Plan Review Notes
Plan Review Notes For Permit 07030852
Permit Number 07030852
Review Stop G
Sequence Number 4
Notes
Date Text
2007-08-21 10:20:08 
  
  
  
  
 PASSED/PROVISO
  
  
 PER SECTION 409.5 EACH APPLIANCE SHALL BE PROVIDED WITH
 A SHUT OFF VALVE. THERE ARE TWO FRYERS INDICATED BUT
 ONLY ONE SHUT OFF VALVE. THERE ARE TWO CONVECTION OVENS
 INDICATED BUT ONLY ONE SHUT OFF VALVE. ALSO 1" IS
 REQUIRED FOR EACH TANKLESS WATER HEATER PER TABLE
 402.4(2). 3/4" IS SHOWN FOR EACH. A REVISION IS
 REQUIRED PRIOR TO FIRST GAS INSPECTION TO CORRECT THESE
 ITEMS LISTED ON THE PROVISO.--GAS VALVES SHALL BE
 ACCESSIBLE PER SECTION 409.1.3.
  
  
  
  
  
  
 .