Date |
Text |
2007-06-08 14:12:40 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| 1. SHT P402 THE FOLLOWING IS REQUIRED FOR THE GAS |
| PERMIT APPROVAL: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| ******RESPONSE NOTED, BUT A CLARIFICATION IS REQUIRED |
| ON THE DROP WITH THE SOLENOID VALVE. THE TOTAL LENGHT |
| IS INDICATED AS 3'0", (1'0" +2'0"). |
| |
| B. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| ******RESPONSE NOTED, BUT DISTANCE SHALL BE VERIFIED |
| WHEN COMMENT "A" CLARIFIED. |
| |
| C. OK |
| |
| D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ******RESPONSE NOTED, NOT ADDRESSED. |
| |
| E. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| ******RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. NO |
| MANUAL SHUT OFF VALVE UPSTREAM OF THE SOLENOID VALVE |
| AND NO UNION INDICATED. |
| |
| 2. OK |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |