Plan Review Notes
Plan Review Notes For Permit 07030852
Permit Number 07030852
Review Stop P
Sequence Number 2
Notes
Date Text
2007-06-07 17:29:14DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ******FROM PREVIOUS REVIEW:
  
 1. ROUTE PLANS TO THE DEPARTMENT OF BUSINESS
 REGULATION, HOTEL & RESTAURANT DIVISION FOR PLAN
 REVIEW. A MINIMUM OF TWO SETS OF PLANS WITH STAMPED
 SHEETS FROM DBPR WITH THE TWO PAGE "WORKSHEETS"
 ATTACHED TO THE STAMPED SHEET SHALL BE RESUBMITTED FOR
 REVIEW. SECTION 102.2.1.
 ******NO RESPONSE/NOT ADDRESSED
  
 2. GREASE INTERCEPTORS SHALL BE SIZED AND INSPECTED BY
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO
 (561) 822-2272 OR CALVIN WILLIAMS(561) 822-2284.
 THEIR FAX NUMBER IS (561) 822-2287. E-MAIL
 [email protected]@WPB.ORG. PLEASE INDICATE
 THEIR RESPONSE. ARTICLE III 90-124(7). ******WAITING
 FOR REPLY FROM C. WILLIAMS. WILL TRY TO ADDRESS ISSUE
 AT THIS END.
  
 3. OK
 4. OK
 5. OK
  
 6. SHT A400 DETAILS 1 & 2 GRAB BARS FOR THE WATER
 CLOSETS AT THE SIDE SHALL BE 42". SEE FIG 11-30E.--
 DETAIL 4 SHOW THE WATER CLOSET TO BE 1'7" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE. 1'6" IS REQUIRED. SEE
 FIG 11-30E.7.
 ******RESPONSE NOTED, NOT ADDRESSED
  
 7. SHT A400 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR
 URINAL
 A. OK
 B. OK
 C. 11-4.18.4 FLUSH CONTROLS
 ******NOT ADDRESSED
 __FOR LAVS
 A MINIMUM 1 LAV OUTSIDE THE ACCESSIBLE STALL SHALL
 COMPLY WITH SECTION 11-4.19 AND ALL SUBSECTIONS.
 FORWARD APPROACH REQUIRED AND SHALL EXTEND UNDERNEATH
 THE LAV A MINIMUM 19" PLEASE SUBMIT A DETAIL FOR THE
 ACCESSIBLE LAV OUTSIDE THE ACCESSIBLE STALL.
 ******RESPONSE NOTED, BUT PER SECTION 11-4.19.1 ALL
 LAVS SHALL BE ACCESSIBLE.
  
 8. SHT A401 DETAILS 1 & 2 FORWARD APPROACH REQUIRED FOR
 THE CLEAR FLOOR SPACE FOR AT LEAST ONE LAV OUTSIDE THE
 ACCESSIBLE STALL PER SECTION 11-419.3. ******RESPONSE
 NOTED, BUT PER SECTION 11-4.19.1 ALL LAVS SHALL BE
 ACCESSIBLE.
  
 9.OK
 10. OK
 11. OK
 12. OK
  
 13. ALL MECHANICAL & PLUMBING SHEETS. THE ENGINEERS
 SIGNATURE IS REQUIRED ON EACH SHEET. IT APPEARS THAT
 INITIALS HAVE BEEN USED. IF INDEED THIS IS THE LEGAL
 SIGNATURE, A SIGNED, SEALED, NOTORIZED LETTER
 INDICATING THE LEGAL SIGNATURE SHALL BE SUBMITTED FOR
 OUR FILES. FAC 61G15-23.002(1)(2) & FS 471.025.
 ******RESPONSE NOTED. THIS WILL BE REQUIRED PRIOR TO
 PERMIT BEING ISSUED.
  
 14. OK
 15. OK
 16. OK
  
 17. SHT P301 PLUMBING/WASTE SCHEDULE. SHOW ALL MARK
 DESIGNATIONS ON THE ENLARGED KITCHEN WASTE PLAN THAT
 CORRELATES WITH THE SCHEDULE. AT THIS POINT THE KITCHEN
 EQUIPMENT CAN NOT BE IDENTIFIED WITHOUT MARK
 DESIGNATIONS. SECTION 106.1.1.
 ******RESPONSE NOTED, BUT THE FOLLOWING ITEMS WERE NOT
 LOCATED ON THE FLOOR PLAN. P6A, P16, P11, P12A, P13A,
 P14, P14.1, P14A, P14B, P15A, P17A P47B, P150 & P150A.
 PLEASE CORRELATE FLOOR PLAN WITH PLUMBING/WASTE
 SCHEDULE.
  
 18. OK
  
 19. SHT P301 PLUMBING/WATER SCHEDULE ITEMS P31-C &
 P39-F INDICATE A WATER FILTER. WATER FILTERS MUST MEET
 THE REQUIREMENTS OF NSF 42. PLEASE SUBMIT MANUF
 SPECIFICATION SHEETS SHOWING COMPLIANCE. SECTION
 611.1.
 ******RESPONSE NOTED, BUT NOT ADDRESSED
  
 20. SHT P301 PLUMBING/WATER SCHEDULE. MARK P33-F
 INDICATES QTY 4, BUT ONLY 2 WERE FOUND. PLEASE CLARIFY.
 SECTION 106.1.1.
 ******RESPONSE NOTED, BUT SCHEDULE NOT CHANGED.
  
 21. OK
  
 22. SHT P302 IDENTIFY ALL FIXURES/APPLIANCES TO REFLECT
 THE MARK NUMBERS INDICATED ON THE PLUMBING/WASTE
 SCHEDULE. MORE INFORMATION IS REQUIRED SECTION
 106.2.1.
 ******RESPONSE NOTED, BUT SOME MARK NUMBER ARE NOT
 INDICATED ON THE FLOOR PLANS. (SEE COMMENT 17).
  
 23. OK
 24. OK
  
 25. SHT P401. DOMESTIC WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN FOR FIXTURES P88-C, P36-C -
 P36-H, (BY P98) & P55-H. PLEASE CORRELATE THE RISER AND
 FLOOR PLAN INFORMATIONS. SECTION 106.1.1.
 ******RESPONSE NOTED, BUT FIXTURE P88-C PIPING ON THE
 RISER DIAGRAM STILL DOES NOT REFLECT THE FLOOR PLAN.
  
 26. OK
 27. OK
 28. OK
 29. OK
  
 30. SHT P402 THE FOLLOWING IS REQUIRED FOR THE GAS
 PERMIT APPROVAL:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ******RESPONSE NOTED, BUT A CLARIFICATION IS REQUIRED
 ON THE DROP WITH THE SOLENOID VALVE. THE TOTAL LENGTH
 IS INDICATED AS 3'0", (1'0" +2'0").
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ******RESPONSE NOTED, BUT DISTANCE SHALL BE VERIFIED
 WHEN COMMENT "A" CLARIFIED.
  
 C. OK
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ******RESPONSE NOTED, NOT ADDRESSED.
  
 E. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ******RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. NO
 MANUAL SHUT OFF VALVE UPSTREAM OF THE SOLENOID VALVE
 AND NO UNION INDICATED.
  
 31. OK
 32. OK
 33. OK
 34. OK
 35. OK
  
 36. TO HELP EXPEDITE PLAN REVIEW, PLEASE RESUBMIT THE
 MARKED UP PLUMBING PLANS ALONG WITH THE NEW PLANS.
 *******NO RESPONSE, NOT ADDRESSED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved