Date |
Text |
2007-06-07 17:29:14 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| WPB MUNICIPAL CODE |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ******FROM PREVIOUS REVIEW: |
| |
| 1. ROUTE PLANS TO THE DEPARTMENT OF BUSINESS |
| REGULATION, HOTEL & RESTAURANT DIVISION FOR PLAN |
| REVIEW. A MINIMUM OF TWO SETS OF PLANS WITH STAMPED |
| SHEETS FROM DBPR WITH THE TWO PAGE "WORKSHEETS" |
| ATTACHED TO THE STAMPED SHEET SHALL BE RESUBMITTED FOR |
| REVIEW. SECTION 102.2.1. |
| ******NO RESPONSE/NOT ADDRESSED |
| |
| 2. GREASE INTERCEPTORS SHALL BE SIZED AND INSPECTED BY |
| ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO |
| (561) 822-2272 OR CALVIN WILLIAMS(561) 822-2284. |
| THEIR FAX NUMBER IS (561) 822-2287. E-MAIL |
| [email protected]@WPB.ORG. PLEASE INDICATE |
| THEIR RESPONSE. ARTICLE III 90-124(7). ******WAITING |
| FOR REPLY FROM C. WILLIAMS. WILL TRY TO ADDRESS ISSUE |
| AT THIS END. |
| |
| 3. OK |
| 4. OK |
| 5. OK |
| |
| 6. SHT A400 DETAILS 1 & 2 GRAB BARS FOR THE WATER |
| CLOSETS AT THE SIDE SHALL BE 42". SEE FIG 11-30E.-- |
| DETAIL 4 SHOW THE WATER CLOSET TO BE 1'7" OFF THE WALL |
| TO THE CENTERLINE OF THE FIXTURE. 1'6" IS REQUIRED. SEE |
| FIG 11-30E.7. |
| ******RESPONSE NOTED, NOT ADDRESSED |
| |
| 7. SHT A400 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR |
| URINAL |
| A. OK |
| B. OK |
| C. 11-4.18.4 FLUSH CONTROLS |
| ******NOT ADDRESSED |
| __FOR LAVS |
| A MINIMUM 1 LAV OUTSIDE THE ACCESSIBLE STALL SHALL |
| COMPLY WITH SECTION 11-4.19 AND ALL SUBSECTIONS. |
| FORWARD APPROACH REQUIRED AND SHALL EXTEND UNDERNEATH |
| THE LAV A MINIMUM 19" PLEASE SUBMIT A DETAIL FOR THE |
| ACCESSIBLE LAV OUTSIDE THE ACCESSIBLE STALL. |
| ******RESPONSE NOTED, BUT PER SECTION 11-4.19.1 ALL |
| LAVS SHALL BE ACCESSIBLE. |
| |
| 8. SHT A401 DETAILS 1 & 2 FORWARD APPROACH REQUIRED FOR |
| THE CLEAR FLOOR SPACE FOR AT LEAST ONE LAV OUTSIDE THE |
| ACCESSIBLE STALL PER SECTION 11-419.3. ******RESPONSE |
| NOTED, BUT PER SECTION 11-4.19.1 ALL LAVS SHALL BE |
| ACCESSIBLE. |
| |
| 9.OK |
| 10. OK |
| 11. OK |
| 12. OK |
| |
| 13. ALL MECHANICAL & PLUMBING SHEETS. THE ENGINEERS |
| SIGNATURE IS REQUIRED ON EACH SHEET. IT APPEARS THAT |
| INITIALS HAVE BEEN USED. IF INDEED THIS IS THE LEGAL |
| SIGNATURE, A SIGNED, SEALED, NOTORIZED LETTER |
| INDICATING THE LEGAL SIGNATURE SHALL BE SUBMITTED FOR |
| OUR FILES. FAC 61G15-23.002(1)(2) & FS 471.025. |
| ******RESPONSE NOTED. THIS WILL BE REQUIRED PRIOR TO |
| PERMIT BEING ISSUED. |
| |
| 14. OK |
| 15. OK |
| 16. OK |
| |
| 17. SHT P301 PLUMBING/WASTE SCHEDULE. SHOW ALL MARK |
| DESIGNATIONS ON THE ENLARGED KITCHEN WASTE PLAN THAT |
