2008-06-18 13:59:53 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON |
| THE PLAN MUST SIGN AND SEAL THE PLAN PER |
| 481.221(1)(B)FS. |
| THE DESIGNER OF RECORD IS THE ONLY PERSON AUTHORIZED TO |
| REVISE HIS/HER PLAN. TAKE ALL PROPOSED CHANGES TO THE |
| DESIGNER TO BE REDRAWN. |
| |
| PLEASE NOTE THAT HAND DRAWN CHANGES TO THE PLAN ARE NOT |
| ACCEPTABLE AS THEY CANNOT BE VERIFIED AS BEING MADE BY |
| THE DESIGNER OF RECORD AS REQUIRED BY FS 471 OR 481, AS |
| APPLICABLE. |
| |
| 2} THE ELECTRICAL PLANS ORIGINALLY SUBMITTED ARE A |
| DIFFERENT FLOOR PLAN THAN IS NOW SUBMITTED RESUBMIT |
| ELECTRICAL PLANS THAT THAT REFLECT THE SCOPE OF WORK |
| INTENDED.IF THE ARCHITECT WHO DESIGNED THE SET |
| SUBMITTED IS TO DO THE REVISED PLAN, IT MUST BE CLEAR. |
| PLANS ARE REQUIRED TO BE DRAFTSMAN QUALITY. PLANS ARE |
| REQUIRED TO CLEARLY INDICATE THE SCOPE OF WORK INTENDED |
| IN THE DESCRIPTION ON THE APPLICATION, AND SUITABLE FOR |
| RECORD RETENTION. |
| |
| 3} THE PERMITTED ELECTRICAL PLAN INDICATED 925 SQUARE |
| FOOT OF RESIDENCE. THE REVISION NOW SUBMITTED INDICATES |
| 1591 SQUARE FEET. INCREASE THE VALUE TO REFLECT THE |
| ADDED LABOR AND MATERIAL. ADJUST THE VALUE AT THE |
| PERMIT CLERKS DESK, AND PAY THE DIFFERENCE IN FEES |
| PRIOR TO RESUBMITTING. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |