Plan Review Notes For Permit 07030932 |
Permit Number |
07030932 |
|
Review Stop |
M |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2008-03-27 09:22:16 | PG M2.1 REV 7 DENIED: | | | | 1. THE 14X12 DUCT FROM VAV 15-24 IS PENETRATING A FIRE | | RESISTANCE RATED WALL AT ROOM 1544 WITHOUT OPENING | | PROTECTIVE. SHOW HOW THIS DUCT PENETRATION IS TO BE | | PROTECTED IN ACCORDANCE WITH FBCM 607.5. | | | | 2. THE 14X12 DUCT FROM VAV 15-4 IS CROSSING A FIRE | | RESISTANCE RATED WALL AT ROOM 1574 WITHOUT OPENING | | PROTECTIVE. SHOW HOW THIS DUCT PENETRATION OF A RATED | | ASSEMBLY WILL BE PROTECTED IN ACCORDANCE WITH FBCM | | 607.5. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|