2007-03-31 17:00:41 | ** UNSAT ** |
| |
| *RUTH CHRIS* |
| INTERIOR BUILD-OUT W/ SOME EXTERIOR WORK. |
| PREVIOUS OCCUPANCY: BUSINESS. |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLEASE SEE SOME AREAS WHICH STATE CODES WHICH ARE |
| NOT YET ADOPTED BY THE STATE OR CODES WHICH ARE NO |
| LONGER IN EFFECT. PLEASE GO OVER PLANS AS CODES AND |
| SECTIONS ARE STATED FROM SEVERAL CODES. |
| PLEASE SEE THE PLANS STATES THE 2001 FBC FOR ADA |
| COMPLIANCE; HOWEVER THIS SHOULD BE THE 2004 W/ 2006 |
| REVISIONS. THE 2004 FBC WENT INTO EFFECT ON OCT. 1ST, |
| 2005. |
| PLEASE SEE AREAS WHERE THE PLANS INDICATE THE 2007 |
| NFPA-72 AND 2006 NFPA-101. SEE CODES ABOVE FOR RELEVANT |
| ADOPTED CODES. |
| PLEASE SEE OTHER REFERENCES TO ADA WHICH SHOULD BE |
| NOTED TO THE 2004 FBC. |
| |
| 2) NOTE: PLEASE SEE MISSING FIRM LICENSE NUMBER FOR THE |
| ARCHITECTURAL FIRM AS REQUIRED ON TITLE BLOCKS PER FAC |
| 61G1-16.004 AND FS 481.219. |
| PLEASE SEE THIS INFORMATION IS REQUIRED FOR ALL TRADES |
| AND FOR ALL SHEETS WHICH CONTAIN THIS TITLE BLOCK |
| WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADE |
| REVIEWER(S). |
| |
| 3) NOTE: PLEASE SEE SEVERAL ARCHITECTURAL SHEETS IN THE |
| PLANS ARE NOT SIGNED OR SEALED. PLEASE SEE SHEETS |
| T-101, LS (BOTH) AND SHEET A-100 THRU A-205. PLEASE SEE |
| FS 481.221. |
| |
| 4) NOTE: PLEASE SEE SHEETS FOR ARCHITECTURAL AND SOME |
| ENGINEERING SHEETS APPEAR TO BE SIGNED WITH *INITIALS*, |
| IF THESE ARE INDEED THE LEGAL SIGNATURES OF THESE |
| DESIGNERS, PLEASE PROVIDE SIGNED, DATED AND SEALED |
| LETTERS FOR SIGNATURE VERIFICATION. THESE WILL BE |
| PLACED IN OUR SIGNATURE FILE FOR ANY NEED OF FUTURE |
| PROJECTS OR REFERENCE. |
| PLEASE BE SURE LETTERS ARE ALSO PROPERLY NOTARIZED PER |
| FS 117.05. |
| ** THIS COMMENT IS FOR MR. DOUGLAS AND MR. LIZASOAIN. |
| |
| 5) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA |
| SHEETS SUBMITTED. |
| ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM |
| SETS. |
| FBC 106.3.5.1.2 |
| |
| 6) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC |
| CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1, |
| .1.2 AND .1.3. PLEASE SEE LIGHTING DIMMING PANELS ARE |
| SHOWN HOWEVER COMPLIANCE WITH THE 2004 FBC W/2006 |
| REVISIONS IS NOT SHOWN AT THIS TIME. |
| PLEASE SUBMIT LIGHTING POWER DENSITIES PER THE 2004 FBC |
| W/ 2006 REVISION. PLEASE SEE 13-415.1.AB.1.1, 13-415.2 |
| FOR LIGHTING PERFORMANCE CALCULATIONS WHICH ARE TO |
| CORRELATE WITH THE ENERGY CALCULATIONS SUBMITTED. |
| PLEASE SEE THE ENERGY CALCULATIONS DO NOT INDICATE ALL |
| THE FIXTURES, TYPES AND WATTAGE PER FIXTURE AS |
| REQUIRED. |
| PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC |
| FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE |
| LPD/CALCULATIONS TO BE REVIEWED FOR COMPLIANCE. PLEASE |
| SUBMIT SCHEDULING IF A LIGHTING CONTROL SYSTEM IS |
| INSTALLED. |
| PLEASE INDICATE ALL OVER RIDE DEVICES AND LOCATIONS ON |
| PLANS. |
| PLEASE STATE ALL MAXIMUM OVER RIDE TIMES. |
| PLEASE SEE MISSING EXTERIOR LIGHTING ALLOWANCES ON |
| PLANS/ENERGY CALCULATIONS. |
| PLEASE SEE THE ENERGY CALCULATIONS INDICATE *MANUAL |
