2008-07-18 11:24:00 | ** DENIED ** |
| |
| ** REVISIONS SUBMITTED. |
| SOME SHEETS ARE OK HOWEVER SHEET E2.2 HAS NOTES BELOW. |
| RESPONSE LETTER FROM DESIGNER MENTIONS A SHEET 3.2 |
| HOWEVER NO SHEET 3.2 WAS SUBMITTED. |
| SHEETS 4.1,4.2 AND 6.2 OK |
| |
| 1) NOTE: PLEASE SEE NEW NOTE #12 ON 2.2 WHICH STATES |
| LIGHTING CONTROLS/SYSTEM BY OTHERS HOWEVER TO DATE NO |
| PLANS OR PERMIT APPLICATION HAS BEEN SUBMITTED. IF THE |
| LIGHTING CONTROLS ARE GOING TO BE BY OTHER THEN PLANS |
| WILL NEED TO BE SUBMITTED ALONG WITH PERMIT |
| APPLICATION. |
| 13-415.1.ABC.1.1,.1.2,.1.3. |
| |
| IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |