Plan Review Notes
Plan Review Notes For Permit 07030852
Permit Number 07030852
Review Stop M
Sequence Number 2
Notes
Date Text
2007-06-07 10:50:37---------------DENIED---------------
 *2ND REVIEW*
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS COMMENTS FOR CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. GENERAL NOTE #40 STILL STATES "ALL... DUCTWORK SHALL
 BE GALVANIZED STEEL, WRAPPED WITH 2"..." THIS IS IN
 CONFLICT WITH NOTES AND DETAILS SHOWING THE USE OF FLEX
 DUCT. PLEASE CLARIFY.
  
 4. OK
  
 5. EXAMPLE: AHU-6 IS LOCATED ABOVE PRIVATE DINING ROOM
 105. FINISH SCHEDULE ON A-600 SHOWS A GYPSUM CEILING.
 CLEARANCES AROUND APPLIANCES TO ELEMENTS OF PERMANENT
 CONSTRUCTION, INCLUDING OTHER INSTALLED EQUIPMENT AND
 APPLIANCES, SHALL BE SUFFICIENT TO ALLOW INSPECTIONS,
 SERVICE, REPAIR OR REPLACEMENT WITHOUT REMOVING SUCH
 ELEMENTS OF PERMANENT CONSTRUCTION OR DISABLING THE
 FUNCTION OF A REQUIRED FIRE RESISTANCE-RATED ASSEMBLY.
 FBC,M 306.1
  
 6. CONTINUATION OF DUCTWORK ON M100 APPEARS TO BE FROM
 AHU-5, NOT AHU-4. THE QUESTIONS RELATED TO AHU-4 IN
 PREVIOUS COMMENT HAVE NOT BEEN ADDRESSED.
  
 7. OK
  
 8. OK
  
 9. NOT CORRECTED. DROPS WERE CIRCLED DURING THIS REVIEW
 ON ONE SET OF PLANS FOR CLARIFICATION OF THE REVIEW
 COMMENT.
  
 10. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
  