Plan Review Notes For Permit 07030949 |
Permit Number |
07030949 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-04-16 07:51:04 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | 1} ELECTRICAL NOTE #1 INCORRECTLY LISTS THE 2002 NEC, | | THE 2005 NEC WAS ADOPTED 8 DECEMBER 2006, ALSO THE 2006 | | REVISIONS TO THE FBC. PLEASE CORRECT NOTE. | | | | 1} PANEL "P2" IS SHOWN IN ROOM 116 AND ROOM 101. PLEASE | | CORRECT THE NUMBERS. | | | | 2} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW | | VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE | | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE | | DISTINGUISHED FROM ALL OTHERS." NEW INTENT IN THE 2005 | | NEC. | | | | 3} THE MOTION SENSORS INDICATED ON E-2.1 FLOOR PLAN AND | | NOTE, DO NOT INDICATE WHEN THEY TIME OFF, SEE | | 13-415.ABC.1.2A(FOR 30 MINUTES). | | | | 4} THE INPUT DATA REPORT, PAGES 2 & 3 IN THE ENERGY | | CALCS SUBMITTED, DOES NOT CORRELATE TO THE DENSITY | | CALCULATIONS ON SHEET E-1.1 OF THE PLAN. IT LISTS ONE | | LUMINAIR WITH A MANUAL ON OFF, FOR ALL AREAS. | | ALSO THE FIXTURES LISTED DO NOT MATCH THE FIXTURE | | SCHEDULE ON THE PLAN. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|