Plan Review Notes
Plan Review Notes For Permit 07030852
Permit Number 07030852
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-31 17:00:41** UNSAT **
  
 *RUTH CHRIS*
 INTERIOR BUILD-OUT W/ SOME EXTERIOR WORK.
 PREVIOUS OCCUPANCY: BUSINESS.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE SOME AREAS WHICH STATE CODES WHICH ARE
 NOT YET ADOPTED BY THE STATE OR CODES WHICH ARE NO
 LONGER IN EFFECT. PLEASE GO OVER PLANS AS CODES AND
 SECTIONS ARE STATED FROM SEVERAL CODES.
 PLEASE SEE THE PLANS STATES THE 2001 FBC FOR ADA
 COMPLIANCE; HOWEVER THIS SHOULD BE THE 2004 W/ 2006
 REVISIONS. THE 2004 FBC WENT INTO EFFECT ON OCT. 1ST,
 2005.
 PLEASE SEE AREAS WHERE THE PLANS INDICATE THE 2007
 NFPA-72 AND 2006 NFPA-101. SEE CODES ABOVE FOR RELEVANT
 ADOPTED CODES.
 PLEASE SEE OTHER REFERENCES TO ADA WHICH SHOULD BE
 NOTED TO THE 2004 FBC.
  
 2) NOTE: PLEASE SEE MISSING FIRM LICENSE NUMBER FOR THE
 ARCHITECTURAL FIRM AS REQUIRED ON TITLE BLOCKS PER FAC
 61G1-16.004 AND FS 481.219.
 PLEASE SEE THIS INFORMATION IS REQUIRED FOR ALL TRADES
 AND FOR ALL SHEETS WHICH CONTAIN THIS TITLE BLOCK
 WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADE
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE SEVERAL ARCHITECTURAL SHEETS IN THE
 PLANS ARE NOT SIGNED OR SEALED. PLEASE SEE SHEETS
 T-101, LS (BOTH) AND SHEET A-100 THRU A-205. PLEASE SEE
 FS 481.221.
  
 4) NOTE: PLEASE SEE SHEETS FOR ARCHITECTURAL AND SOME
 ENGINEERING SHEETS APPEAR TO BE SIGNED WITH *INITIALS*,
 IF THESE ARE INDEED THE LEGAL SIGNATURES OF THESE
 DESIGNERS, PLEASE PROVIDE SIGNED, DATED AND SEALED
 LETTERS FOR SIGNATURE VERIFICATION. THESE WILL BE
 PLACED IN OUR SIGNATURE FILE FOR ANY NEED OF FUTURE
 PROJECTS OR REFERENCE.
 PLEASE BE SURE LETTERS ARE ALSO PROPERLY NOTARIZED PER
 FS 117.05.
 ** THIS COMMENT IS FOR MR. DOUGLAS AND MR. LIZASOAIN.
  
 5) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA
 SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
  
 6) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1,
 .1.2 AND .1.3. PLEASE SEE LIGHTING DIMMING PANELS ARE
 SHOWN HOWEVER COMPLIANCE WITH THE 2004 FBC W/2006
 REVISIONS IS NOT SHOWN AT THIS TIME.
 PLEASE SUBMIT LIGHTING POWER DENSITIES PER THE 2004 FBC
 W/ 2006 REVISION. PLEASE SEE 13-415.1.AB.1.1, 13-415.2
 FOR LIGHTING PERFORMANCE CALCULATIONS WHICH ARE TO
 CORRELATE WITH THE ENERGY CALCULATIONS SUBMITTED.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT INDICATE ALL
 THE FIXTURES, TYPES AND WATTAGE PER FIXTURE AS
 REQUIRED.
 PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC
 FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE
 LPD/CALCULATIONS TO BE REVIEWED FOR COMPLIANCE. PLEASE
 SUBMIT SCHEDULING IF A LIGHTING CONTROL SYSTEM IS
 INSTALLED.
 PLEASE INDICATE ALL OVER RIDE DEVICES AND LOCATIONS ON
 PLANS.
 PLEASE STATE ALL MAXIMUM OVER RIDE TIMES.
 PLEASE SEE MISSING EXTERIOR LIGHTING ALLOWANCES ON
 PLANS/ENERGY CALCULATIONS.
 PLEASE SEE THE ENERGY CALCULATIONS INDICATE *MANUAL
 ON/OFF* FOR METHOD OF LIGHTING CONTROL, HOW IS THIS
 POSSIBLE WHEN LIGHTING IS REQUIRED TO BE AUTOMATED.
 PLEASE BE SURE TO HAVE THE DESIGNER OF RECORD FOR THE
 ENERGY CALCULATIONS SIGN, DATE AND SEAL THESE AS
 REQUIRED PER 13-103.1.1.1
 ** PLEASE KNOW THAT AS MUCH OF THIS INFORMATION HAS NOT
 YET BEEN SUBMITTED, MANY OF THESE THINGS CAN NOT YET BE
 REVIEWED FOR CODE COMPLIANCE.
  
