Plan Review Notes For Permit 07030890 |
Permit Number |
07030890 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-26 16:28:13 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | FBC2004 | | FACFLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)THE NAME OF THE ENGINEERING FIRM DOES NOT MATCH | | THE CERTIFICATE OF AUTHORIZATION ("BUCK ENGINEERING" | | RATHER THAN "BUCK ENGINEERING INC."). | | | | 2.)FBC35, ASCE7-02 IS TO BE USED RATHER THAN | | ASCE7-05. | | | | 3.)PROVIDE MANUFACTURER SPEC SHEETS FOR THE BASE | | SHEET.BASE SHEET WIDTH OF -31.11502 IS SPECIFIED BY | | THE ENGINEER. | | | | 4.)PROVIDE CALCULATIONS IN ACCORDANCE WITH RAS117. | | | | 5.)YOU HAVE SPECIFIED BASE SHEET FASTENING IN | | FRACTIONS OF INCHES.ALL SPACING IS TO BE ROUNDED | | DOWN, SEE RAS117 10.4.2. | | | | 6.)CONTRACTOR IS TO SELECT METHOD OF INSTALLATION FOR | | THE METAL ROOF. | | |
|