Plan Review Notes
Plan Review Notes For Permit 07030852
Permit Number 07030852
Review Stop P
Sequence Number 1
Notes
Date Text
2007-05-09 12:25:36DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ROUTE PLANS TO THE DEPARTMENT OF BUSINESS
 REGULATION, HOTEL & RESTAURANT DIVISION FOR PLAN
 REVIEW. A MINIMUM OF TWO SETS OF PLANS WITH STAMPED
 SHEETS FROM DBPR WITH THE TWO PAGE "WORKSHEETS"
 ATTACHED TO THE STAMPED SHEET SHALL BE RESUBMITTED FOR
 REVIEW. SECTION 102.2.1.
  
 2. GREASE INTERCEPTORS SHALL BE SIZED AND INSPECTED BY
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO
 (561) 822-2272 OR CALVIN WILLIAMS(561) 822-2284.
 THEIR FAX NUMBER IS (561) 822-2287. E-MAIL
 [email protected]@WPB.ORG. PLEASE INDICATE
 THEIR RESPONSE. ARTICLE III 90-124(7).
  
 3. ALL SHEETS WITH AOA ASSOCIATES TITLE BLOCK. THE
 ARCHITECTS BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61G1-16.004(2) & FS 481.219, 481.2055.
  
 4. SHT T101 INDEX OF DRAWINGS DOES NOT REFLECT THE
 SHEETS SUBMITTED. SHEETS M101 & P402 ARE NOT SHOWN ON
 THE INDEX. SHTS M102, M301, M302, M303 & E100 ARE SHOWN
 ON THE INDEX BUT NOT SUBMITTED. PLEASE CORRELATE THE
 INDEX WITH SHEETS SUBMITTED. SECTION 106.1.1.
  
 5. SHT T101 APPLICABLE CODES ACCESSIBILITY INDICATES
 2001. WE HAVE SINCE ADPOTED THE FBC-2004 ACCESSIBLITY
 CODE. (CHAPTER 11). PLEASE CHANGE CODE REFERENCE.
  
 6. SHT A400 DETAILS 1 & 2 GRAB BARS FOR THE WATER
 CLOSETS AT THE SIDE SHALL BE 42". SEE FIG 11-30E.--
 DETAIL 4 SHOW THE WATER CLOSET TO BE 1'7" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE. 1'6" IS REQUIRED. SEE
 FIG 11-30E.7.
  
 7. SHT A400 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR
 URINAL
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 __FOR LAVS
 A MINIMUM 1 LAV OUTSIDE THE ACCESSIBLE STALL SHALL
 COMPLY WITH SECTION 11-4.19 AND ALL SUBSECTIONS.
 FORWARD APPROACH REQUIRED AND SHALL EXTEND UNDERNEATH
 THE LAV A MINIMUM 19" PLEASE SUBMIT A DETAIL FOR THE
 ACCESSIBLE LAV OUTSIDE THE ACCESSIBLE STALL.
  
 8. SHT A401 DETAILS 1 & 2 FORWARD APPROACH REQUIRED FOR
 THE CLEAR FLOOR SPACE FOR AT LEAST ONE LAV OUTSIDE THE
 ACCESSIBLE STALL PER SECTION 11-419.3.
  
 9. SHT A600 ROOM 113 EMPLOYEES RESTROOM CALLS FOR BCT-1
 FOR THE FLOOR. THE FINISH KEY SHT A602 DOES NOT
 INDICATE WHAT BCT-1 REPRESENTS. PLEASE CLARIFY.
 SECTIONS 106.1.1 & 1210.1.
  
 10. SHT A600 FINISH SCHEDULE FOR ROOMS 110 & 111 STATE
 "SEE EL" FOR THE BASE, BUT THE BASE FOR THE WALLS BY
 THE W/C'S & URINALS DO NOT INDICATE THE MATERIAL FOR
 THE BASE. PLEASE CLARIFY. SECTIONS 106.1.1 & 1210.1.
  
