2007-04-18 13:24:56DENIED;
  
 1.PAGE LS-1 (APPLICABLE CODES) THE BUILDING IS
 SEPERATED INTO TWO OCCUPANCY CLASSIFICATIONS, EACH
 OCCUPANCY MUST MEET FBC- 2004 PLUMBING CODE TABLE
 403.1. A DRINKING FOUNTAIN IS REQUIRED IN THE OFFICE
 AREA.
 2. PAGE P-1.1 ( WATER RISER DIAGRAM) WATER HAMMER
 ARRESTORS ARE REQUIRED IN KITCHEN, PER SECTION 604.9.
 PLEASE SHOW ON PLANS AND SPEC OUT TYPE TO BE USED.
 3. PAGE P-1.1 PLUMBING FIXTURES, SK-2 KITCHEN SINK MUST
 MEET THE HANDICAP CODE SECTION 11-4.24.4 DEPTH OF SINK
 TO BE NO DEEPER THAN 6 1/2 INCH. THE FAUSET MUST BE
 LEVER TYPE, SECTION 11-4.24.7. GARBAGE DISPOSER CAN NOT
 INTERFERE WITH THE KNEE SPACE REQUIRED PER SECTION
 11-4.24.3. A INTERIOR DESIGNER MAY NOT COMPLY WITH THE
 HANDICAP CODE, THIS WOULD CAUSE NON-COMPLIANCE TO THE
 CODE REQUIREMENTS.
 4. THE BATHROOMS ARE NOT PRIVATE. MORE THAN ONE PERSON
 WILL BE USING THE BATHROOMS. SEE SECTION 11-4.1.3(11).
 PAGE A-5 DETAIL 17, MISSING TOTLE WIDTH OF BATHROOM
 SHOW TOILET AT 18" OF SIDE WALL SEE FIGURE 28 IN H/C
 CODE. GRAB BARS ARE REQUIRED.
 5. WALL AND FLOOR FINISHES NOT FOUND ON PLANS FOR
 BATHROOM WALLS AND FLOOR.