2007-04-23 16:28:38----------------DENIED--------------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH 1 AS AMENDED BY THE CITY OF WEST PALM BEACH
 NFPA 90A
 NFPA 96
 ASHRAE 62.1-2004
  
 1. M001 GENERAL NOTE #15: AIR CONDITIONING CONDENSATE
 SHALL NOT BE DISCHARGED INTO WASTE WATER PIPING PER
 W.P.B. MUNICIPAL CODE SEC 90-125(B)(5)
  
 2. M001: GENERAL NOTE #31 IS IN CONFLICT WITH DETAIL
 DRAWINGS ON M002. PLEASE COORDINATE NOTES AND DETAILS
 ON 0DRAWINGS. FBC 106.1.1
  
 3. M001: GENERAL NOTE #40 IS IN CONFLICT WITH GENERAL
 NOTE #31 AND DETAILS ON M002. PLEASE COORDINATE NOTES
 AND DETAILS ON DRAWINGS. FBC 106.1.1
  
 4. M101 VENTILATION TABLE: PLEASE REFERENCE CORRECT
 ASHRAE STANDARD TO BE USED IN DETERMINING VENTILATION
 REQUIREMENTS: ASHRAE 62.1-2004 PER FBC,M 304.3.
  
 5. M101: EQUIPMENT OVER HARD CEILINGS REQUIRE ACCESS
 AND SERVICE SPACE PER FBC,M 306.1 AND 306.3.
  
 6. M101: AHU 4 RETURN DUCT SHOWS A RETURN OPENING ON
 SIDE OF 36X16 DUCT. DOES THIS HAVE A MOTORIZED AND
 MANUAL DAMPER? WHAT IS THE SIZE OF THE OPENING? HOW
 MANY CFM OF RETURN? IS THIS SPACE TO BE USED AS A
 PLENUM? IF SO, EXHAUST DUCTS UNDER POSITIVE PRESSURE
 SHALL NOT BE LOCATED IN A PLENUM PER FBC,M 601.3.
  
 7. M101: OA DUCT FOR AHU 7 APPEARS TO BE MARKED AS 10'
 ROUND AND 12" ROUND. PLEASE CLARIFY.
  
 8. M101 OA DUCT FOR AHU 6: PLEASE SHOW SIZE OF OA DUCT
 FOR AHU 6 ON PLANS.
  
 9. M101 AHU 2: THERE ARE 4 DROPS MISSING CFM, 3 OF THEM
 ARE ALSO MISSING SIZE. PLEASE CLARIFY.
  
 10. M100 WALK-IN COOLER CONDENSERS: BY WHAT MEANS WILL
 COPPER LINES FOR WALK-INS BE ROUTED INTO BUILDING?
 PLEASE PRIVIDE DETAILED INSTRUCTIONS. REFRIGERANNT
 PIPING TO COMPLY WITH FBC,M 1107.2.1
  
 NOTE: SEPARATE PERMITS REQUIRED FOR KITCHEN HOODS, HOOD
 SUPPRESSION SYSTEMS AND WALK-IN COOLERS/FREEZERS.
  
  
 ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561,805.6719
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved