2007-03-26 16:28:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THE NAME OF THE ENGINEERING FIRM DOES NOT MATCH
 THE CERTIFICATE OF AUTHORIZATION ("BUCK ENGINEERING"
 RATHER THAN "BUCK ENGINEERING INC.").
  
 2.)FBC35, ASCE7-02 IS TO BE USED RATHER THAN
 ASCE7-05.
  
 3.)PROVIDE MANUFACTURER SPEC SHEETS FOR THE BASE
 SHEET.BASE SHEET WIDTH OF -31.11502 IS SPECIFIED BY
 THE ENGINEER.
  
 4.)PROVIDE CALCULATIONS IN ACCORDANCE WITH RAS117.
  
 5.)YOU HAVE SPECIFIED BASE SHEET FASTENING IN
 FRACTIONS OF INCHES.ALL SPACING IS TO BE ROUNDED
 DOWN, SEE RAS117 10.4.2.
  
 6.)CONTRACTOR IS TO SELECT METHOD OF INSTALLATION FOR
 THE METAL ROOF.
  