2007-06-07 08:54:28 | BUILDING PLAN REVIEW |
| PERMIT: 07030852 |
| ADD: 651 OKEECHOBEE BLVD# 100 |
| CONT: RCC ASSOCIATES, INC |
| TEL: (954)691-5385 |
| FBC = 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2NDREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT. |
| NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, |
| SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE |
| POSTING OF THE |
| NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE |
| THE |
| FIRST INSPECTION. |
| |
| 3-9 ) COMPLIED. |
| |
| 10 2ND REQUEST, 10) SHEET A201- A205 INDICATE TYPE OF |
| WALL FINISHES, THEY INCLUDE WALL COVERINGS, GLASS, |
| METAL LAMINATES, PANEL FABRIC, WALL PANEL & WOOD |
| VENEERS, PLEASE PROVIDE THE FLAME SPREAD INDEX AND |
| SMOKE DEVELOPMENT INDEX FOR EACH OF THE MATERIALS TO BE |
| INSTALLED. SEE TABLE 803.5 PLEASE TAKE NOTE OF |
| FOOTNOTES A, B, AND C. |
| THESE ARE WALL FINISHES THAT DO NOT PROVIDE A FLAME |
| SPREAD RATING: |
| 10A) WV-01 BRAEWOOD PREFINISHED VENEERS |
| 10B) WV-02 FORMICA CORDIAL CHERRY BIRDSEVE |
| 10C) WV-03 FORMICA KOFFE FINELINE |
| 10D) PF-03 PERFORMANCE SUEDE |
| 10E) BLAIRP 5-6 LEATHERED PLISSE ESPRESSO UPHOLSTERY |
| |
| 11) TEXTILES;803.6 TEXTILES. WHERE USED AS INTERIOR |
| WALL OR CEILING FINISH MATERIALS, TEXTILES, INCLUDING |
| MATERIALS HAVING WOVEN OR NONWOVEN, NAPPED, TUFTED, |
| LOOPED OR SIMILAR SURFACE, SHALL COMPLY WITH THE |
| REQUIREMENTS OF THIS SECTION. |
| |
| 803.6.1 TEXTILE WALL COVERINGS. |
| TEXTILE WALL COVERINGS SHALL HAVE A CLASS A FLAME |
| SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 AND BE |
| PROTECTED BY AUTOMATIC SPRINKLERS INSTALLED IN |
| ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 OR THE |
| COVERING SHALL MEET THE CRITERIA OF SECTION 803.6.1.1 |
| OR 803.6.1.2 WHEN TESTED IN THE MANNER INTENDED FOR USE |
| IN ACCORDANCE WITH NFPA 265 USING THE PRODUCT MOUNTING |
| SYSTEM, INCLUDING ADHESIVE. |
| |
| 803.6.1.1 METHOD A TEST PROTOCOL. |
| DURING THE METHOD A PROTOCOL, FLAME SHALL NOT SPREAD TO |
| THE CEILING DURING THE 40 KW EXPOSURE. DURING THE 150 |
| KW EXPOSURE, THE TEXTILE WALL COVERING SHALL COMPLY |
| WITH ALL OF THE FOLLOWING: |
| 1.FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITY OF |
| THE SAMPLE ON THE 8-FOOT BY 12-FOOT (203 MM BY 305 MM) |
| WALL. |
| 2.THE SPECIMEN SHALL NOT BURN TO THE OUTER |
| EXTREMITY OF THE 2-FOOT-WIDE (610 MM) SAMPLES MOUNTED |
| IN THE CORNER OF THE ROOM. |
| 3.BURNING DROPLETS DEEMED CAPABLE OF IGNITING |
| TEXTILE WALL COVERINGS OR THAT BURN FOR 30 SECONDS OR |
| MORE SHALL NOT FORM. |
| 4.FLASHOVER, AS DEFINED IN NFPA 265, SHALL NOT |
| OCCUR. |
| 5.THE MAXIMUM NET INSTANTANEOUS PEAK HEAT RELEASE |
| RATE, DETERMINED BY SUBTRACTING THE BURNER OUTPUT FROM |
| THE MAXIMUM HEAT RELEASE RATE, DOES NOT EXCEED 300 KW. |
| |
| |
| 803.6.1.2 METHOD B TEST PROTOCOL. |
| DURING THE METHOD B PROTOCOL, FLAMES SHALL NOT SPREAD |
| TO THE CEILING AT ANY TIME DURING THE 40 KW EXPOSURE. |
| DURING THE 150 KW EXPOSURE, THE TEXTILE WALL COVERING |
| SHALL COMPLY WITH THE FOLLOWING: |
| 1.FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITIES |
| OF THE SAMPLES ON THE 8-FOOT BY 12-FOOT (203 MM BY 305 |
| MM) WALLS. |
| 2.FLASHOVER, AS DESCRIBED IN NFPA 265, SHALL NOT |
| OCCUR. |
| |
| 803.6.2 TEXTILE CEILING FINISH. |
| WHERE USED AS A CEILING FINISH, CARPET AND SIMILAR |
| TEXTILE MATERIALS SHALL HAVE A CLASS A FLAME SPREAD |
| INDEX IN ACCORDANCE WITH ASTM E 84 AND BE PROTECTED BY |
| AUTOMATIC SPRINKLERS. |
| |
| 12) COMPLIED. |
| |
| 13) 2ND REQUEST,805.5 TRIM. MATERIAL USED AS INTERIOR |
| TRIM SHALL HAVE A MINIMUM CLASS C FLAME SPREAD INDEX |
| AND SMOKE-DEVELOPED INDEX. COMBUSTIBLE TRIM, EXCLUDING |
| HANDRAILS AND GUARDRAILS, SHALL NOT EXCEED 10 PERCENT |
| OF THE AGGREGATE WALL OR CEILING AREA IN WHICH IT IS |
| LOCATED. |
| PLEASE PROVIDE THE PER-CENTAGES THAT THE VENEERS AND |
| COMBUSTIBLE WOOD TRIM CONTRIBUTE FOR EACH WALL. 805.5 |
| INDICATES THAT EACH OF THESE MATERIALS SHALL HAVE A |
| MINIMUM FLAME SPREAD RATING OF C" ANDSHALL NOT EXCEED |
| 10 PERCENT OF THE AGGREGATE WALL OR CEILING AREA IN |
| WHICH IT IS LOCATED. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL |
| INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR |
| THAT WERE NOT PART OF THIS REVIEW. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |