Plan Review Notes
Plan Review Notes For Permit 07030852
Permit Number 07030852
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-06 19:25:52** UNSAT 2ND REVIEW **
  
 *** PLEASE KNOW THAT AS THERE ARE SOME ITEMS WHICH ARE
 FROM PREVIOUS REVIEW AND SOME NEW ITEMS BASED ON
 REVISED PLANS AND NEW COMMENTS.
  
  
 1) NOTE: PLEASE SEE THERE ARE STILL SOME CODE SECTIONS
 ON PLANS WHICH ARE IN NEED O CORRECTING. PLEASE SEE THE
 PREVIOUS NOTES FOR ADA ADOPTED CODE FOR CHAPTER 11 OF
 THE FBC 2004 W/2006 REVISIONS.
 PLEASE SEE SOME ARE NOW INDICATING THE * 1992* CODE?
 PLEASE SEE THE COVER/T-SHEET IS OK, HOWEVER SEE E002.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO
 SIGNATURES FOR SOME ARCHITECTURAL AND ENGINEERING
 SHEETS. ONLY ONE LETTER SUBMITTED BY THE ARCHITECT FOR
 SIGNATURE VERIFICATION. THIS WAS NOT SIGNED, DATED AND
 SEALED. THESE LETTER(S) IN PACKAGE WERE PHOTO-COPIES
 AND NOT ORIGINAL. PLEASE ALSO BE SURE THE LETTER IS
 CORRECTLY NOTARIZED PER FLORIDA STATUTES 117.05 AS THE
 NOTARIZATION AS SUBMITTED DOES NOT COMPLY WITH THE
 MINIMUM INFORMATION REQUIRED PER SAID STATUE GIVEN. NO
 LETTER WAS FOUND FOR ENGINEER MR. LIZASOAIN AND THE
 RESPONSE LETTER FROM SGM ENGINEERS DID NOT CONTAIN ANY
 RESPONSE FOR THIS NOTE?
 THESE WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY NEED
 OF FUTURE PROJECTS OR REFERENCE.
 PLEASE BE SURE BOTH LETTERS ARE PROPERLY NOTARIZED PER
 FS 117.05. THIS INFORMATION CAN BE FOUND ON THE STATES
 WEBSITE AT: WWW.LEG.STATE.FL.US/WELCOME/INDEX.CFM **
 THIS COMMENT WAS FOR MR. DOUGLAS AND MR. LIZASOAIN.
  
