2007-11-26 11:55:29 | ** DENIED REVISIONS ** | | | | 1) NOTE: PLEASE CLARIFY WHERE AND HOW THE EXISTING | | PANEL A/C-1 IS BEING FED? | | PLANS INDICATE THIS PANEL IS TO REMAIN AND REVISED | | RISER MENTIONS PANEL SCHEDULE WAS REMOVED. | | WHAT DOES THIS PANEL NOW FEED AND HOW IS THIS PANEL | | FED? | | PLEASE SEE THE RISER DOES SHOW A 225AMP BREAKER FOR | | SOMETHING HOWEVER THERE IS NO DESIGNATION FOR WHAT THIS | | BREAKER FEEDS. | | | | 2) NOTE: PLEASE PROVIDE NOTES ON PLANS PER | | 13-413.2.ABC.1.2 AND .2.2. | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|