 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} AN ATS AND GENERATOR WERE PERMITTED UNDER #06040674
 AND REMAINS OPEN. INDICATE IF THIS IS A SECOND
 GENERATOR AND SERVICE BEING ADDED. SEE 230.2 FOR NUMBER
 OF SERVICES ALLOWED.
  
 2} PROVIDE A SITE PLAN LOCATING ALL SERVICE LOCATIONS
 ON THE BUILDING. 106.1.2 FBC.
  
 3} PAL GROUP IS REPRESENTING ITSELF AS THE DESIGNER OF
 RECORD. THEIR TITLE BLOCK REQUIRES A CERTIFICATE OF
 AUTHORIZATION PER 471.023 FS.
  
 4} THE ARCHITECT WHO SEALED THE PLANS MUST PROVIDE A
 TITLE BLOCK PER 61G1-16.004 FAC.
  