Notes
Date Text
2007-08-27 15:20:21DENIED 3RD TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **OK**
  
 3. **OK**
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 4. SHEET A-2 ELEVATION DETAIL FOR THE DRINKING
 FOUNTAIN: THE ELEVATION DETAIL OF THE DRINKING FOUNTAIN
 DOES NOT INDICATE COMPLIANCE TO 11-4.3(10)(A) WHERE
 ONLY ONE DRINKING FOUNTAIN IS PROVIDED THERE SHALL BE A
 DRINKING FOUNTAIN WHICH IS ACCESSIBLE TO INDIVIDUALS
 WHO USE WHEELCHAIRS IN ACCORDANCE TO 11-4.15 AND ONE
 ACCESSIBLE TO THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING; OR BY SUCH OTHER MEANS AS WOULD ACHIEVE THE
 REQUIRED ACCESSIBILITY FOR EACH GROUP.
  
 5. SHEET A2.1 AND P-1 THE EMERGENCY SHOWER AND
 EYEWASH: PER FBC-2004 PLUMBING SECTION 411.2 WASTE
 CONNECTIONS SHALL NOT BE REQUIRED FOR EMERGENCY SHOWERS
 AND EYEWASH STATIONS. THE RESUBMITTED PLANS ARE
 INDICATING A 150/GAL NEUTRALIZATION TANK BEING
 INSTALLED WITH THIS EMERGENCY SHOWER AND EYEWASH
 STATION. PLEASE CLARIFY WHY THIS IS REQUIRED. ARE THERE
 CHEMICALS INVOLVED? IF THERE ARE CHEMICALS INVOVED WHAT
 ARE THEY?
 NOTE:PER FBC-2004 PLUMBING SECTION 301.3 CONNECTIONS TO
 THE SANITARY DRAINAGE SYSTEM. ALL PLUMBING FIXTURES,
 DRAINS, APPURTENANCES AND APPLIANCES USED TO RECIEVE OR
 DISCHARGE LIQUID WASTES (NEUTRALIZATION TANK) OR SEWAGE
 SHALL BE DIRECTLY CONNECTED TO THE SANITARY DRAINAGE
 SYSTEM OF THE BUILDING OR PREMISES.
  
 END OF COMMENTS:
  