Plan Review Notes
Plan Review Notes For Permit 07030973
Permit Number 07030973
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-03 12:00:47 
  
  
 NONCOMPLIANT
  
 1} THE ARHCHITECTS SEAL ON THE PLANS SUBMITTED IS NOT
 AN "IMPRESSION TYPE" AS REQUIRED BY ARTICLE
 481.221FLORIDA STATUTES.
  
 2} THE TITLE BLOCK FOR THE DESIGNER OF RECORD MUST
 CONTAIN A CERTIFICATE OF AUTHORIZATION PER F.A.C.
  
 3} THE DISCONNECTS MUST BE GROUPED PER 230.72. IN THIS
 CASE ALL IN THE SAME ROOM. A METER OUTSIDE WITH THE
 EXISTING ONE AND A NIPPLE TO A NEW 200 AMP DISCONNECT
 WOULD MEET THIS REQUIREMENT. PLEASE INDICATE COMPLIANCE
 ON THE PLANS.
  
 4} CHANGE THE DESCRIPTION OF THE PROJECT ON THE
 APPLICATION TO MATCH THE WORK INTENDED. SEE " SERVICE
 UPGRADE-----", THIS IS ADDING TO SERVICE.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  