Plan Review Notes
Plan Review Notes For Permit 07030918
Permit Number 07030918
Review Stop E
Sequence Number 2
Notes
Date Text
2008-06-18 13:59:53 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON
 THE PLAN MUST SIGN AND SEAL THE PLAN PER
 481.221(1)(B)FS.
 THE DESIGNER OF RECORD IS THE ONLY PERSON AUTHORIZED TO
 REVISE HIS/HER PLAN. TAKE ALL PROPOSED CHANGES TO THE
 DESIGNER TO BE REDRAWN.
  
 PLEASE NOTE THAT HAND DRAWN CHANGES TO THE PLAN ARE NOT
 ACCEPTABLE AS THEY CANNOT BE VERIFIED AS BEING MADE BY
 THE DESIGNER OF RECORD AS REQUIRED BY FS 471 OR 481, AS
 APPLICABLE.
  
 2} THE ELECTRICAL PLANS ORIGINALLY SUBMITTED ARE A
 DIFFERENT FLOOR PLAN THAN IS NOW SUBMITTED RESUBMIT
 ELECTRICAL PLANS THAT THAT REFLECT THE SCOPE OF WORK
 INTENDED.IF THE ARCHITECT WHO DESIGNED THE SET
 SUBMITTED IS TO DO THE REVISED PLAN, IT MUST BE CLEAR.
 PLANS ARE REQUIRED TO BE DRAFTSMAN QUALITY. PLANS ARE
 REQUIRED TO CLEARLY INDICATE THE SCOPE OF WORK INTENDED
 IN THE DESCRIPTION ON THE APPLICATION, AND SUITABLE FOR
 RECORD RETENTION.
  
 3} THE PERMITTED ELECTRICAL PLAN INDICATED 925 SQUARE
 FOOT OF RESIDENCE. THE REVISION NOW SUBMITTED INDICATES
 1591 SQUARE FEET. INCREASE THE VALUE TO REFLECT THE
 ADDED LABOR AND MATERIAL. ADJUST THE VALUE AT THE
 PERMIT CLERKS DESK, AND PAY THE DIFFERENCE IN FEES
 PRIOR TO RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718