 7) NOTE: PLEASE SEE THE SQUARE FOOTAGE ON T-101 SHEET
 DOES NOT CORRELATE WITH THE SQ FT ON THE ENERGY
 CALCULATIONS.
 PLEASE CORRELATE. FBC 106.1.2
  
 8) NOTE: PLEASE KNOW THAT THE SIGNS AS SHOWN ON THE
 ELEVATIONS ON PLANS WILL BE UNDER SEPARATE PERMITS.
 THIS IS ONLY NOTED AND NO CHANGES NEED TO BE MADE.
  
 9) NOTE: PLEASE INDICATE THE EXISTING OR NEW
 TRANSFORMER GROUND PER 250.20,250.30, 250.66. PLEASE
 INDICATE THE ATTACHMENT POINT.
  
 10) NOTE: PLEASE CLARIFY RISER AS THE SERVICE IS BEING
 SHOWN AS ONE EXISTING SERVICE YET THIS BUILD OUT IS
 BEING DONE FROM WHAT USED TO BE TWO SEPARATE TENANTS.
 WHAT IS BEING DONE WITH THE SERVICE WHICH USED TO FEED
 THE PREVIOUS TENANT WHO IS BEING TAKEN OVER/EXPANDED?
 FBC 106.1.2
  
 11) NOTE: PLEASE SPECIFY THE SERVICE EQUIPMENT,
 ELECTRICAL PANELS, AND TRANSFORMER LOCATIONS. ARE THESE
 LOCATED IN AN ELECTRICAL ROOM?
 PLEASE PROVIDE ROOM AND AREA DESIGNATIONS FOR ALL AREAS
 AND ROOMS.
 110.26, 240.24, 450.11, 450.13 ETC
 PLEASE INDICATE HOW THE TRANSFORMER IS MOUNTED.
 EXISTING FLOOR?
  
 12) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED
 ARE NOT COMPLETED AT THIS TIME. PLEASE SEE THE LOAD
 SUMMARY WHICH DOES NOT SHOW ANY LIGHTING LOADS? PLEASE
 SHOW. 215.3, 230.42, 220.12, 220.14, 220.42, 220.43,
 220.44, ETC.
  
 13) NOTE: PLEASE SEE MISSING SIGN CIRCUIT PER 600.5,
 PLEASE INDICATE MINIMUM LOADS REQUIRED.
 PLEASE ALSO SEE 210.62 FOR MISSING WINDOW RECEPTACLES
 AND LOADS PER 220.43.
  
 14) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 ON THE LIGHTING CONTROL PANELS.
 PLEASE SEE NOTE #6 AS ONLY DIMMING PANELS ARE BEING
 SHOWN.
 110.3, 90.7.
 FBC 106.1.2
  
 15) NOTE: PLEASE SEE 2005 NEC 210.8B3 AS ALL 15/20AMP
 120V RECEPTACLES IN KITCHEN AREAS AND THE LIKE SHALL BE
 GFI/GFI PROTECTED. PLEASE SEE PANEL SCHEDULE NOTES SOME
 OF THESE BUT NOT ALL.
  
 16) NOTE: PLEASE PROVIDE SHUNT DETAIL FOR CONNECTION
 AND SHUT OFF OF ALL ELECTRICAL TO HOOD. NFPA-96. FBC
 106.1.2
  
 17) NOTE: PLEASE CONFIRM TIMES ON EMERGENCY LIGHTING
 FIXTURES AS NOTED ON LEGEND.
 PLEASE SEE NFPA-101 7.8, 7.9
 PLEASE ALSO SUBMIT PHOTO-METRICS FOR MINIMUM LEVELS OF
 LIGHTING FOR STAIRS AND EGRESS PATHS PER NFPA-101
 7.8.1.3, 7.9.2.2.
 THIS REQUIRES A MINIMUM OF 10FT CANDLES UNDER NORMAL
 FOR STAIRS AND IS PERMITTED TO DOWN TO 1FC UNDER
 EMERGENCY CONDITIONS.
 THIS IS REQUIRED FOR LIFE SAFETY AND TRIPPING HAZARDS.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED, THERE MAY NEW COMMENTS ON THE FOLLOWING
 REVIEW ONCE PLANS ARE COMPLETED FOR REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]