Plan Review Notes
Plan Review Notes For Permit 07030932
Permit Number 07030932
Review Stop P
Sequence Number 2
Notes
Date Text
2007-09-12 17:59:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. ALL SHEETS. THE BUSINESS NUMBER FOR "YJ
 ARCHITECTURAL DESIGN" IS REQUIRED IN THE TITLE BLOCK.
 FAC 61G1-16.004(2) & FS 481.219, 481.2055.
 ****NO RESPONSE, NOT ADDRESSED. THE FLORIDA STATE DBPR
 FIRM LICENSE NUMBER IS REQUIRED.
  
 2. SHT 1-16.C PER TABLE 403.1 3 DRINKING FOUNTAINS ARE
 REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING
 FOUNTAIN.
 ****RESPONSE NOTED, BUT ON THE 16TH FLOOR PLAN, ONE
 DRINKING FOUNTAIN HAS SANITARY, BUT NO WATER SUPPLY &
 ONE DRINKING FOUNTAIN SHOWS NO SANITARY OR WATER
 SUPPLY. WATER AND DRAINAGE ARE REQUIRED AT EACH
 FIXTURE. SECTIOND 301.3 & 301.4.
  
 3. SHT 1-16.C BATHROOM (1608) SHALL BE ACCESSIBLE OR
 ADAPTABLE PER SECTIONS 11-4.22 OR 11-4.1.3(11). PLEASE
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.21 WITH ALL SUBSECTIONS IF
 BATHROOM IS TO BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 ALL BACKING FOR GRAB BARS FOR THE W/C & SHOWER, SPACING
 FOR THE W/C, (MIN. 33" WITH THE W/C BEING 18" OFF THE
 WALL AND MIN. 15" OFF THE SHOWER), A TURNING AREA IN
 THE BATHROOM, THE VALVE LOCATION FOR THE SHOWER, AND A
 CURB DETAIL OF THE SHOWER, (MAX 1/2").
 ****NO RESPONSE, NOT ADDRESSED.
  
 4. SHT 1-16.C THE SINKS IN ROOMS 1613, 1628, 1633, 1643
 & 1656 SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 5. SHT 1-16.C MORE INFORMATION IS REQUIRED FOR THE
 PLANTERS. PLEASE INDICATE IF THE PLANTERS WILL HAVE
 WATER SUPPLY OR DRAINAGE CONNECTED TO THEM. SECTION
 106.1.2. IF SO THE DRAINAGE PIPING & SUPPLY PIPING
 SHALL BE SHOWN ON THE FLOOR PLANS AND ON THE RISER
 DIAGRAMS. SECTION 106.3.5.1.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. OK
  
 7. SHT 1-16.C ROOMS 1613 & 1628. PLEASE INDICATE THE
 FIXTURE TYPE, (BS), IN EACH ROOM. SECTION 106.1.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 8. SUBMIT DETAILS FOR THE MEN'S & WOMEN'S TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17,
 11-4.18, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. ****NO
 RESPONSE, NOT ADDRESSED.--THIS SHALL APPLY FOR THE
 NEW TOILET ROOMS ADDED TO EACH FLOOR ALSO.
  
 9. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 WILL
 ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ****NO RESPONSE, NOT ADDRESSED.
  
 10. OK
 11. OK
  
 12. SHT 1-15.C THE SINK IN ROOM 1520SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 13. SHT S-1 SHALL BE SEALED WITH AN EMBOSSED OR
 IMPRESSION TYPE SEAL. NAIM & ASSOCIATES SHALL INDICATE
 THEIR BUSINESS NUMBER, (CERTIFICATE OF AUTHORIZATION),
 IN THE TITLE BLOCK. A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER'S REPRESENTATIVE, OR
 OTHER DOCUMENTS PREPARED OR ISSUED BY SAID REGISTRANT
 AND BEING FILED FOR PUBLIC RECORD. THE DATE THAT THE
 SIGNATURE AND SEAL IS AFFIXED AS PROVIDED HEREIN SHALL
 BE ENTERED ON SAID PLANS, SPECIFICATIONS, REPORTS, OR
 OTHER DOCUMENTS IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) FS 471.025. ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS AND LICENSE
 NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGINEERS, ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER,
 AS WELL AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET. A TITLE BLOCK WILL SATISFY THIS
 REQUIREMENT. (THE CERTIFICATE OF AUTHORIZATION IS NOT
 INDICATED IN THE TITLE BLOCK).FAC 61G15-23.002(2) -
 FS 471.025.--PLANS APPEAR TO BE SIGNED WITH
 INITIALS. INITIALS ARE NOT APPROVED, THE LEGAL
 SIGNATURE IS REQUIRED. IF INDEED THIS IS THE LEGAL
 SIGNATURE, A SIGNED, SEALED, NOTORIZED LETTER SHALL BE
 SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR
 FILES.
 ****NO RESPONSE, NOT ADDRESSED. --NEW SHEET S-2 SHALL
 MEET THE SAME REQUIREMENTS. S-2 NOT SIGNED, SEALED,
 DATED ETC.
  