 3) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 IS STILL IN NEED OF ADDRESSING.
 PLEASE SEE THE SQ FT ON ENERGY CALCULATIONS STILL DOES
 NOT CORRELATE WITH PLANS.
 PLEASE SEE THE NUMBER OF FIXTURES ON ENERGY
 CALCULATIONS DO NOT CORRELATE WITH PLANS.
 PLEASE SEE THE NUMBER OF EACH TYPE OF FIXTURE DOES NOT
 CORRELATE WITH PLANS. (SHOWS ONE FIXTURE FOR EACH TYPE)
 THIS IS NOT POSSIBLE. THE ENERGY CALCULATIONS
 SPECIFICALLY STATE THE NUMBER(S) OF FIXTURE FOR EACH
 TYPE.
 PLEASE SEE THE WATTAGE FOR FIXTURES AND COORDINATION OF
 THE CALCULATIONS TO THE PLANS CAN NOT BE DONE AT THIS
 TIME.
 PLEASE SEE THE VERSION OF THE ENERGY CALCULATIONS IS
 NOT THE CURRENT VERSION FOR THE 2006 REVISIONS TO THE
 2004 FBC. (3.0)
 PLEASE SEE THAT ALL SEPARATE SPACES FOR LIGHTING
 CONTROLS AND/OR OVER RIDES NEED TO MEET
 13-415.1.ABC.1.2. PLEASE SEE ANY TYPE OF OVER RIDE
 DEVICES NEED TO STATE THE MAXIMUM TIME FOR OVER RIDE OF
 SYSTEM OR FOR INDIVIDUAL CONTROL OF A SEPARATE SPACE.
 PLANS INCLUDE NEW TIMER SWITCHES FOR SOME ROOMS HOWEVER
 NO MAXIMUM TIME(S) IS SHOWN ON LEGEND.
 PLEASE SEE 13-415.1.ABC.1.1 (4HRS MAXIMUM FOR TIMER
 TYPE(S) AND 30MINUTES MAXIMUM FOR ANY OS TYPE DEVICES.
 PLEASE INDICATE ALL OVER RIDE DEVICES AND LOCATIONS ON
 PLANS.
 PLEASE STATE ALL MAXIMUM OVER RIDE TIMES.
 PLEASE SEE MISSING EXTERIOR LIGHTING ALLOWANCES ON
 ENERGY CALCULATIONS. PLEASE SEE ENERGY CALCULATIONS
 INDICATE *NONE ENTERED* AND NONE ON THE INPUT DATA
 REPORT.HOW IS THIS POSSIBLE WHEN PLANS CLEARLY
 INDICATE LIGHTING?
 PLEASE CLARIFY WHERE THE ALLOWED WATTS PER SQ FT ON
 TABLE E003 IS COMING FROM? THERE ARE NO NUMBERS IN THE
 TABLES OF THE FBC CHAPTER 13-415.2.B, 13-415.2.C.1
 WHICH CONTAIN THESE SAME HIGH NUMBERS. PLEASE SEE THE
 ENERGY CALCULATIONS AS BEING SUBMITTED IS METHOD A.
 PLEASE CALL TO GO OVER THIS.
 PLEASE SEE THE METHOD OF CONTROL FOR LIGHTING ON ENERGY
 CALCULATIONS IS NOT ENTIRELY ACCURATE AS SOME OF THE
 LIGHTING IS NOT ON A PROGRAMMABLE TIMER.
 PLEASE BE SURE THE *OWNER AGENT* SPACE ON THE SHEET #2
 FOR CERTIFICATIONS IS SIGNED. THIS IS BLANK AT THIS
 TIME.13-103.1.1.1
 ** PLEASE KNOW THAT AS MUCH OF THIS INFORMATION HAS NOT
 YET BEEN COORDINATED REVIEW OF THESE ITEMS WILL STILL
 NEED TO TAKE PLACE FOR CODE COMPLIANCE REVIEW.
  
 4) NOTE: THE RESPONSE LETTER MENTIONS THE EXISTING
 SERVICE FOR PREVIOUS RESTAURANT IS OF SUFFICIENT SIZE
 AND THE PREVIOUS SERVICE FOR THE BUSINESS OCCUPANCY
 WILL NOT BE NEEDED. PLEASE PROVIDE DETAIL AND NOTES ON
 THIS PREVIOUS SERVICE EQUIPMENT INCLUDING, METER, MAINS
 AND PANELS BEING DELETED AND REMOVED.
 FBC 106.1.3.5.1.2
 NEC 230.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE WHICH REQUESTED
 (ALL) SERVICE EQUIPMENTTO BE SHOWN ON PLANS. MOST
 WERE LOCATED ON PREVIOUS PLANS HOWEVER HDP COULD NOT BE
 LOCATED.
 PLEASE SPECIFY THE SERVICE EQUIPMENT, ELECTRICAL
 PANELS, AND TRANSFORMER LOCATIONS. ARE THESE LOCATED IN
 AN ELECTRICAL ROOM?
 PLEASE PROVIDE ROOM AND AREA DESIGNATIONS FOR ALL AREAS
 AND ROOMS.
 AS REQUESTED PLEASE INDICATE ROOMS AND USE AS SECOND
 FLOOR ROOM FOR SOME OF THE ELECTRICAL EQUIPMENT IS NOT
 IDENTIFIED.
 110.26, 240.24, 450.11, 450.13, 408.7 ETC
  
 6) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED ARE
 NOT COMPLETED AT THIS TIME. PLEASE SUBMIT A COMPLETE
 LOAD SUMMARY ON HOW LOADS WERE DERIVED FOR SERVICE.
 PLEASE SEE PREVIOUS NOTES WITH RESPECT TO SHOW WINDOWS,
 SIGN CIRCUIT. PLEASE CLARIFY HOW AND WHERE CU 1,2,3,4
 AND 5 ARE FED? LOADS ON A/C HEAT ETC.
 PLEASE SEE LOADS ON EACH PANEL ARE NOT CLEAR WHERE AND
 WHAT TYPE OF DE-RATING IS BEING DONE. (EXAMPLE, PLEASE
 SEE RECEPTACLES WHICH INDICATES FOR DEMANDON EACH
 PANEL COLUMN * NEC *. THIS IS OK FOR LOADS ON PANELS
 HOWEVER HOW ARE NO RECEPTACLE LOADS SHOWN ON LDP? IT IS
 BEING ASSUMED HOW LOADS ARE BEING FIGURED, HOWEVER AS
 THESE ARE RECORD SETS OF PLANS, THESE SHOULD COORDINATE
 WITH THAT OF THE NEC.
 PLEASE SHOW DETAILED LOAD CALCULATIONS. 215.3, 230.42,
 220.12, 220.14, 220.42, 220.43, 220.44, ETC.
  