 11. SHT A600 WALLS FOR THE W/C'S AND URINALS IN ROOMS
 110 & 111 INDICATE CT-3 ON THE ELEVATIONS, BUT CT-3 IS
 NOT INDICATED ON THE FINISH SCHEDULE. PLEASE CLARIFY.
 SECTIONS 106.1.1. & 1210.2.
  
 12. SHT A600 ROOM 113 WALLS CALL FOR PT-1B. SECTION
 1210.2 CALLS FOR A SMOOTH, HARD, NONABSORBENT SURFACE
 WITHIN 2' OF THE W/C. PAINT DOES NOT COMPLYWITH
 REQUIREMENT FOR A HARD SURFACE. PLEASE SHOW
 COMPLIANCE.
  
 13. ALL MECHANICAL & PLUMBING SHEETS. THE ENGINEERS
 SIGNATURE IS REQUIRED ON EACH SHEET. IT APPEARS THAT
 INITIALS HAVE BEEN USED. IF INDEED THIS IS THE LEGAL
 SIGNATURE, A SIGNED, SEALED, NOTORIZED LETTER
 INDICATING THE LEGAL SIGNATURE SHALL BE SUBMITTED FOR
 OUR FILES. FAC 61G15-23.002(1)(2) & FS 471.025.
  
 14. SHT P001 GENERAL NOTES #3. THE SANITARY PIPING
 SHALL BE INSTALLED PER TABLE 704.1. ALL PIPE 2-1/2" AND
 SMALLER SHALL BE SLOPED 1/4"/FT. PLEASE ADJUST NOTE TO
 REFLECT THIS REQUIREMENT.
  
 15. SHT P001 GENERAL NOTES #30. DIELECTRIC UNIONS ARE
 MANUF. FOR GAS SYSTEMS ONLY. FOR USE IN A WATER SYSTEM
 A DIELECTRIC COUPLING SHALL BE USED. PLEASE ADJUST NOTE
 TO REFLECT THIS REQUIREMENT.
  
 16. SUBMIT A SANITARY RISER DIAGRAM FOR THE PIPING TO
 THE SECOND FLOOR MECHANICAL ROOM. SECTION
 106.3.5.1.3(4)(6)(13).
  
 17. SHT P301 PLUMBING/WASTE SCHEDULE. SHOW ALL MARK
 DESIGNATIONS ON THE ENLARGED KITCHEN WASTE PLAN THAT
 CORRELATES WITH THE SCHEDULE. AT THIS POINT THE KITCHEN
 EQUIPMENT CAN NOT BE IDENTIFIED WITHOUT MARK
 DESIGNATIONS. SECTION 106.1.1.
  
 18. SHT P301. PLUMBING/WASTE SCHEDULE. P36-C & P36-H
 INDICATES QTY 6, BUT ONLY 5 WERE FOUND.PLEASE
 CORRELATE. SECTION 106.1.1.
  
 19. SHT P301 PLUMBING/WATER SCHEDULE ITEMS P31-C &
 P39-F INDICATE A WATER FILTER. WATER FILTERS MUST MEET
 THE REQUIREMENTS OF NSF 42. PLEASE SUBMIT MANUF
 SPECIFICATION SHEETS SHOWING COMPLIANCE. SECTION
 611.1.
  
 20. SHT P301 PLUMBING/WATER SCHEDULE. MARK P33-F
 INDICATES QTY 4, BUT ONLY 2 WERE FOUND. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 21. SHT P301 PLUMBING/GAS SCHEDULE. PK104 DESCRIPTION &
 REMARKS INDICATED A GAS DROP BY THE GENERAL CONTRACTOR.
 ALL GAS WORK SHALL BE BY THE PLUMBING CONTRACTOR.
 PLEASE CHANGE REFERENCE. FS 489.105(M).
  
