Plan Review Notes
Plan Review Notes For Permit 07030852
Permit Number 07030852
Review Stop B
Sequence Number 2
Notes
Date Text
2007-06-07 08:54:28BUILDING PLAN REVIEW
 PERMIT: 07030852
 ADD: 651 OKEECHOBEE BLVD# 100
 CONT: RCC ASSOCIATES, INC
 TEL: (954)691-5385
 FBC = 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE
 POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE
 FIRST INSPECTION.
  
 3-9 ) COMPLIED.
  
 10 2ND REQUEST, 10) SHEET A201- A205 INDICATE TYPE OF
 WALL FINISHES, THEY INCLUDE WALL COVERINGS, GLASS,
 METAL LAMINATES, PANEL FABRIC, WALL PANEL & WOOD
 VENEERS, PLEASE PROVIDE THE FLAME SPREAD INDEX AND
 SMOKE DEVELOPMENT INDEX FOR EACH OF THE MATERIALS TO BE
 INSTALLED. SEE TABLE 803.5 PLEASE TAKE NOTE OF
 FOOTNOTES A, B, AND C.
 THESE ARE WALL FINISHES THAT DO NOT PROVIDE A FLAME
 SPREAD RATING:
 10A) WV-01 BRAEWOOD PREFINISHED VENEERS
 10B) WV-02 FORMICA CORDIAL CHERRY BIRDSEVE
 10C) WV-03 FORMICA KOFFE FINELINE
 10D) PF-03 PERFORMANCE SUEDE
 10E) BLAIRP 5-6 LEATHERED PLISSE ESPRESSO UPHOLSTERY
  
 11) TEXTILES;803.6 TEXTILES. WHERE USED AS INTERIOR
 WALL OR CEILING FINISH MATERIALS, TEXTILES, INCLUDING
 MATERIALS HAVING WOVEN OR NONWOVEN, NAPPED, TUFTED,
 LOOPED OR SIMILAR SURFACE, SHALL COMPLY WITH THE
 REQUIREMENTS OF THIS SECTION.
  
 803.6.1 TEXTILE WALL COVERINGS.
 TEXTILE WALL COVERINGS SHALL HAVE A CLASS A FLAME
 SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 AND BE
 PROTECTED BY AUTOMATIC SPRINKLERS INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 OR THE
 COVERING SHALL MEET THE CRITERIA OF SECTION 803.6.1.1
 OR 803.6.1.2 WHEN TESTED IN THE MANNER INTENDED FOR USE
 IN ACCORDANCE WITH NFPA 265 USING THE PRODUCT MOUNTING
 SYSTEM, INCLUDING ADHESIVE.
  
 803.6.1.1 METHOD A TEST PROTOCOL.
 DURING THE METHOD A PROTOCOL, FLAME SHALL NOT SPREAD TO
 THE CEILING DURING THE 40 KW EXPOSURE. DURING THE 150
 KW EXPOSURE, THE TEXTILE WALL COVERING SHALL COMPLY
 WITH ALL OF THE FOLLOWING:
 1.FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITY OF
 THE SAMPLE ON THE 8-FOOT BY 12-FOOT (203 MM BY 305 MM)
 WALL.
 2.THE SPECIMEN SHALL NOT BURN TO THE OUTER
 EXTREMITY OF THE 2-FOOT-WIDE (610 MM) SAMPLES MOUNTED
 IN THE CORNER OF THE ROOM.
 3.BURNING DROPLETS DEEMED CAPABLE OF IGNITING
 TEXTILE WALL COVERINGS OR THAT BURN FOR 30 SECONDS OR
 MORE SHALL NOT FORM.
 4.FLASHOVER, AS DEFINED IN NFPA 265, SHALL NOT
 OCCUR.
 5.THE MAXIMUM NET INSTANTANEOUS PEAK HEAT RELEASE
 RATE, DETERMINED BY SUBTRACTING THE BURNER OUTPUT FROM
 THE MAXIMUM HEAT RELEASE RATE, DOES NOT EXCEED 300 KW.
  
  
 803.6.1.2 METHOD B TEST PROTOCOL.
 DURING THE METHOD B PROTOCOL, FLAMES SHALL NOT SPREAD
 TO THE CEILING AT ANY TIME DURING THE 40 KW EXPOSURE.
 DURING THE 150 KW EXPOSURE, THE TEXTILE WALL COVERING
 SHALL COMPLY WITH THE FOLLOWING:
 1.FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITIES
 OF THE SAMPLES ON THE 8-FOOT BY 12-FOOT (203 MM BY 305
 MM) WALLS.
 2.FLASHOVER, AS DESCRIBED IN NFPA 265, SHALL NOT
 OCCUR.
  
 803.6.2 TEXTILE CEILING FINISH.
 WHERE USED AS A CEILING FINISH, CARPET AND SIMILAR
 TEXTILE MATERIALS SHALL HAVE A CLASS A FLAME SPREAD
 INDEX IN ACCORDANCE WITH ASTM E 84 AND BE PROTECTED BY
 AUTOMATIC SPRINKLERS.
  
 12) COMPLIED.
  
 13) 2ND REQUEST,805.5 TRIM. MATERIAL USED AS INTERIOR
 TRIM SHALL HAVE A MINIMUM CLASS C FLAME SPREAD INDEX
 AND SMOKE-DEVELOPED INDEX. COMBUSTIBLE TRIM, EXCLUDING
 HANDRAILS AND GUARDRAILS, SHALL NOT EXCEED 10 PERCENT
 OF THE AGGREGATE WALL OR CEILING AREA IN WHICH IT IS
 LOCATED.
 PLEASE PROVIDE THE PER-CENTAGES THAT THE VENEERS AND
 COMBUSTIBLE WOOD TRIM CONTRIBUTE FOR EACH WALL. 805.5
 INDICATES THAT EACH OF THESE MATERIALS SHALL HAVE A
 MINIMUM FLAME SPREAD RATING OF C" ANDSHALL NOT EXCEED
 10 PERCENT OF THE AGGREGATE WALL OR CEILING AREA IN
 WHICH IT IS LOCATED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL
 INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR
 THAT WERE NOT PART OF THIS REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
 )