Plan Review Notes For Permit 07030852 |
Permit Number |
07030852 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-06-07 10:50:37 | ---------------DENIED--------------- | | *2ND REVIEW* | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PREVIOUS COMMENTS FOR CONTINUITY. | | | | 1. OK | | | | 2. OK | | | | 3. GENERAL NOTE #40 STILL STATES "ALL... DUCTWORK SHALL | | BE GALVANIZED STEEL, WRAPPED WITH 2"..." THIS IS IN | | CONFLICT WITH NOTES AND DETAILS SHOWING THE USE OF FLEX | | DUCT. PLEASE CLARIFY. | | | | 4. OK | | | | 5. EXAMPLE: AHU-6 IS LOCATED ABOVE PRIVATE DINING ROOM | | 105. FINISH SCHEDULE ON A-600 SHOWS A GYPSUM CEILING. | | CLEARANCES AROUND APPLIANCES TO ELEMENTS OF PERMANENT | | CONSTRUCTION, INCLUDING OTHER INSTALLED EQUIPMENT AND | | APPLIANCES, SHALL BE SUFFICIENT TO ALLOW INSPECTIONS, | | SERVICE, REPAIR OR REPLACEMENT WITHOUT REMOVING SUCH | | ELEMENTS OF PERMANENT CONSTRUCTION OR DISABLING THE | | FUNCTION OF A REQUIRED FIRE RESISTANCE-RATED ASSEMBLY. | | FBC,M 306.1 | | | | 6. CONTINUATION OF DUCTWORK ON M100 APPEARS TO BE FROM | | AHU-5, NOT AHU-4. THE QUESTIONS RELATED TO AHU-4 IN | | PREVIOUS COMMENT HAVE NOT BEEN ADDRESSED. | | | | 7. OK | | | | 8. OK | | | | 9. NOT CORRECTED. DROPS WERE CIRCLED DURING THIS REVIEW | | ON ONE SET OF PLANS FOR CLARIFICATION OF THE REVIEW | | COMMENT. | | | | 10. OK | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|