Plan Review Notes
Plan Review Notes For Permit 07030852
Permit Number 07030852
Review Stop E
Sequence Number 4
Notes
Date Text
2007-08-15 11:35:55*** PROVISO ***
 **4TH REVIEW**
  
 ***IMPORTANT***
 THE BELOW COMMENTS ARE TO BE REVISED BEFORE ANY ROUGH
 ELECTRICAL INSPECTION IS SCHEDULED OR 30 DAYS WHICH
 EVER COMES FIRST. THIS CONDITION IS PLACED ON THIS
 PROJECT UPON AND 30 DAY TIME BEGINS AT THE DATE OF
 ISSUANCE OF PERMIT FOR REVISED ELECTRICAL PLANS AND
 POSSIBLY ENERGY CALCULATIONS TO BE SUBMITTED FOR
 REVIEW.
 IF PLANS HAVE NOT BEEN SUBMITTED AND CORRECTED IN THIS
 TIME FRAME THE PERMIT MAY BE PLACED ON HOLD OR REVOKED
 AS STATED IN FBC 105.5.2
  
 1) NOTE: PLEASE SEE THE INFORMATION ON LIGHTING
 DENSITIES TABLES ON SHEET E003 HAS NOT BEEN REVISED TO
 COORDINATE WITH LIGHTING PLANS AND THE SUBMITTED ENERGY
 CALCULATIONS.
 PLEASE COORDINATE AND REVISE. PLEASE SEE THE FOLLOWING
 COMMENT ALSO.
 13-415.1.A, 13-415.2
  
 2) NOTE: PLEASE SEE THERE ARE SEVERAL LIGHTING FIXTURES
 ON LIGHTING PLANS WHICH ARE STILL SHOWN BUT IN LT GRAY
 AND DO NOT CONTAIN CIRCUITING OR CONTROLS. PLEASE SEE
 THESE ITEMS ARE REDLINED ON SHEET EL 101 AS IT HAS NOT
 BEEN DETERMINED WHETHER OR NOT THESE ARE A MISPRINT ON
 AN OVERLAY OR IF THESE ARE ACTUAL FIXTURES TO BE
 INSTALLED. PLEASE SEE FOR EXAMPLE *STORAGE 102 WHICH
 SHOWS 3-L-16 FIXTURES, BUT ALSO ONLY SHOWS 1-L27
 FIXTURE? ANOTHER EXAMPLE:*BAR AREA WHICH CONTAIN
 SEVERAL L2,L4 AND L5 FIXTURES WITH NO CONNECTION
 POINTS,* THESE ARE ONLY A COUPLE AS NOTED.
 PLEASE SEE THE PHOTO-METRIC SHEETS WERE NOT REVISED TO
 COORDINATE WITH THE LIGHTING SHEETS. (FIRST FLOOR
 MAINLY).
 PLEASE BE SURE TO CORRELATE AND COORDINATE ALL OF THE
 LIGHTING ON PLANS WITH THE FIXTURES ON PHOTO-METRICS
 SHEETS.
 PLEASE SEE THAT THE ENERGY CALCULATIONS DO SEEM TO
 MATCH WITH PLANS FOR LIGHTING WHICH IS CIRCUITED,
 HOWEVER AS IT IS NOT DETERMINED WHETHER OR NOT SOME OF
 THESE FIXTURES IN LT GRAY ARE TO BE ON PLANS, THE
 ENERGY CALCULATIONS DO CONTAIN MORE FIXTURES/LUMINARIES
 THAN WHAT ARE CIRCUITED ON PLANS.
 PLEASE REVISE ENERGY CALCULATIONS IF ADDITIONAL
 FIXTURES ARE ADDED TO PLANS AND CIRCUITED.
 13-415.1, 13-415.2
 FBC 106.1.2
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]