 22. SHT P302 IDENTIFY ALL FIXURES/APPLIANCES TO REFLECT
 THE MARK NUMBERS INDICATED ON THE PLUMBING/WASTE
 SCHEDULE. MORE INFORMATION IS REQUIRED SECTION
 106.2.1.
  
 23. SHT P302 THE DISHWASHER, (ITEM 55 ON SHT P301),
 SHALL CONNECT TO THE SANITARY SYSTEM, NOT THE GREASE
 SYSTEM. CITY CODE ARTICLE III SECTION 90-124(7)(B).
 PLEASE CHANGE FLOOR PLAN PIPING.
  
 24. SHT P304 BAR SANITARY/WASTE PLAN. DRY HORIZONTAL
 VENTS ARE PROHIBITED. SECTION 905.3. EVERY DRY VENT
 CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE
 THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. ALSO SEE
 SECTION 905.4.
  
 25. SHT P401. DOMESTIC WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN FOR FIXTURES P88-C, P36-C -
 P36-H, (BY P98) & P55-H. PLEASE CORRELATE THE RISER AND
 FLOOR PLAN INFORMATIONS. SECTION 106.1.1.
  
 26. SHT P401 FULL OPEN VALVES ARE REQUIRED ON THE WATER
 SUPPLY PIPE TO EVERY W/H. SECTION 606.1(7).
  
 27. SHT P401 A WATER HAMMER ARRESTOR IS REQUIRED ON THE
 WATER SUPPLY TO P55-H WHEN DRAWN ON THE RISER DIAGRAM.
 SECTION 604.9.
  
 28. SHT P402 KITCHEN WASTE& VENT RISER DIAGRAM. THE
 FLOOR SINK FOR THE DISH WASHER SHALL CONNECT TO THE
 SANITARY SYSTEM, NOT THE GREASE SYSTEM. ARTICLE III
 SECTION 90-124(7)(B). PLEASE CHANGE RISER DIAGRAM.
  
 29. SHT P402. BAR WASTE AND VENT RISER DIAGRAM. DRY
 HORIZONTAL VENTS ARE PROHIBITED. SECTION 905.3. EVERY
 DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. ALSO
 SEE SECTION 905.4.
  
 30. SHT P402 THE FOLLOWING IS REQUIRED FOR THE GAS
 PERMIT APPROVAL:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 C. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 E. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 31. SHT P501 GAS INSTANT WATER HEATER PIPING SCHEMATIC.
 THE DIRT LEGS SHALL BE DOWNSTREAM OF THE GAS SHUT OFF
 VALVES. SECTION 408.4.
  
 32. SHT P501 FLOOR SINK DETAIL. THE AIR GAP SHALL BE A
 MINIMUM OF TWICE THE EFFECTIVE OPENING OF THE INDIRECT
 WASTE PIPE. SECTION 802.2.1.-- THE FLOOR SINK SHALL
 BE SET 1" ABOVE THE FINISHED FLOOR AS IT IS FOR
 INDIRECT WASTE ONLY, NOT A FLOOR DRAIN.PLEASE ADJUST
 THE FLOOR SINK DETAIL.
  
 33. SHT PD201 GENERAL NOTES #2 DEAD ENDS ARE
 PROHIBITED. ALL DEMO'D & CAPPED PIPING SHALL BE LEFT
 UNCOVERED UNTIL FIELD INSPECTOR'S APPROVAL. SECTION
 704.5.
  
 34. SHT PD201 GENERAL NOTES #3 & #10 HAVE NOT BEEN
 LOCATED. PLEASE CLARIFY. SECTION 106.1.1.
  
 35. SHT PD202 GENERAL NOTES #1 DEAD ENDS ARE
 PROHIBITED. ALL DEMO'D & CAPPED PIPING SHALL BE LEFT
 UNCOVERED UNTIL FIELD INSPECTOR'S APPROVAL. SECTION
 704.5.
  
 36. TO HELP EXPEDITE PLAN REVIEW, PLEASE RESUBMIT THE
 MARKED UP PLUMBING PLANS ALONG WITH THE NEW PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  