Plan Review Notes
Plan Review Notes For Permit 07030852
Permit Number 07030852
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-05-17 12:22:08*****DENIED*****
  
  
 01.THE COMPLETE ADDRESS, INCLUDING THE SUITE NUMBER,
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION AND THE
 FLORIDA FIRE PREVENTION CODE - 2004 EDITION SHALL BE
 REFERENCED.AMEND SHEET T101, UNDER APPLICABLE CODES.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING FIRE LANES).
  
 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY
 AS NECESSARY FOR SAFE OPERATRIONS.
  
 06.ON THE APPROPIATE EXTERIOR ELEVATION (SHEET A200),
 DISPLAY THE SUITE NUMBER FOR THIS PROJECT.AS PER WEST
 PALM BEACH CODE,SUITE NUMBERS SHALL BE NO LESS THAN
 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
 07.ON SHEET F001, FIRE PROTECTION NOTE #1, REFERENCE
 NFPA 13 - 2002 EDITION.
  
 08.ON SHEET ED101 & ED102, GENERAL NOTE (D.), MIKE
 CARSILLO, NOT CARSICCO, SHOULD BE LISTED AS THE FIRE
 MARSHAL.
  
 09.IT APPEARS THAT THE EXIT LIGHTS ARRANGEMENT ON
 SHEETS EL101- EL102 DO NOT CORRELATE TO LS101- LS102.
  
 10.NO EMERGENCY LIGHTING NOTED.
  
 11.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE
 WITH NFPA 96 - 2001 EDITION.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  