Plan Review Notes
Plan Review Notes For Permit 07030852
Permit Number 07030852
Review Stop E
Sequence Number 6
Notes
Date Text
2007-11-26 11:55:29** DENIED REVISIONS **
  
 1) NOTE: PLEASE CLARIFY WHERE AND HOW THE EXISTING
 PANEL A/C-1 IS BEING FED?
 PLANS INDICATE THIS PANEL IS TO REMAIN AND REVISED
 RISER MENTIONS PANEL SCHEDULE WAS REMOVED.
 WHAT DOES THIS PANEL NOW FEED AND HOW IS THIS PANEL
 FED?
 PLEASE SEE THE RISER DOES SHOW A 225AMP BREAKER FOR
 SOMETHING HOWEVER THERE IS NO DESIGNATION FOR WHAT THIS
 BREAKER FEEDS.
  
 2) NOTE: PLEASE PROVIDE NOTES ON PLANS PER
 13-413.2.ABC.1.2 AND .2.2.
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  