2007-04-04 12:19:06 | *****DENIED***** |
| |
| |
| 01.ON SHEET A1.0 UNDER CODE COMPLIANCE, REFERENCE (1) |
| FLORIDA FIRE PREVENTION CODE 2004 EDITION(2) NFPA |
| 101, LIFE SAFETY CODE, 2003 EDITION. |
| |
| 02.ON SHEET A1.0 UNDER GENERAL NOTES, NOTE #05, |
| CORRECT FIRE EXTINGUISHER RATING TO 2A-10BC INSTEAD OF |
| 210ABC. |
| |
| 03.THE COMPLETE ADDRESS INCLUDING THE SUITE NUMBER(S) |
| OF WHERE THE SCOPE OF WORK WILL BE CONDUCTED SHALL BE |
| IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. |
| |
| 04.PLEASE INDICATE EXISTING AND PROPOSED OCCUPANCY |
| CLASSIFICATION FOR THIS LOCATION. |
| |
| 05.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 06.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| |
| 07. THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF |
| NEW BUILDING SUPPLIES & MATERIALS SHALL NOT INTERFERE |
| OR HINDER WITH ACCESS TO OR EGRESS FROM THE PROPERTY OR |
| VICINITY THEREOF (INCLUDING STREETS, ROADS, AND FIRE |
| LANES). |
| |
| 08. OPERATIONS INVOLVING THE USE OF CUTTING AND WELDING |
| SHALL BE DONE IN ACCORDANCE WITH NFPA 51B. |
| |
| 09.WILL THE NEW DIMISING WALL IMPACT THE DISTRUBUTION |
| PATTERN OF THE FIRE SPRINKLER SYSTEM?IF SO, SEPARATE |
| PLANS AND PERMIT WILL BE REQUIRED FOR THE FIRE |
| SPRINKLER REMODEL. |
| |
| 10.WHEN/IF IT IS NECESSARY TO SHUT DOWN THE FIRE |
| PROTECTION SYSTEM, THE FIRE DEPARTMENT WILL BE NOTIFIED |
| WHEN IT IS SHUT DOWN AND WHEN IT IS RETURNED TO |
| SERVICE. |
| |
| 11.ALL REQUIRED EXIT COMPONENTS WITHIN THE STRUCTURE |
| SHALL BE MAINTAINED. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH ITEM |
| WAS ADDRESSED |
| |
| |