Date |
Text |
2007-09-12 17:59:50 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. ALL SHEETS. THE BUSINESS NUMBER FOR "YJ |
| ARCHITECTURAL DESIGN" IS REQUIRED IN THE TITLE BLOCK. |
| FAC 61G1-16.004(2) & FS 481.219, 481.2055. |
| ****NO RESPONSE, NOT ADDRESSED. THE FLORIDA STATE DBPR |
| FIRM LICENSE NUMBER IS REQUIRED. |
| |
| 2. SHT 1-16.C PER TABLE 403.1 3 DRINKING FOUNTAINS ARE |
| REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING |
| FOUNTAIN. |
| ****RESPONSE NOTED, BUT ON THE 16TH FLOOR PLAN, ONE |
| DRINKING FOUNTAIN HAS SANITARY, BUT NO WATER SUPPLY & |
| ONE DRINKING FOUNTAIN SHOWS NO SANITARY OR WATER |
| SUPPLY. WATER AND DRAINAGE ARE REQUIRED AT EACH |
| FIXTURE. SECTIOND 301.3 & 301.4. |
| |
| 3. SHT 1-16.C BATHROOM (1608) SHALL BE ACCESSIBLE OR |
| ADAPTABLE PER SECTIONS 11-4.22 OR 11-4.1.3(11). PLEASE |
| SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS |
| 11-4.16, 11-4.19 & 11-4.21 WITH ALL SUBSECTIONS IF |
| BATHROOM IS TO BE ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| ALL BACKING FOR GRAB BARS FOR THE W/C & SHOWER, SPACING |
| FOR THE W/C, (MIN. 33" WITH THE W/C BEING 18" OFF THE |
| WALL AND MIN. 15" OFF THE SHOWER), A TURNING AREA IN |
| THE BATHROOM, THE VALVE LOCATION FOR THE SHOWER, AND A |
| CURB DETAIL OF THE SHOWER, (MAX 1/2"). |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 4. SHT 1-16.C THE SINKS IN ROOMS 1613, 1628, 1633, 1643 |
| & 1656 SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL |
| SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| SUBSECTIONS. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 5. SHT 1-16.C MORE INFORMATION IS REQUIRED FOR THE |
| PLANTERS. PLEASE INDICATE IF THE PLANTERS WILL HAVE |
| WATER SUPPLY OR DRAINAGE CONNECTED TO THEM. SECTION |
| 106.1.2. IF SO THE DRAINAGE PIPING & SUPPLY PIPING |
| SHALL BE SHOWN ON THE FLOOR PLANS AND ON THE RISER |
| DIAGRAMS. SECTION 106.3.5.1.3. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 6. OK |
| |
| 7. SHT 1-16.C ROOMS 1613 & 1628. PLEASE INDICATE THE |
| FIXTURE TYPE, (BS), IN EACH ROOM. SECTION 106.1.2. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 8. SUBMIT DETAILS FOR THE MEN'S & WOMEN'S TOILET ROOMS |
| SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17, |
| 11-4.18, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. ****NO |
| RESPONSE, NOT ADDRESSED.--THIS SHALL APPLY FOR THE |
| NEW TOILET ROOMS ADDED TO EACH FLOOR ALSO. |
| |
| 9. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING |
| FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 WILL |
| ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) |
| PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| STOOPING. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 10. OK |
| 11. OK |
| |
| 12. SHT 1-15.C THE SINK IN ROOM 1520SHALL BE |
| ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE |
| WITH SECTION 11-4.24 AND ALL SUBSECTIONS. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 13. SHT S-1 SHALL BE SEALED WITH AN EMBOSSED OR |
| IMPRESSION TYPE SEAL. NAIM & ASSOCIATES SHALL INDICATE |
| THEIR BUSINESS NUMBER, (CERTIFICATE OF AUTHORIZATION), |
| IN THE TITLE BLOCK. A PROFESSIONAL ENGINEER SHALL SIGN |
| HIS NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| SPECIFICATIONS, REPORTS AND FINAL BID DOCUMENTS |
| PROVIDED TO THE OWNER OR THE OWNER'S REPRESENTATIVE, OR |
| OTHER DOCUMENTS PREPARED OR ISSUED BY SAID REGISTRANT |
| AND BEING FILED FOR PUBLIC RECORD. THE DATE THAT THE |
| SIGNATURE AND SEAL IS AFFIXED AS PROVIDED HEREIN SHALL |
| BE ENTERED ON SAID PLANS, SPECIFICATIONS, REPORTS, OR |
| OTHER DOCUMENTS IMMEDIATELY UNDER THE SIGNATURE OF THE |
| PROFESSIONAL |
| ENGINEER, FAC 61G15-23.002(1) FS 471.025. ENGINEERS |
| SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS AND LICENSE |
| NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY |
| AUTHORIZED ENGINEERING BUSINESS, ENGINEERS, ENGINEERS |
| SHALL LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, |
| AS WELL AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS ON |
| EACH SHEET. A TITLE BLOCK WILL SATISFY THIS |
| REQUIREMENT. (THE CERTIFICATE OF AUTHORIZATION IS NOT |
| INDICATED IN THE TITLE BLOCK).FAC 61G15-23.002(2) - |
| FS 471.025.--PLANS APPEAR TO BE SIGNED WITH |
| INITIALS. INITIALS ARE NOT APPROVED, THE LEGAL |
| SIGNATURE IS REQUIRED. IF INDEED THIS IS THE LEGAL |
| SIGNATURE, A SIGNED, SEALED, NOTORIZED LETTER SHALL BE |
| SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR |
| FILES. |
| ****NO RESPONSE, NOT ADDRESSED. --NEW SHEET S-2 SHALL |
| MEET THE SAME REQUIREMENTS. S-2 NOT SIGNED, SEALED, |
| DATED ETC. |
| |
| 14. OK |
| 15. OK |
| 16. OK |
| 17. OK |
| 18. OK |
| 19. OK |
| 20. OK |
| |
| 21. SHT P2.2 NOTE INDICATES PLUMBING FIXTURE SCHEDULE |
| PROVIDED BY THE ARCHITECT. NO FIXTURE SCHEDULE HAS BEEN |
| LOCATED, AND NOTHING TO INDICATED WHAT FIXTURE "BS" |
| REPRESENTS.( SEE ROOMS 1613 & 1628).PLEASE INDICATE |
| WHERE THE FIXTURE SCHEDULE CAN BE FOUND. SECTION |
| 106.1.2. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 22. OK |
| |
| 23. SHT P3.1 PLEASE INDICATE WHAT THE COLD WATER LINE |
| TO ROOM 1544 CONNECTS TO. PER SECTION 608, BACKFLOW |
| PROTECTION MAY BE REQUIRED. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO |
| INDICATION AS TO WHAT THE COLD WATER LINE CONNECTS TO. |
| ALSO NO DRAIN SHOWN. PLEASE CLARIFY. SECTION 106.1.1. |
| |
| 24. OK |
| |
| 25. SHT P3.2 BACKFLOW PREVENTION IS REQUIRED ON THE |
| COLD WATER SUPPLY TO THE WATER WALL. PLEASE INDICATE |
| METHOD. SECTION 608. |
| ****RESPONSE NOTED, BUT CHECK VALVES ARE NOT APPROVED. |
| SEE TABLE 608.1.--A VACUUM BREAKER INSTALLED AT THE |
| HIGHEST POINT OF THE SUPPLY LINE TO THE WATER WALL IS |
| REQUIRED. (A WATTS MODEL N-36 OR EQUAL IS REQUIRED). |
| |
| 26. OK |
| 27. OK |
| 28. OK |
| |
| 29. SHT P51 THERMAL EXPANSION CONTROL IS REQUIRED FOR |
| THE WATER HEATERS ON THE 15TH & 16TH FLOORS. PLEASE |
| INDICATE THE METHOD OF CONTROL. SECTION 607.3.2. |
| ****RESPONSE NOTED, BUT CALCULATIONS SHALL BE PROVIDED |
| SHOWING THE CORRECT SIZE REQUIRED FOR 130 GALLONS, |
| (TOTAL OF BOTH WATER HEATERS). SEE ATTACHED SHEET FOR |
| AN EXAMPLE OF CALCULATIONS. INDICATE MANUF. AND MODEL |
| WHEN SUMBITTING CALCULATIONS. |
| |
| 30. OK |
| 31. OK |
| |
| ***********NEW COMMENTS*********** |
| |
| 1B. SHT P61 UPON REVIEW OF THE WATER RISER DIAGRAM FOR |
| THE 15TH FLOOR, POTABLE WATER IS SHOWN TO A/C UNITS. |
| THIS IS NOT APPROVED. PLEASE CLARIFY THE USE FOR THE |
| WATER TO AN A/C UNIT SECTION 106.1.1.--PER 2003 |
| NFPA-75 SECTION 5.2* & A.5.2 WATER SHOULD NOT BE IN THE |
| SPACE ABOVE THE SUSPENDED CEILING AND OVER INFORMATION |
| TECHNOLOGY EQUIPMENT OTHE THAN FOR SPRINKLER SYSTEM |
| USE. |
| |
| 2B. SHT P61 DELETE THE CHECK VALVES FROM THE WATER |
| RISER DIAGRAMS WHERE THE TOILET ROOMS 1573/1581 & |
| 1663/1665 CONNECT TO THE WATER RISER OR ANY OTHER |
| LOCATION ON THE RISER DIAGRAM. CHECK VALVES ARE NOT |
| APPROVED FOR BACKFLOW PREVENTION. TABLE 608.1. |
| |
| 3B. SHT P0.1 DETAIL FOR THE PLATFORM MOUNTED WATER |
| HEATERS. THE 80 GALLON EWH-2 WILL HAVE A TOTAL WEIGHT |
| APPROX. 850 LBS. PLEASE SUBMIT INFORMATION ON THE |
| SUPPORT FOR THE PLATFORM ATTACHMENT TO THE WALL. WILL |
| THE STUDS BEHIND THE WALL BE STRUCTURAL STUDS OR |
| DRYWALL STUDS. PLEASE INDICATE THE GUAGE OF THE STUDS |
| AND THE SIZE OF THE BLOCKING THAT THE PLATFORM ANGLE |
| BRACKETS WILL ATTACH TO. THIS INFORMATION SHOULD BE |
| SUBMITTED BY THE STRUCTURAL ENGINEER. SECTION 106.1.2. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |