROFESSIONAL FOR COMMERCIAL
 WORK.
  
 4) PLEASE CONTACT LILY URSA AT 822-1239 FOR ADDRESSING
 EITHER THIS NEEDS TO BE ADDES AS A UNIT OR A LOT SPLIT
 HAS OCCURED THE PCN OESN'T MATCH WITH THE ONE LISTED ON
 THE PERMIT APPLICATION.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WILL BE PERMITED.
 NOTE 2006 FBC EXISTING BUILDING CODE ALSO PROVIDE LEVEL
 OF ALTERATION.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) NUMBER OF UNITS
  
 6)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY THIS
 STATEMENT ALSO INDICATES A R-3 OCCUPANCY?
  
 7) PLAANS DO NOT PROVIDE INFORMATION TO BREAKAREA SINK?
 SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK
  
 8)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) SWING DOORS EXTERIOR
  
 9)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]