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
  
 21. SHT P2.2 NOTE INDICATES PLUMBING FIXTURE SCHEDULE
 PROVIDED BY THE ARCHITECT. NO FIXTURE SCHEDULE HAS BEEN
 LOCATED, AND NOTHING TO INDICATED WHAT FIXTURE "BS"
 REPRESENTS.( SEE ROOMS 1613 & 1628).PLEASE INDICATE
 WHERE THE FIXTURE SCHEDULE CAN BE FOUND. SECTION
 106.1.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 22. OK
  
 23. SHT P3.1 PLEASE INDICATE WHAT THE COLD WATER LINE
 TO ROOM 1544 CONNECTS TO. PER SECTION 608, BACKFLOW
 PROTECTION MAY BE REQUIRED.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO
 INDICATION AS TO WHAT THE COLD WATER LINE CONNECTS TO.
 ALSO NO DRAIN SHOWN. PLEASE CLARIFY. SECTION 106.1.1.
  
 24. OK
  
 25. SHT P3.2 BACKFLOW PREVENTION IS REQUIRED ON THE
 COLD WATER SUPPLY TO THE WATER WALL. PLEASE INDICATE
 METHOD. SECTION 608.
 ****RESPONSE NOTED, BUT CHECK VALVES ARE NOT APPROVED.
 SEE TABLE 608.1.--A VACUUM BREAKER INSTALLED AT THE
 HIGHEST POINT OF THE SUPPLY LINE TO THE WATER WALL IS
 REQUIRED. (A WATTS MODEL N-36 OR EQUAL IS REQUIRED).
  
 26. OK
 27. OK
 28. OK
  
 29. SHT P51 THERMAL EXPANSION CONTROL IS REQUIRED FOR
 THE WATER HEATERS ON THE 15TH & 16TH FLOORS. PLEASE
 INDICATE THE METHOD OF CONTROL. SECTION 607.3.2.
 ****RESPONSE NOTED, BUT CALCULATIONS SHALL BE PROVIDED
 SHOWING THE CORRECT SIZE REQUIRED FOR 130 GALLONS,
 (TOTAL OF BOTH WATER HEATERS). SEE ATTACHED SHEET FOR
 AN EXAMPLE OF CALCULATIONS. INDICATE MANUF. AND MODEL
 WHEN SUMBITTING CALCULATIONS.
  
 30. OK
 31. OK
  
 ***********NEW COMMENTS***********
  
 1B. SHT P61 UPON REVIEW OF THE WATER RISER DIAGRAM FOR
 THE 15TH FLOOR, POTABLE WATER IS SHOWN TO A/C UNITS.
 THIS IS NOT APPROVED. PLEASE CLARIFY THE USE FOR THE
 WATER TO AN A/C UNIT SECTION 106.1.1.--PER 2003
 NFPA-75 SECTION 5.2* & A.5.2 WATER SHOULD NOT BE IN THE
 SPACE ABOVE THE SUSPENDED CEILING AND OVER INFORMATION
 TECHNOLOGY EQUIPMENT OTHE THAN FOR SPRINKLER SYSTEM
 USE.
  
 2B. SHT P61 DELETE THE CHECK VALVES FROM THE WATER
 RISER DIAGRAMS WHERE THE TOILET ROOMS 1573/1581 &
 1663/1665 CONNECT TO THE WATER RISER OR ANY OTHER
 LOCATION ON THE RISER DIAGRAM. CHECK VALVES ARE NOT
 APPROVED FOR BACKFLOW PREVENTION. TABLE 608.1.
  
 3B. SHT P0.1 DETAIL FOR THE PLATFORM MOUNTED WATER
 HEATERS. THE 80 GALLON EWH-2 WILL HAVE A TOTAL WEIGHT
 APPROX. 850 LBS. PLEASE SUBMIT INFORMATION ON THE
 SUPPORT FOR THE PLATFORM ATTACHMENT TO THE WALL. WILL
 THE STUDS BEHIND THE WALL BE STRUCTURAL STUDS OR
 DRYWALL STUDS. PLEASE INDICATE THE GUAGE OF THE STUDS
 AND THE SIZE OF THE BLOCKING THAT THE PLATFORM ANGLE
 BRACKETS WILL ATTACH TO. THIS INFORMATION SHOULD BE
 SUBMITTED BY THE STRUCTURAL ENGINEER. SECTION 106.1.2.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved