Plan Review Notes
Plan Review Notes For Permit 07030933
Permit Number 07030933
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-04-04 11:06:45*****DENIED*****
  
  
 1.ON SHEET T101 UNDER APPLICABLE CODES, REFERENCES
 SHALL BE MADE TO:(1)FLORIDA FIRE PREVENTION CODE
 2004 EDITION(2) NFPA 101, LIFE SAFETY CODE, 2003
 EDITION.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FORM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING SUPPLIES & MATERIALS SHALL NOT INTERFERE
 OR HINDER WITH ACCESS TO OR EGRESS FROM THE PROPERTY OR
 VICINITY THEREOF (INCLUDING STREETS, ROADS, AND FIRE
 LANES).
  
 5.DEMOLITION OPERATIONS INVOLVING THE USE OF CUTTING
 AND WELDING SHALL BE DONE IN ACCORDANCE WITH NFPA 51B
  
 6.WHEN/IF IT IS NECESSARY TO SHUT DOWN THE FIRE
 PROTECTION SYSTEM, THE FIRE DEPARTMENT WILL BE NOTIFIED
 WHEN IT IS SHUT DOWN AND WHEN IT IS RETURNED TO
 SERVICE.
  
 7.ALL REQUIRED EXIT COMPONENTS WITHIN THE STRUCTURE
 SHALL BE MAINTAINED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH ITEM
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722