Plan Review Notes
Plan Review Notes For Permit 07030927
Permit Number 07030927
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-31 08:08:14 
 ****** UNSAT *****
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE OF FLORIDA
 BUILDING COMMISSION.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES. PLEASE SEE AT THIS TIME
 THE PLANS LIST A 2006 FBC IN SEVERAL LOCATIONS. THE
 STATE IS STILL UNDER THE 2004 FBC, AND ONLY ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC. PLEASE ADJUST.
 PLEASE LIST THE FOLLOWING ON SHEETS FOR THIS REVIEWER
 AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE STATE THE USE AND OCCUPANCY ON THIS
 SPACE/TENANT USE.
 PLEASE CLARIFY SUITE/UNIT # AS THE PLANS INDICATE TWO
 SUITE NUMBERS FOR WHAT IS BEING SHOWN AS THE SAME
 TENANT? SHOWS BOTH UNIT #11 AND #12.
  
 3) NOTE: PLEASE SEE 13-415.2 AS LIGHTING PERFORMANCE
 BASED ON THE USE IS STILL REQUIRED EVEN IF IN A NON
 CONDITIONED SPACE.
  
 4) NOTE: PLEASE CLARIFY THE PLANS WHICH INDICATE A
 LIGHTING CONTROL PANEL BEING INSTALLED WITH OVER RIDES
 HOWEVER PLANS DO NOT DETAIL THIS PANEL WITH THE OVER
 RIDE DEVICES AND THE PLANS ONLY INDICATE OCCUPANCY TYPE
 DEVICES. IF ONLY INCORPORATING OC TYPE DEVICES PLEASE
 CLARIFY.
 IF INSTALLING A LCP, PLEASE PROVIDE DETAIL/MORE
 INFORMATION FOR THIS.
 FBC 106.3.5.1.2
  
 5) NOTE: PLEASE SEE THE BATHROOMS ARE SHOWING TWO
 CIRCUITS THROUGH A SINGLE POINT OF USE FIXTURES? PLEASE
 SEE 210.4 AS ONE DEVICE BEING FED FROM MORE THAN ONE
 CIRCUIT REQUIRES THESE TO BE FED FROM A 2-POLE BREAKER.
 AS THESE ARE SHOWN ON CIRCUIT # 2 AND #6 ON PANEL
 SCHEDULE, THIS IS NOT POSSIBLE.
 PLEASE EITHER RELOCATE BRANCH BREAKERS AND PLACE ON TWO
 POLE BREAKER OR PERHAPS PLACE ON THE SAME CIRCUIT.
 FBC 106.3.5.1.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  