 7) NOTE: PLEASE SEE THE MISSING SIGN CIRCUIT IS NOW
 SHOWN HOWEVER THE LOAD AS INDICATED DOES NOT MEET THE
 MINIM PER 600.5 (1200VA MIN)
 PLEASE SEE 220.43A FOR LOADS FOR SHOW WINDOW
 RECEPTACLES.
  
 8) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS ON
 THE LIGHTING CONTROL PANELS. THIS WAS REQUESTED ON THE
 PREVIOUS REVIEW. THE RESPONSE MENTIONS SHEETS ADDED TO
 PLANS, HOWEVER NO LISTINGS COULD BE LOCATED AND
 SPECS/CUT SHEETS ON ACTUAL LIGHTING CONTROL/DIMMING
 PANELS ARE BEING REQUESTED FOR REVIEW. 110.3, 90.7.
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE THE PHOTO-METRICS WERE SUBMITTED AS
 PREVIOUSLY REQUESTED FOR REVIEW OF LIGHTING LEVELS OF
 EGRESS PATHS UNDER NORMAL AND EMERGENCY CONDITIONS
 HOWEVER PLANS MENTIONS AND SHOWS NUMEROUS
 *EMERGENCY/NIGHT LIGHT* BATTERY BACK UP TYPE OF
 FIXTURES SHOWN AS BEING DIMMED TO AS MUCH AS 30%. HOW
 IS THE MINIMUM NORMAL AND EMERGENCY LIGHTING LEVELS
 STILL OBTAINED AS REQUIRED UNDER THE LIFE SAFETY CODE
 WHEN THE DIMMED LEVELS FALL BELOW THE 10FT CANDLES FOR
 STAIRS UNDER NORMAL AND UNDER 1FT CANDLE FOR STAIRS
 UNDER EMERGENCY. HOW ARE THE MINIMUM LIGHTING LEVELS
 MET FOR ALL OTHER EGRESS PATHS UNDER EMERGENCY WHEN
 LIGHTS ARE DIMMED AT 30%? ONE STAIR DOES INDICATE A
 NOTE WHICH STATES THE LIGHTING FIXTURES WILL BE WIRED
 AHEAD OF LIGHTING CONTROL AND DIMMING PANELS. PLEASE
 KNOW AT THIS TIME THIS INFORMATION IS BEING FORWARDED
 TO THE FIRE MARSHAL FOR REVIEW.
 THIS IS REQUIRED FOR LIFE SAFETY AND TRIPPING HAZARDS.
  
 10) NOTE: PLEASE BE SURE WHEN OLD/VOIDED ARE REMOVED
 THAT WHEN NEW SHEETS ARE INSERTED OR WHEN NEW SETS ARE
 SUBMITTED THAT ALL SHEETS ARE BOUND INTO SETS. PLEASE
 SEE THAT ALL THE MEP SHEETS WERE SUBMITTED LOOSE IN
 SETS.
  
 11) NOTE: PLEASE LABEL LIGHTING/DIMMING PANELS. (D-1,
 D-2)
 FBC 106.1.2, 106.3.5.1.2
  
 12) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT CODE COMPLIANT COMMENTS. THIS IS ONLY A NOTICE
 GIVEN AT THIS TIME.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED, THERE MAY NEW COMMENTS ON THE FOLLOWING
 REVIEW ONCE PLANS ARE COMPLETED FOR REVIEW.
  
 ** PLEASE SEE SOME ITEMS ARE REDLINED ON ONE OF THE
 SETS FO PLANS FOR SOME ITEMS WHICH MAY HELP LOCATE
 NOTES AS TYPES.
  
 ** PLEASE KNOW AS STATED ON PREVIOUS REVIEW: PLEASE BE
 SURE TO CALL IF THERE ARE ANY QUESTIONS OR COMMENTS
 WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF THERE ARE
 ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, NOT
 UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE AND THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]