2007-05-24 12:53:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THE 2X6 RAIL DOES NOT COMPLY WITH GRASPABILITY
 REQUIREMENTS OF FBC R311.5.6.
  
 2.)A6 SHOWS THE HANDRAIL AT 28.5".SEE FBC R
 311.5.6.1, FBC R 312.1.
  
 3.)THE HANDRAIL IS TO BE CONTINUOUS, FBC R 311.5.6.2.
  
  
 4.)SHOW COMPLIANCE WITH STAIR ILLUMINATION
 REQUIREMENTS, FBC R 311.5.7.
  
 5.)SPECIFY DESIGN CRITERIA FOR THE HANDRAIL AND GUARD
 COMPONENTS, FBC R TABLE 301.5.
  
 6.)SHOW DIMENSIONS BETWEEN LANDINGS (VERTICAL), FBC R
 311.5.4.
  
 7.)B6, SHEET 2, SHOW LANDING DIMENSION FBC R
 311.5.4.
  
 8.)SHOW COMPLIANCE WITH FBC R 312.2, EXCEPTIONS.
  
 9.)THE ENGINEER'S SEAL IS NOT LEGIBLE.
 FAC61G15-23.002.
  