2007-05-17 08:25:22 | ** UNSAT 2ND REVIEW ** |
| |
| ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| BY THE CITY OF WEST PALM BEACH. |
| |
| * PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING. |
| |
| |
| 1) NOTE: PLEASE SEE THE ADDRESS AS APPLIED STILL |
| INDICATES UNIT/SUITES 11&12, YET PLANS NOW CALL FOR |
| THIS SPACE TO BE UNIT 10? THIS WILL NEED TO BE GONE |
| OVER WITH THE ADDRESSING REVIEWER AND COORDINATE FINAL |
| UNIT/SUITE # AND MAKE ANY ADJUSTMENTS AS NEEDED. |
| |
| 2) NOTE: PLEASE SEE THAT NOT ENOUGH INFORMATION WAS |
| SUBMITTED FOR THE LIGHTING CONTROL PANEL. NO DETAILS, |
| NO INDICATION ON OVER RIDES AND TYPES PER CHAPTER 13. |
| PLEASE SEE 13-415.1.ABC.1.1 AS NO MORE THAN 30MINS IS |
| PERMITTED ON OCCUPANCY TYPE DEVICES. |
| PLEASE SEE PLANS CALL FOR ALL AT 4HRS WHICH IS NOT |
| PERMITTED. |
| PLEASE SEE NO SCHEDULING IS SHOWNON PLANS WHICH IS |
| REQUIRED TO BE PART OF THE RECORD SETFOR PROPOSED |
| SCOPE OF WORK. |
| PLEASE SEE 13-415 |
| |
| 3) NOTE: PLEASE SEE OCCUPANCY IS NOW BEING STATED ON |
| PLANS, HOWEVER EVEN AS NO PAINT SPRAY BOOTH IS SHOWN AT |
| THIS TIME AND NOT MENTIONED, THE SPACE STILL FALLS |
| UNDER 511 OF THE NEC. |
| PLEASE SPECIFY AREAS FOR CLASS AND DIVISIONS ON PLANS. |
| PLEASE INDICATE WIRING METHODS/INSTALLATIONS ETC PER |
| MINIMUM REQUIREMENTS IN THE NEC. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |