2007-05-16 09:24:29 | BUILDING PLAN REVIEW |
| PERMIT: 07030852 |
| ADD: 651 OKEECHOBEE BLVD# 100 |
| CONT: RCC ASSOCIATES, INC |
| TEL: (954)691-5385 |
| FBC = 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT. |
| NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, |
| SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE |
| POSTING OF THE |
| NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE |
| THE |
| FIRST INSPECTION. |
| |
| 3) SHEET T-101, APPLICABLE CODES- THE 2001 |
| ACCESSIBILITY CODE IS THE WRONG CODE PLEASE CORRECT TO |
| THE 2004 FBC CHAPTER 11FLORIDA ACCESSIBILITY CODE |
| |
| 4) SHEET T-101, APPLICABLE CODES- PREVIOUS OCCUPANCY |
| WAS ALSO A RESTAURANT: A2 OCCUPANCY |
| |
| 5) SHEET T-101, CONSTRUCTION TYPE: THIS IS A HIGH RISE |
| BUILDING REQUIRING TYPE IA CONSTRUCTION. |
| |
| 6) IN THE SEET OF PLANSREVIEWED THE DESIGNER OF |
| RECORD MISSED SIGNING AND SEALING THE T, LS ANDQUITE |
| A FEW A SHEETS. |
| PLANS, SPECIFICATIONS, REPORTS OR |
| OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| BEING FILED FOR PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| TO THE DOCUMENT. |
| FL STATE STAT: 61G15-23.002 ENGINEERS |
| FL ATATE STAT: 61G16.003 ARCHITECTS |
| |
| 7)VOA ASSOCIATES INCORP. DOESN'T INDICATE THEIR |
| CERTIFICATE OF AUTHORIZATION. |
| 481.219 F.S.CERTIFICATE OF |
| AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| SHEET BEARING THE NAME OF AN ARCHITECT |
| PRACTICING UNDER A FICTITIOUS NAME, A |
| CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL |
| SERVICES, SHALL INCLUDE |
| THE CERTIFICATE OF AUTHORIZATION |
| NUMBER.ADD THE NUMBER TO EACH SHEET. |
| THIS MAY BE ADDED BY HAND. |
| |
| 8)ON SHEET A101 THIS SHEET INDICATES A KITHEN BUT NO |
| FREEZERS NOR WALK IN COOLERS ARE SHOWN, |
| WILL THIS BE UNDER A SEPERATE PERMIT? PLEASE SHOW |
| LOCATION. 106.1.2* ADD INFO REQUIRED. |
| |
| 9) SHEET A102 MEZANINE LEVEL IT APPEARS OVER THE 2ND |
| FLOOR RESTROOMS IT APPEARSTO BE A VOID SPACE OR ROOM, |
| WITH THE EXISTINGWALL HAVING A WALL TYPE MARKER # 3 |
| AND A NEW WALL WITH NO WALL TYPE DESIGNATION, PLEASE |
| EXPLAIN THIS AREA? 106.1.2* ADD INFO REQUIRED. |
| |
| 10) SHEET A201- A205 INDICATE TYPE OF WALL FINISHES, |
| THEY INCLUDE WALL COVERINGS, GLASS, METAL LAMINATES, |
| PANEL FABRIC, WALL PANEL & WOOD VENEERS, PLEASE PROVIDE |
| THE FLAME SPREADINDEX AND SMOKE DEVELOPMENT INDEX FOR |
| EACH OF THE MATERIALS TO BE INSTALLED. SEE TABLE 803.5 |
| PLEASE TAKE NOTE OF FOOTNOTES A, B, AND C. |
| |
| 11) TEXTILES;803.6 TEXTILES. WHERE USED AS INTERIOR |
| WALL OR CEILING FINISH MATERIALS, TEXTILES, INCLUDING |
| MATERIALS HAVING WOVEN OR NONWOVEN, NAPPED, TUFTED, |
| LOOPED OR SIMILAR SURFACE, SHALL COMPLY WITH THE |
| REQUIREMENTS OF THIS SECTION. |
| |
| 803.6.1 TEXTILE WALL COVERINGS. |
| TEXTILE WALL COVERINGS SHALL HAVE A CLASS A FLAME |
| SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 AND BE |
| PROTECTED BY AUTOMATIC SPRINKLERS INSTALLED IN |
| ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 OR THE |
| COVERING SHALL MEET THE CRITERIA OF SECTION 803.6.1.1 |
| OR 803.6.1.2 WHEN TESTED IN THE MANNER INTENDED FOR USE |
| IN ACCORDANCE WITH NFPA 265 USING THE PRODUCT MOUNTING |
| SYSTEM, INCLUDING ADHESIVE. |
| |
| 803.6.1.1 METHOD A TEST PROTOCOL. |
| DURING THE METHOD A PROTOCOL, FLAME SHALL NOT SPREAD TO |
| THE CEILING DURING THE 40 KW EXPOSURE. DURING THE 150 |
| KW EXPOSURE, THE TEXTILE WALL COVERING SHALL COMPLY |
| WITH ALL OF THE FOLLOWING: |
| 1.FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITY OF |
| THE SAMPLE ON THE 8-FOOT BY 12-FOOT (203 MM BY 305 MM) |
| WALL. |
| 2.THE SPECIMEN SHALL NOT BURN TO THE OUTER |
| EXTREMITY OF THE 2-FOOT-WIDE (610 MM) SAMPLES MOUNTED |
| IN THE CORNER OF THE ROOM. |
| 3.BURNING DROPLETS DEEMED CAPABLE OF IGNITING |
| TEXTILE WALL COVERINGS OR THAT BURN FOR 30 SECONDS OR |
| MORE SHALL NOT FORM. |
| 4.FLASHOVER, AS DEFINED IN NFPA 265, SHALL NOT |
| OCCUR. |
| 5.THE MAXIMUM NET INSTANTANEOUS PEAK HEAT RELEASE |
| RATE, DETERMINED BY SUBTRACTING THE BURNER OUTPUT FROM |
| THE MAXIMUM HEAT RELEASE RATE, DOES NOT EXCEED 300 KW. |
| |
| |
| 803.6.1.2 METHOD B TEST PROTOCOL. |
| DURING THE METHOD B PROTOCOL, FLAMES SHALL NOT SPREAD |
| TO THE CEILING AT ANY TIME DURING THE 40 KW EXPOSURE. |
| DURING THE 150 KW EXPOSURE, THE TEXTILE WALL COVERING |
| SHALL COMPLY WITH THE FOLLOWING: |
| 1.FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITIES |
| OF THE SAMPLES ON THE 8-FOOT BY 12-FOOT (203 MM BY 305 |
| MM) WALLS. |
| 2.FLASHOVER, AS DESCRIBED IN NFPA 265, SHALL NOT |
| OCCUR. |
| |
| 803.6.2 TEXTILE CEILING FINISH. |
| WHERE USED AS A CEILING FINISH, CARPET AND SIMILAR |
| TEXTILE MATERIALS SHALL HAVE A CLASS A FLAME SPREAD |
| INDEX IN ACCORDANCE WITH ASTM E 84 AND BE PROTECTED BY |
| AUTOMATIC SPRINKLERS. |
| |
| 12) THE MATERIALS LIST ON SHEETS A201-A205 INCLUDE |
| GLASS IS THIS TRUELY GLASS OR LIGHT TRANSMITTING |
| PLASTICS?IF GLASS PROVIDE HOW IT WILL BE SECURED AND |
| THE TYPE OF GLASS? IF PLASTICS |
| PLEASE PROVIDE THE SPEC IN ACCORDANCE WITH 2606.4. |
| |
| 13) DECORATIONS AND TRIM:805.1 GENERAL. |
| IN OCCUPANCIES OF GROUPS A, E, I, R-1 AND DORMITORIES |
| IN GROUP R-2, CURTAINS, DRAPERIES, HANGINGS AND OTHER |
| DECORATIVE MATERIALS SUSPENDED FROM WALLS OR CEILINGS |
| SHALL BE FLAME RESISTANT IN ACCORDANCE WITH SECTION |
| 805.2 AND NFPA 701 OR NONCOMBUSTIBLE. |
| IN GROUPS I-1 AND I-2, COMBUSTIBLE DECORATIONS SHALL BE |
| FLAME RETARDANT UNLESS THE DECORATIONS, SUCH AS |
| PHOTOGRAPHS AND PAINTINGS, ARE OF SUCH LIMITED |
| QUANTITIES THAT A HAZARD OF FIRE DEVELOPMENT OR SPREAD |
| IS NOT PRESENT. IN GROUP I-3, COMBUSTIBLE DECORATIONS |
| ARE PROHIBITED. |
| |
| 805.1.1 NONCOMBUSTIBLE MATERIALS. |
| THE PERMISSIBLE AMOUNT OF NONCOMBUSTIBLE DECORATIVE |
| MATERIAL SHALL NOT BE LIMITED. |
| |
| 805.1.2 FLAME-RESISTANT MATERIALS. |
| THE PERMISSIBLE AMOUNT OF FLAME-RESISTANT DECORATIVE |
| MATERIALS SHALL NOT EXCEED 10 PERCENT OF THE AGGREGATE |
| AREA OF WALLS AND CEILINGS. |
| EXCEPTION: IN AUDITORIUMS OF GROUP A, THE PERMISSIBLE |
| AMOUNT OF FLAME-RESISTANT DECORATIVE MATERIAL SHALL NOT |
| EXCEED 50 PERCENT OF THE AGGREGATE AREA OF WALLS AND |
| CEILING WHERE THE BUILDING IS EQUIPPED THROUGHOUT WITH |
| AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| SECTION 903.3.1.1 AND THE MATERIAL IS INSTALLED IN |
| ACCORDANCE WITH SECTION 803.3 . |
| |
| 805.2 ACCEPTANCE CRITERIA AND REPORTS. |
| WHERE REQUIRED TO BE FLAME RESISTANT, DECORATIVE |
| MATERIALS SHALL BE TESTED BY AN APPROVED AGENCY AND |
| PASS TEST 1 OR 2, AS APPROPRIATE, DESCRIBED IN NFPA 701 |
| OR SUCH MATERIALS SHALL BE NONCOMBUSTIBLE. REPORTS OF |
| TEST RESULTS SHALL BE PREPARED IN ACCORDANCE WITH NFPA |
| 701 AND FURNISHED TO THE CODE OFFICIAL UPON REQUEST. |
| PLASTIC |
| 805.3 FOAM PLASTIC . |
| FOAM PLASTIC USED AS TRIM IN ANY OCCUPANCY SHALL COMPLY |
| WITH SECTION 2604.2 . |
| PLASTIC |
| 805.4 PYROXYLIN PLASTIC . |
| IMITATION LEATHER OR OTHER MATERIAL CONSISTING OF OR |
| COATED WITH A PYROXYLIN OR SIMILARLY HAZARDOUS BASE |
| SHALL NOT BE USED IN GROUP A OCCUPANCIES. |
| |
| 805.5 TRIM. |
| MATERIAL USED AS INTERIOR TRIM SHALL HAVE A MINIMUM |
| CLASS C FLAME SPREAD INDEX AND SMOKE-DEVELOPED INDEX. |
| COMBUSTIBLE TRIM, EXCLUDING HANDRAILS AND GUARDRAILS, |
| SHALL NOT EXCEED 10 PERCENT OF THE AGGREGATE WALL OR |
| CEILING AREA IN WHICH IT IS LOCATED. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL |
| INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR |
| THAT WERE NOT PART OF THIS REVIEW. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| ) |