2007-09-20 07:03:35 | 525 OKEECHOBEE BLVD |
| INTECH |
| SEPT.19, 2007 |
| |
| |
| BUILDING PLAN REVIEW |
| PERMIT: 07030932 |
| ADD: 525 OKEECHOBEE BLVD PENTHOUSE A & B |
| CONT: CENTEX/ BALFOUR BEATTY |
| TEL: (954)214-9415 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) NOTE IN SOME TITLE BLOCKS THERE IS YCJ DESIGN AND |
| OTHER TITLE BLOCKS YJ ARCHITECTURAL DESIGNS ( YOUSEF |
| JALALI) , PLEASE SEE THE FOLLOWING FLORIDA STATUTES FOR |
| ARCHITECTS AND INTERIOR DESIGNERS: |
| |
| 3A)Y J ARCHITECTURAL DESIGN WILL REQUIRE A |
| CERTIFICATE OF AUTHORIZATION, FLORIDA STATE STATUTE |
| 481.219(2) (ARCHITECT),THE TITLE BLOCK FOR ANY |
| SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER |
| A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP, |
| OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE |
| CERTIFICATE OF AUTHORIZATION NUMBER. |
| |
| 3B) YCJ DESIGN, FLORIDA S. S. 481.219(3)(INTERIOR |
| DECORATORS)FOR THE PURPOSES OF THIS SECTION, A |
| CERTIFICATE OF AUTHORIZATION SHALL BE REQUIRED FOR A |
| CORPORATION, LIMITED LIABILITY COMPANY, PARTNERSHIP, OR |
| PERSON OPERATING UNDER A FICTITIOUS NAME, OFFERING |
| INTERIOR DESIGN SERVICES TO THE PUBLIC JOINTLY OR |
| SEPARATELY. HOWEVER, WHEN AN INDIVIDUAL IS PRACTICING |
| INTERIOR DESIGN IN HER OR HIS OWN NAME, SHE OR HE SHALL |
| NOT BE REQUIRED TO BE CERTIFIED UNDER THIS SECTION. |
| |
| 3C) PLEASE SEE FLORIDA STATE STATUTE 481.2131 (INTERIOR |
| DESIGNERS) PRACTICE REQUIREMENTS; DISCLOSURE OF |
| COMPENSATION FOR PROFESSIONAL SERVICES. |
| |
| 3D) THE CONSULTING STRUCTURAL ENGINEER NAIM& ASSOCIATES |
| ARE THE ONLY STRUCTURAL ENGINEERING FIRM LISTED ON THE |
| SHEET, NO INDIVIDUAL ENGINEER HAS SIGNED AND SEALED THE |
| PLANS.FLORIDA |
| ADMINISTRATIVE CODE 61G15-23.002(2) |
| |
| 3E) ) 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED & |
| SEALED BY A PROFESSIONAL ENGINEER |
| SHALL INCLUDE EITHER: |
| - THE NAME,ADDRESS AND LICENSE NUMBER OF THE ENGINEER |
| OR, |
| - THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE |
| NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER |
| OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER |
| IS PRACTICING |
| (471.025 F.S. AND471.023 F.S.). |
| |
| 4)SECOND REQUEST, SHEET S-1 DOES NOT APPEAR IN THE |
| INDEX SHEET. STRUCTURAL SHEET S-1 WILL REQUIRE A RAISED |
| IMPRESSION TYPE SEAL NOT A STAMPED SEAL. FLORIDA |
| ADMINISTRATIVE CODE 61G15-23.001, THE DESIGN |
| PROFESSIONAL MUST BE A LICENSED ENGINEER IN THE STATE |
| OF FLORIDA. FL S. S.471.025. THE RESPONSE INDICATES |
| THAT THE STRUCTURAL SHEETS WILL HAVE A RAISED |
| IMPRESSION SEAL BY A LICENSED ENGINEER IN FLORIDA BUT |
| THIS SET OF PLANS THE CONSULTING STRUCTURAL ENGINEER |
| NAIM& ASSOCIATES ARE THE ONLY STRUCTURAL ENGINEERING |
| FIRM LISTED ON THE SHEET, NO INDIVIDUAL ENGINEER HAS |
