Plan Review Notes
Plan Review Notes For Permit 07030890
Permit Number 07030890
Review Stop B
Sequence Number 2
Notes
Date Text
2007-04-07 12:58:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)PROVIDE CALCULATIONS FOR THE CORNER AND PERIMETER
 FASTENING SHOWING VALUE PER FASTENER PER SQUARE.THIS
 WILL INCLUDE THE ROW AT THE LAP AS WELL AS THE FIELD
 ROWS.
  
 IT IS NOT CLEAR WHETHER THE ROW FASTENING IS COMPLIANT
 AS THEY WERE NOT ENHANCED IN THE SAME PROPORTION AS THE
 FIELD ROWS, BUT THE RAS117 TAKES ALL ROWS INTO ACCOUNT,
 NOT ONLY THE FIELD.THEREFORE, PROVIDE CALCULATIONS
 SHOWING THAT THE VALUE PER FASTENER EXCEEDS THE VALUE
 REQUIRED TO MEET THE PRESSURES SPECIFIED.
  
 2.)PROVIDE SPECS FROM THE MANUFACTURER FOR THE BASE
 SHEET SPECIFIED.NOTE THAT THE NOA DOES NOT INCLUDE
 INFORMATION ON PRODUCTS THAT ARE NOT MANUFACTURED BY
 POLYGLASS.THE FIRST SET OF ENGINEERING STATED THAT
 THE SHEET HAD A 31INCH WIDTH, THIS ONE STATES THAT IT
 IS 36INCHES.TO MY KNOWLEDGE THIS HAS ALWAYS HAD A
 39.4" SHEET WIDTH.PLEASE PROVIDE SPECIFICATIONS
 SHOWING THE 36" WIDTH AS REQUESTED.
  