Plan Review Notes For Permit 07030852 |
Permit Number |
07030852 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-07-16 15:16:17 | ---------------DENIED----------------- | | | | NOTE: AT THIS TIME ALL OUTSTANDING MECHANICAL PLAN | | REVIEW COMMENTS HAVE BEEN ADEQUATELY ADDRESSED. | | HOWEVER, SOME CORRECTIONS ARE NEEDED TO THE ENERGY | | CALCULATIONS. | | | | 1. PLEASE INDICATE ON THE PROJECT SUMMARY THE MAX | | TONNAGE SHOULD INDICATE THE LARGEST PIECE OF EQUIPMENT | | SERVING THE SPACE. | | | | 2. AT LEAST 2 COPIES OF THE ENERGY CALCULATIONS SHALL | | BE PROVIDED WITH THE PLANS THAT CONTAIN ORIGINAL | | SIGNATURES AND SEALS PER FBC 13-103.1.1.1 AND SHALL BE | | SIGNED BY THE BUILDING OWNER OR OWNER'S AGENT PER FBC | | 13-103.1.2 | | | | 3. THE INPUT DATA REPORT SHOWS MATERIALS AND TYPES OF | | CONSTRUCTION WHICH DO NOT APPLY TO THIS PROJECT. | | EXAMPLES: METAL SIDING W/ R-11 BATTS AND 1/2" GYP BD IS | | LISTED UNDER WALL TYPE, METAL BLDG ROOF W/ R-19 BATTS | | IS LISTED FOR ROOF TYPE, ALUMINUM POLYSTYRENE-FILLED | | DOORS ARE SHOWN AS DOOR TYPE. | | PLEASE USE DATA WHICH ACCURATELY REFLECTS THE | | CONSTRUCTION MATERIALS WHICH ARE IN PLACE AND WHICH | | ACCURATELY REFLECT THE R-VALUES AS THEY ACTUALLY OCCUR | | IN THE BUILDING. | | | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|