| SIGNED AND SEALED THE PLANS. |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.002(2).PLANS |
| SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL |
| INCLUDE EITHER THE NAME, ADDRESS AND LICENSE NUMBER OF |
| THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE |
| ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF |
| AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS |
| THROUGH WHICH THE ENGINEER IS PRACTICING |
| |
| 5) SECOND REQUEST, THE SAME HOLDS TRUE FOR THE |
| CALCULATIONS SUBMITTED FOR THE STAIRS BETWEEN THE 15TH |
| & 16TH FLOOR. MUST BE A LICENSED ENGINEER FOR THE STATE |
| OF FLORIDA AND IF THE ENGINEER OF RECORD DOES NOT SEAL |
| EACH SHEET THEN A SEALED COVER SHEET LISTING HOW MANY |
| PAGES ARE COVERED UNDER THIS SEAL. 61G15-23.002. |
| |
| 6) COMPLIED. |
| |
| 7A) LS-01 THERE IS A DISCREPANCY IN FLOOR AREA FROM THE |
| LIFE SAFETY PLAN & THE ENERGY CALCS PLEASE CORRECT. |
| |
| 7B) LIFE SAFETY PLANS HAVE THE WRONG WIND CRITERIA |
| PLEASE CORRECT THE REFERENCE TO ASCE 7-98. |
| 8)COMPLIED. |
| |
| 9) COMPLIED. |
| |
| 10) SECOND REQUEST, SHEET 1-16C INDICATE TWO TYPE OF |
| DOORS THAT WILL BE PENETRATING THE 1 HR RATED WALL DOOR |
| TYPED-6 WHICH DOES HAVE 45 MINUTE RATING AND DOOR TYPE |
| D-3 WHICH DOES NOT PLEASE CORRECT. TABLE 715.3. |
| |
| 11) SECOND REQUEST, RESPONSE INDICATES THE NOTE IS |
| ADDED TO THE GENERAL NOTES NOT NUMBER 58, SHEET I-G.1 |
| THE GENERAL NOTES ONLY GO UP TO 44.PLEASE TAKE NOTE |
| OF : 404.7 INTERIOR FINISH. THE INTERIOR FINISH OF |
| WALLS AND CEILINGS OF THE ATRIUM SHALL NOT BE LESS THAN |
| CLASS B WITH NO REDUCTION IN CLASS FOR SPRINKLER |
| PROTECTION. |
| |
| 12) COMPLIED. |
| |
| 13-15) COMPLIED. |
| |
| 16) 2ND REQUEST, A FLORIDA REGISTERED ENGINEER, |
| PLEASE PROVIDE ADDITIONAL INFORMATION ON THE GLASS |
| HANDRAILS AND GUARDS SEE 2407. |
| 2407.1.1 LOADS. |
| THE PANELS AND THEIR SUPPORT SYSTEM SHALL BE DESIGNED |
| TO WITHSTAND THE LOADS SPECIFIED IN SECTION 1607.7 . A |
| SAFETY FACTOR OF FOUR SHALL BE USED. |
| |
| 2407.1.2 SUPPORT. |
| EACH HANDRAIL OR GUARD SECTION SHALL BE SUPPORTED BY A |
| MINIMUM OF THREE GLASS BALUSTERS OR SHALL BE OTHERWISE |
| SUPPORTED TO REMAIN IN PLACE SHOULD ONE BALUSTER PANEL |
| FAIL. GLASS BALUSTERS SHALL NOT BE INSTALLED WITHOUT AN |
| ATTACHED HANDRAIL OR GUARD. |
| |
| 17)COMPLIED. |
| |
| 18) SECOND REQUEST, THE RESPONSE SHEET INDICATES A NOTE |
| 59 WAS ADDED TO THE GENERAL COMMENTS? THE GLASS WALL IS |
| ALSO CONSIDERED A HAZARDOUS LOCATION 15TH AND 16TH |
| FLOORS. SEE 2406.3(7) |
| 7.GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE |
| PANEL, OTHER THAN IN THOSE LOCATIONS DESCRIBED IN |
| PRECEDING ITEMS 5 AND 6, WHICH MEETS ALL OF THE |
| FOLLOWING CONDITIONS: |
| 7.1.EXPOSED AREA OF AN INDIVIDUAL PANE GREATER |
| THAN 9 SQUARE FEET (0.84 M 2 ); |
| 7.2.EXPOSED BOTTOM EDGE LESS THAN 18 INCHES (457 |
