Plan Review Notes
Plan Review Notes For Permit 07030949
Permit Number 07030949
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-05-03 18:14:24*****DENIED*****
  
  
  
 1.IS THE BUILDING CLASSIFIED AS A COMBINED BUSINESS
 OCCUPANCY AND PARKING STRUCTURE COMPLYING WITH 38.1.2
 OF NFPA 101, LIFE SAFETY CODE, 2003 EDITION?
  
 2.PROVIDE THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 3.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A OR CLASS B IN EXITS AND IN EXIT ACESS
 CORRIDORS, AND CLASS A, CLASS B, OR CLASS C IN ALL
 OTHER SPACES.
  
 4.IT IS SHOWN ON SHEET E1-1 THAT THERE IS AN EXIT
 DOOR LEADING TO THE STORAGE/WAREHOUSE/PARKING AREA.IS
 THIS AREA CONSIDERED TO BE MORE HAZARDOUS THAN THE
 BUSINESS AREA FROM WHENCE THEY'RE EXITING?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722