2007-08-15 11:35:55 | *** PROVISO *** |
| **4TH REVIEW** |
| |
| ***IMPORTANT*** |
| THE BELOW COMMENTS ARE TO BE REVISED BEFORE ANY ROUGH |
| ELECTRICAL INSPECTION IS SCHEDULED OR 30 DAYS WHICH |
| EVER COMES FIRST. THIS CONDITION IS PLACED ON THIS |
| PROJECT UPON AND 30 DAY TIME BEGINS AT THE DATE OF |
| ISSUANCE OF PERMIT FOR REVISED ELECTRICAL PLANS AND |
| POSSIBLY ENERGY CALCULATIONS TO BE SUBMITTED FOR |
| REVIEW. |
| IF PLANS HAVE NOT BEEN SUBMITTED AND CORRECTED IN THIS |
| TIME FRAME THE PERMIT MAY BE PLACED ON HOLD OR REVOKED |
| AS STATED IN FBC 105.5.2 |
| |
| 1) NOTE: PLEASE SEE THE INFORMATION ON LIGHTING |
| DENSITIES TABLES ON SHEET E003 HAS NOT BEEN REVISED TO |
| COORDINATE WITH LIGHTING PLANS AND THE SUBMITTED ENERGY |
| CALCULATIONS. |
| PLEASE COORDINATE AND REVISE. PLEASE SEE THE FOLLOWING |
| COMMENT ALSO. |
| 13-415.1.A, 13-415.2 |
| |
| 2) NOTE: PLEASE SEE THERE ARE SEVERAL LIGHTING FIXTURES |
| ON LIGHTING PLANS WHICH ARE STILL SHOWN BUT IN LT GRAY |
| AND DO NOT CONTAIN CIRCUITING OR CONTROLS. PLEASE SEE |
| THESE ITEMS ARE REDLINED ON SHEET EL 101 AS IT HAS NOT |
| BEEN DETERMINED WHETHER OR NOT THESE ARE A MISPRINT ON |
| AN OVERLAY OR IF THESE ARE ACTUAL FIXTURES TO BE |
| INSTALLED. PLEASE SEE FOR EXAMPLE *STORAGE 102 WHICH |
| SHOWS 3-L-16 FIXTURES, BUT ALSO ONLY SHOWS 1-L27 |
| FIXTURE? ANOTHER EXAMPLE:*BAR AREA WHICH CONTAIN |
| SEVERAL L2,L4 AND L5 FIXTURES WITH NO CONNECTION |
| POINTS,* THESE ARE ONLY A COUPLE AS NOTED. |
| PLEASE SEE THE PHOTO-METRIC SHEETS WERE NOT REVISED TO |
| COORDINATE WITH THE LIGHTING SHEETS. (FIRST FLOOR |
| MAINLY). |
| PLEASE BE SURE TO CORRELATE AND COORDINATE ALL OF THE |
| LIGHTING ON PLANS WITH THE FIXTURES ON PHOTO-METRICS |
| SHEETS. |
| PLEASE SEE THAT THE ENERGY CALCULATIONS DO SEEM TO |
| MATCH WITH PLANS FOR LIGHTING WHICH IS CIRCUITED, |
| HOWEVER AS IT IS NOT DETERMINED WHETHER OR NOT SOME OF |
| THESE FIXTURES IN LT GRAY ARE TO BE ON PLANS, THE |
| ENERGY CALCULATIONS DO CONTAIN MORE FIXTURES/LUMINARIES |
| THAN WHAT ARE CIRCUITED ON PLANS. |
| PLEASE REVISE ENERGY CALCULATIONS IF ADDITIONAL |
| FIXTURES ARE ADDED TO PLANS AND CIRCUITED. |
| 13-415.1, 13-415.2 |
| FBC 106.1.2 |
| |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |