2007-04-07 12:58:44 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| |
| 1.)PROVIDE CALCULATIONS FOR THE CORNER AND PERIMETER |
| FASTENING SHOWING VALUE PER FASTENER PER SQUARE.THIS |
| WILL INCLUDE THE ROW AT THE LAP AS WELL AS THE FIELD |
| ROWS. |
| |
| IT IS NOT CLEAR WHETHER THE ROW FASTENING IS COMPLIANT |
| AS THEY WERE NOT ENHANCED IN THE SAME PROPORTION AS THE |
| FIELD ROWS, BUT THE RAS117 TAKES ALL ROWS INTO ACCOUNT, |
| NOT ONLY THE FIELD.THEREFORE, PROVIDE CALCULATIONS |
| SHOWING THAT THE VALUE PER FASTENER EXCEEDS THE VALUE |
| REQUIRED TO MEET THE PRESSURES SPECIFIED. |
| |
| 2.)PROVIDE SPECS FROM THE MANUFACTURER FOR THE BASE |
| SHEET SPECIFIED.NOTE THAT THE NOA DOES NOT INCLUDE |
| INFORMATION ON PRODUCTS THAT ARE NOT MANUFACTURED BY |
| POLYGLASS.THE FIRST SET OF ENGINEERING STATED THAT |
| THE SHEET HAD A 31INCH WIDTH, THIS ONE STATES THAT IT |
| IS 36INCHES.TO MY KNOWLEDGE THIS HAS ALWAYS HAD A |
| 39.4" SHEET WIDTH.PLEASE PROVIDE SPECIFICATIONS |
| SHOWING THE 36" WIDTH AS REQUESTED. |
| |