| MM) ABOVE THE FLOOR; |
| 7.3.EXPOSED TOP EDGE GREATER THAN 36 INCHES (914 |
| MM) ABOVE THE FLOOR; AND |
| 7.4.ONE OR MORE WALKING SURFACE(S) WITHIN 36 |
| INCHES (914 MM) HORIZONTALLY OF THE PLANE OF THE |
| GLAZING. |
| EXCEPTION: SAFETY GLAZING FOR ITEM 7 IS NOT REQUIRED |
| FOR THE FOLLOWING INSTALLATIONS: |
| 1.A PROTECTIVE BAR 1? INCHES (38 MM) OR MORE IN |
| HEIGHT, CAPABLE OF WITHSTANDING A HORIZONTAL LOAD OF 50 |
| POUNDS PLF (730 N/M) WITHOUT CONTACTING THE GLASS, IS |
| INSTALLED ON THE ACCESSIBLE SIDES OF THE GLAZING 34 |
| INCHES TO 38 INCHES (864 MM TO 965 MM) ABOVE THE |
| FLOOR. |
| |
| 19-23B) COMPLIED. |
| |
| 24) A NEW COMMENT, E2.1 INDICATES WORK BEING COMPLETED |
| ON THE 17TH FLOOR AND E2.2 INDICATES THE 16TH FLOOR, |
| PLEASE CORRECT THIS DISCREPANCY. |
| |
| 25) A NEW COMMENT,I-15.C ROOMS 1543& 1544 BOTH ARE |
| INDICATED AS COMPUTER EQUIPMENT ROOMS SEE ELECTRICAL |
| COMMENTS AS TO THE 1 HR FIRE RATING REQUIREMENTS. |
| |
| 26) ENERGY CALCULATIONS PLEASE PROVIDE THE INFORMATION |
| FOR THE SKYLIGHTS TO BE INSTALLED ON THE |
| ROOF OF THE 16TH FLOOR. ADDITIONAL INFORMATION REQUIRED |
| 106.1.2* |
| 27) SHEET I-15.R PLEASE CORRECT THIS SHEET TITLE BLOCK |
| IT APPEARS WHITE OUT WAS USED IN THE TITLE BLOCK AND |
| THEN HAND DRAWN NUMERALS. |
| |
| 28) SHEETS S-1 AND S-2 INDICATE NEW STAIRS AND FLOOR |
| BEAMS COMMUNICATING BETWEEN THE FLOORS, AS PART OF A |
| THRESHOLD BUILDING THE FOLLOWING ITEMS WILL NEED TO BE |
| ADDRESSED: |
| |
| 28A)105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| A THRESHOLD BUILDING PURSUANT TO A "STRUCTURAL |
| INSPECTION PLAN" |
| PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| 28B) THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE |
| OF COMPLETION, THE STRUCTURAL PLANS FOR THIS TENANT |
| SPACE SHALL BE REVIEWED BY THE ENGINEER OF RECORD FOR |
| THE " BASE BUILDING" |
| AND BE STAMPED WITH THEIR SHOP DRAWING STAMP THEY ARE |
| APPROVING THE PLANS AND WORK TO BE COMPLETED UNDER THIS |
| PERMIT BEFORE THEIR CERTIFICATE OF COMPLETION HAS BEEN |
| ISSUED. |
| |
| 28C) THE SAME HOLDS TRUE FOR THE ARCHITECTURAL SHEETS, |
| THE DESIGNER OF RECORD FOR THE BUILDING SHALL REVIEW |
| AND AFFIX THEIR SHOP DRAWING STAMP TO THESE PLANS WITH |
| THEIR APPROVAL. |
| |
| 28D) SINCE THERE WILL NEED TO BE A THRESHOLD INSPECTOR |
| ON SITE, A THIRD SET OF PLANS, SUBMITTALS AND OR OTHER |
| DOCUMENTS WILL NEED TO BE SUBMITTED BEFORE ISSUANCE OF |
| THIS PERMIT. |
| |
| 28E) SINCE THE STEEL BEAMS ARE NEW ELEMENTS AND NEED TO |
| INDICATE FIRE PROOFING AS TO TABLE 601 FLOOR AND BEAM 3 |
| HR RATING SEE FOOTNOTE "G" 1 HR REDUCTION FOR FIRE |
| SPRINKLED BUILDINGS. |
| PLEASE SHOW COMPLIANCE. |
| |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| APPLICABLE. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| |
| |