2008-03-27 09:22:16PG M2.1 REV 7 DENIED:
  
 1. THE 14X12 DUCT FROM VAV 15-24 IS PENETRATING A FIRE
 RESISTANCE RATED WALL AT ROOM 1544 WITHOUT OPENING
 PROTECTIVE. SHOW HOW THIS DUCT PENETRATION IS TO BE
 PROTECTED IN ACCORDANCE WITH FBCM 607.5.
  
 2. THE 14X12 DUCT FROM VAV 15-4 IS CROSSING A FIRE
 RESISTANCE RATED WALL AT ROOM 1574 WITHOUT OPENING
 PROTECTIVE. SHOW HOW THIS DUCT PENETRATION OF A RATED
 ASSEMBLY WILL BE PROTECTED IN ACCORDANCE WITH FBCM
 607.5.
  