2007-05-17 12:22:08 | *****DENIED***** |
| |
| |
| 01.THE COMPLETE ADDRESS, INCLUDING THE SUITE NUMBER, |
| SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN |
| SHEET. |
| |
| 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION AND THE |
| FLORIDA FIRE PREVENTION CODE - 2004 EDITION SHALL BE |
| REFERENCED.AMEND SHEET T101, UNDER APPLICABLE CODES. |
| |
| 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 04.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF |
| NEW BUILDING MATERIALS SHALL NOT HINDER OR INTERFERE |
| WITH EMERGENCY ACCESS TO THE PROPERTY OR VICINITY |
| THEREOF (INCLUDING FIRE LANES). |
| |
| 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| SHALL BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY |
| AS NECESSARY FOR SAFE OPERATRIONS. |
| |
| 06.ON THE APPROPIATE EXTERIOR ELEVATION (SHEET A200), |
| DISPLAY THE SUITE NUMBER FOR THIS PROJECT.AS PER WEST |
| PALM BEACH CODE,SUITE NUMBERS SHALL BE NO LESS THAN |
| 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. |
| |
| 07.ON SHEET F001, FIRE PROTECTION NOTE #1, REFERENCE |
| NFPA 13 - 2002 EDITION. |
| |
| 08.ON SHEET ED101 & ED102, GENERAL NOTE (D.), MIKE |
| CARSILLO, NOT CARSICCO, SHOULD BE LISTED AS THE FIRE |
| MARSHAL. |
| |
| 09.IT APPEARS THAT THE EXIT LIGHTS ARRANGEMENT ON |
| SHEETS EL101- EL102 DO NOT CORRELATE TO LS101- LS102. |
| |
| 10.NO EMERGENCY LIGHTING NOTED. |
| |
| 11.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE |
| WITH NFPA 96 - 2001 EDITION. |
| |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE EACH ITEM WAS ADRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |