Plan Review Notes
Plan Review Notes For Permit 07030932
Permit Number 07030932
Review Stop E
Sequence Number 9
Notes
Date Text
2008-07-18 11:24:00** DENIED **
  
 ** REVISIONS SUBMITTED.
 SOME SHEETS ARE OK HOWEVER SHEET E2.2 HAS NOTES BELOW.
 RESPONSE LETTER FROM DESIGNER MENTIONS A SHEET 3.2
 HOWEVER NO SHEET 3.2 WAS SUBMITTED.
 SHEETS 4.1,4.2 AND 6.2 OK
  
 1) NOTE: PLEASE SEE NEW NOTE #12 ON 2.2 WHICH STATES
 LIGHTING CONTROLS/SYSTEM BY OTHERS HOWEVER TO DATE NO
 PLANS OR PERMIT APPLICATION HAS BEEN SUBMITTED. IF THE
 LIGHTING CONTROLS ARE GOING TO BE BY OTHER THEN PLANS
 WILL NEED TO BE SUBMITTED ALONG WITH PERMIT
 APPLICATION.
 13-415.1.ABC.1.1,.1.2,.1.3.
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  