Plan Review Notes For Permit 07030927 |
Permit Number |
07030927 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-06-04 09:59:38 | DENIED; | | 1.EMERGENCY EYE WASH AND SHOWER SHALL COMPLY WITH | | ISEA-Z358.1, PER SECTION 411.1 OF THE FBC PLUMBING | | CODE. SEND IN MANUFACTURE'S CUT SHEET THAT SHOWS | | COMPLIANCE TO ISEA STANDARDS. | | 2. WATER RISER DIAGRAM; SHUT OFF VALVE REQUIRED FOR BAY | | 10. WATER SUPPLY FOR EYE WASH AND EMERGENCY SHOWER ARE | | NOT SHOWN. WATER SUPPLY TO MEET MANUFACTURE | | INSTRUCTIONS. | | 3.SERVICE SINK REQUIRES HOT WATER FOR BUILDING | | MAINTENANCE. SECTION 607.1 | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|