| ON/OFF* FOR METHOD OF LIGHTING CONTROL, HOW IS THIS |
| POSSIBLE WHEN LIGHTING IS REQUIRED TO BE AUTOMATED. |
| PLEASE BE SURE TO HAVE THE DESIGNER OF RECORD FOR THE |
| ENERGY CALCULATIONS SIGN, DATE AND SEAL THESE AS |
| REQUIRED PER 13-103.1.1.1 |
| ** PLEASE KNOW THAT AS MUCH OF THIS INFORMATION HAS NOT |
| YET BEEN SUBMITTED, MANY OF THESE THINGS CAN NOT YET BE |
| REVIEWED FOR CODE COMPLIANCE. |
| |
| 7) NOTE: PLEASE SEE THE SQUARE FOOTAGE ON T-101 SHEET |
| DOES NOT CORRELATE WITH THE SQ FT ON THE ENERGY |
| CALCULATIONS. |
| PLEASE CORRELATE. FBC 106.1.2 |
| |
| 8) NOTE: PLEASE KNOW THAT THE SIGNS AS SHOWN ON THE |
| ELEVATIONS ON PLANS WILL BE UNDER SEPARATE PERMITS. |
| THIS IS ONLY NOTED AND NO CHANGES NEED TO BE MADE. |
| |
| 9) NOTE: PLEASE INDICATE THE EXISTING OR NEW |
| TRANSFORMER GROUND PER 250.20,250.30, 250.66. PLEASE |
| INDICATE THE ATTACHMENT POINT. |
| |
| 10) NOTE: PLEASE CLARIFY RISER AS THE SERVICE IS BEING |
| SHOWN AS ONE EXISTING SERVICE YET THIS BUILD OUT IS |
| BEING DONE FROM WHAT USED TO BE TWO SEPARATE TENANTS. |
| WHAT IS BEING DONE WITH THE SERVICE WHICH USED TO FEED |
| THE PREVIOUS TENANT WHO IS BEING TAKEN OVER/EXPANDED? |
| FBC 106.1.2 |
| |
| 11) NOTE: PLEASE SPECIFY THE SERVICE EQUIPMENT, |
| ELECTRICAL PANELS, AND TRANSFORMER LOCATIONS. ARE THESE |
| LOCATED IN AN ELECTRICAL ROOM? |
| PLEASE PROVIDE ROOM AND AREA DESIGNATIONS FOR ALL AREAS |
| AND ROOMS. |
| 110.26, 240.24, 450.11, 450.13 ETC |
| PLEASE INDICATE HOW THE TRANSFORMER IS MOUNTED. |
| EXISTING FLOOR? |
| |
| 12) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED |
| ARE NOT COMPLETED AT THIS TIME. PLEASE SEE THE LOAD |
| SUMMARY WHICH DOES NOT SHOW ANY LIGHTING LOADS? PLEASE |
| SHOW. 215.3, 230.42, 220.12, 220.14, 220.42, 220.43, |
| 220.44, ETC. |
| |
| 13) NOTE: PLEASE SEE MISSING SIGN CIRCUIT PER 600.5, |
| PLEASE INDICATE MINIMUM LOADS REQUIRED. |
| PLEASE ALSO SEE 210.62 FOR MISSING WINDOW RECEPTACLES |
| AND LOADS PER 220.43. |
| |
| 14) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| ON THE LIGHTING CONTROL PANELS. |
| PLEASE SEE NOTE #6 AS ONLY DIMMING PANELS ARE BEING |
| SHOWN. |
| 110.3, 90.7. |
| FBC 106.1.2 |
| |
| 15) NOTE: PLEASE SEE 2005 NEC 210.8B3 AS ALL 15/20AMP |
| 120V RECEPTACLES IN KITCHEN AREAS AND THE LIKE SHALL BE |
| GFI/GFI PROTECTED. PLEASE SEE PANEL SCHEDULE NOTES SOME |
| OF THESE BUT NOT ALL. |
| |
| 16) NOTE: PLEASE PROVIDE SHUNT DETAIL FOR CONNECTION |
| AND SHUT OFF OF ALL ELECTRICAL TO HOOD. NFPA-96. FBC |
| 106.1.2 |
| |
| 17) NOTE: PLEASE CONFIRM TIMES ON EMERGENCY LIGHTING |
| FIXTURES AS NOTED ON LEGEND. |
| PLEASE SEE NFPA-101 7.8, 7.9 |
| PLEASE ALSO SUBMIT PHOTO-METRICS FOR MINIMUM LEVELS OF |
| LIGHTING FOR STAIRS AND EGRESS PATHS PER NFPA-101 |
| 7.8.1.3, 7.9.2.2. |
| THIS REQUIRES A MINIMUM OF 10FT CANDLES UNDER NORMAL |
| FOR STAIRS AND IS PERMITTED TO DOWN TO 1FC UNDER |
| EMERGENCY CONDITIONS. |
| THIS IS REQUIRED FOR LIFE SAFETY AND TRIPPING HAZARDS. |
| |
| ** PLEASE KNOW AS THERE IS INFORMATION NOT YET |
| SUBMITTED, THERE MAY NEW COMMENTS ON THE FOLLOWING |
| REVIEW ONCE PLANS ARE COMPLETED FOR REVIEW. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |