Plan Review Notes For Permit 07030852 |
Permit Number |
07030852 |
|
Review Stop |
M |
Sequence Number |
8 |
|
Notes |
Date |
Text |
2007-11-02 09:27:04 | REVIEWED FOR CODE COMPLIANCE. FIELD VERIFICATION BY THE | | INSPECTION TEAM IS REQUIRED TO DETERMINE IF THIS SYSTEM | | IS APPLICABLE FOR THE CONDITIONS IN THE FIELD. | | NOTE: FBC 712.4.1.2 REQUIRES THAT A THROUGH-PENETRATIN | | FIRESTOP SYSTEM IN HORIZONTAL ASSEMBLIES MAINTAINS THE | | F AND T RATING OF THE ASSEMBLY BEING PENETRATED, BUT | | NOT LESS THAN 1 HOUR. THIS ASSEMBLY SHOWS A T RATING OF | | ZERO HOURS. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] | | |
|