| CORRELATES WITH THE SCHEDULE. AT THIS POINT THE KITCHEN |
| EQUIPMENT CAN NOT BE IDENTIFIED WITHOUT MARK |
| DESIGNATIONS. SECTION 106.1.1. |
| ******RESPONSE NOTED, BUT THE FOLLOWING ITEMS WERE NOT |
| LOCATED ON THE FLOOR PLAN. P6A, P16, P11, P12A, P13A, |
| P14, P14.1, P14A, P14B, P15A, P17A P47B, P150 & P150A. |
| PLEASE CORRELATE FLOOR PLAN WITH PLUMBING/WASTE |
| SCHEDULE. |
| |
| 18. OK |
| |
| 19. SHT P301 PLUMBING/WATER SCHEDULE ITEMS P31-C & |
| P39-F INDICATE A WATER FILTER. WATER FILTERS MUST MEET |
| THE REQUIREMENTS OF NSF 42. PLEASE SUBMIT MANUF |
| SPECIFICATION SHEETS SHOWING COMPLIANCE. SECTION |
| 611.1. |
| ******RESPONSE NOTED, BUT NOT ADDRESSED |
| |
| 20. SHT P301 PLUMBING/WATER SCHEDULE. MARK P33-F |
| INDICATES QTY 4, BUT ONLY 2 WERE FOUND. PLEASE CLARIFY. |
| SECTION 106.1.1. |
| ******RESPONSE NOTED, BUT SCHEDULE NOT CHANGED. |
| |
| 21. OK |
| |
| 22. SHT P302 IDENTIFY ALL FIXURES/APPLIANCES TO REFLECT |
| THE MARK NUMBERS INDICATED ON THE PLUMBING/WASTE |
| SCHEDULE. MORE INFORMATION IS REQUIRED SECTION |
| 106.2.1. |
| ******RESPONSE NOTED, BUT SOME MARK NUMBER ARE NOT |
| INDICATED ON THE FLOOR PLANS. (SEE COMMENT 17). |
| |
| 23. OK |
| 24. OK |
| |
| 25. SHT P401. DOMESTIC WATER RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN FOR FIXTURES P88-C, P36-C - |
| P36-H, (BY P98) & P55-H. PLEASE CORRELATE THE RISER AND |
| FLOOR PLAN INFORMATIONS. SECTION 106.1.1. |
| ******RESPONSE NOTED, BUT FIXTURE P88-C PIPING ON THE |
| RISER DIAGRAM STILL DOES NOT REFLECT THE FLOOR PLAN. |
| |
| 26. OK |
| 27. OK |
| 28. OK |
| 29. OK |
| |
| 30. SHT P402 THE FOLLOWING IS REQUIRED FOR THE GAS |
| PERMIT APPROVAL: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| ******RESPONSE NOTED, BUT A CLARIFICATION IS REQUIRED |
| ON THE DROP WITH THE SOLENOID VALVE. THE TOTAL LENGTH |
| IS INDICATED AS 3'0", (1'0" +2'0"). |
| |
| B. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| ******RESPONSE NOTED, BUT DISTANCE SHALL BE VERIFIED |
| WHEN COMMENT "A" CLARIFIED. |
| |
| C. OK |
| |
| D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ******RESPONSE NOTED, NOT ADDRESSED. |
| |
| E. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| ******RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. NO |
| MANUAL SHUT OFF VALVE UPSTREAM OF THE SOLENOID VALVE |
| AND NO UNION INDICATED. |
| |
| 31. OK |
| 32. OK |
| 33. OK |
| 34. OK |
| 35. OK |
| |
| 36. TO HELP EXPEDITE PLAN REVIEW, PLEASE RESUBMIT THE |
| MARKED UP PLUMBING PLANS ALONG WITH THE NEW PLANS. |
| *******NO RESPONSE, NOT ADDRESSED |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |