Plan Review Notes
Plan Review Notes For Permit 07030975
Permit Number 07030975
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-04-10 13:36:40*****DENIED******
  
  
  
 1.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2.THE SUBMITTED PLANS SHALL NOT CONTAIN "WHITE OUT"
 AS PER STANDARDS ESTABLISHED THROUGH WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT POLICY STANDARDS FOR
 PLANS AND SPECIFICATIONS.
  
 3.AS THE 2003 EDITION OF NFPA 72, THE AUDIBLE
 APPLIANCE SHALL HAVE A SOUND LEVEL OF AT LEAST 15DB
 ABOVE THE AVERAGE AMBIENT OR 5DB ABOVE THE MAXIMUM
 SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS,
 WHICHEVER IS GREATER, MEASURED 5FEET ABOVE THE FLOOR IN
 THE OCCUPIABLE AREA.
  
 4.NEED TO FILE A NOTICE OF COMMENCEMENT ,PER F. S.
 713.13 .
  
 5.SUBMITTED PLANS REQUIRED TO BE SIGNED, DATED AND
 SEALED AS PER FS 481.221 AND FAC 61G1-16
  
  
  
 CAPT. MICHAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved