2007-11-02 09:27:04REVIEWED FOR CODE COMPLIANCE. FIELD VERIFICATION BY THE
 INSPECTION TEAM IS REQUIRED TO DETERMINE IF THIS SYSTEM
 IS APPLICABLE FOR THE CONDITIONS IN THE FIELD.
 NOTE: FBC 712.4.1.2 REQUIRES THAT A THROUGH-PENETRATIN
 FIRESTOP SYSTEM IN HORIZONTAL ASSEMBLIES MAINTAINS THE
 F AND T RATING OF THE ASSEMBLY BEING PENETRATED, BUT
 NOT LESS THAN 1 HOUR. THIS ASSEMBLY SHOWS A T RATING OF
 ZERO HOURS.
  