2007-05-16 09:24:29BUILDING PLAN REVIEW
 PERMIT: 07030852
 ADD: 651 OKEECHOBEE BLVD# 100
 CONT: RCC ASSOCIATES, INC
 TEL: (954)691-5385
 FBC = 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE
 POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE
 FIRST INSPECTION.
  
 3) SHEET T-101, APPLICABLE CODES- THE 2001
 ACCESSIBILITY CODE IS THE WRONG CODE PLEASE CORRECT TO
 THE 2004 FBC CHAPTER 11FLORIDA ACCESSIBILITY CODE
  
 4) SHEET T-101, APPLICABLE CODES- PREVIOUS OCCUPANCY
 WAS ALSO A RESTAURANT: A2 OCCUPANCY
  
 5) SHEET T-101, CONSTRUCTION TYPE: THIS IS A HIGH RISE
 BUILDING REQUIRING TYPE IA CONSTRUCTION.
  
 6) IN THE SEET OF PLANSREVIEWED THE DESIGNER OF
 RECORD MISSED SIGNING AND SEALING THE T, LS ANDQUITE
 A FEW A SHEETS.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 7)VOA ASSOCIATES INCORP. DOESN'T INDICATE THEIR
 CERTIFICATE OF AUTHORIZATION.
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 8)ON SHEET A101 THIS SHEET INDICATES A KITHEN BUT NO
 FREEZERS NOR WALK IN COOLERS ARE SHOWN,
 WILL THIS BE UNDER A SEPERATE PERMIT? PLEASE SHOW
 LOCATION. 106.1.2* ADD INFO REQUIRED.
  
 9) SHEET A102 MEZANINE LEVEL IT APPEARS OVER THE 2ND
 FLOOR RESTROOMS IT APPEARSTO BE A VOID SPACE OR ROOM,
 WITH THE EXISTINGWALL HAVING A WALL TYPE MARKER # 3
 AND A NEW WALL WITH NO WALL TYPE DESIGNATION, PLEASE
 EXPLAIN THIS AREA? 106.1.2* ADD INFO REQUIRED.
  
 10) SHEET A201- A205 INDICATE TYPE OF WALL FINISHES,
 THEY INCLUDE WALL COVERINGS, GLASS, METAL LAMINATES,
 PANEL FABRIC, WALL PANEL & WOOD VENEERS, PLEASE PROVIDE
 THE FLAME SPREADINDEX AND SMOKE DEVELOPMENT INDEX FOR
 EACH OF THE MATERIALS TO BE INSTALLED. SEE TABLE 803.5
 PLEASE TAKE NOTE OF FOOTNOTES A, B, AND C.
  
 11) TEXTILES;803.6 TEXTILES. WHERE USED AS INTERIOR
 WALL OR CEILING FINISH MATERIALS, TEXTILES, INCLUDING
 MATERIALS HAVING WOVEN OR NONWOVEN, NAPPED, TUFTED,
 LOOPED OR SIMILAR SURFACE, SHALL COMPLY WITH THE
 REQUIREMENTS OF THIS SECTION.
  
 803.6.1 TEXTILE WALL COVERINGS.
 TEXTILE WALL COVERINGS SHALL HAVE A CLASS A FLAME
 SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 AND BE
 PROTECTED BY AUTOMATIC SPRINKLERS INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 OR THE
 COVERING SHALL MEET THE CRITERIA OF SECTION 803.6.1.1
 OR 803.6.1.2 WHEN TESTED IN THE MANNER INTENDED FOR USE
 IN ACCORDANCE WITH NFPA 265 USING THE PRODUCT MOUNTING
 SYSTEM, INCLUDING ADHESIVE.
  
 803.6.1.1 METHOD A TEST PROTOCOL.
 DURING THE METHOD A PROTOCOL, FLAME SHALL NOT SPREAD TO
 THE CEILING DURING THE 40 KW EXPOSURE. DURING THE 150
 KW EXPOSURE, THE TEXTILE WALL COVERING SHALL COMPLY
 WITH ALL OF THE FOLLOWING:
 1.FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITY OF
 THE SAMPLE ON THE 8-FOOT BY 12-FOOT (203 MM BY 305 MM)
 WALL.
 2.THE SPECIMEN SHALL NOT BURN TO THE OUTER
 EXTREMITY OF THE 2-FOOT-WIDE (610 MM) SAMPLES MOUNTED
 IN THE CORNER OF THE ROOM.
 3.BURNING DROPLETS DEEMED CAPABLE OF IGNITING
 TEXTILE WALL COVERINGS OR THAT BURN FOR 30 SECONDS OR
 MORE SHALL NOT FORM.
 4.FLASHOVER, AS DEFINED IN NFPA 265, SHALL NOT
 OCCUR.
 5.THE MAXIMUM NET INSTANTANEOUS PEAK HEAT RELEASE
 RATE, DETERMINED BY SUBTRACTING THE BURNER OUTPUT FROM
 THE MAXIMUM HEAT RELEASE RATE, DOES NOT EXCEED 300 KW.
  
  
 803.6.1.2 METHOD B TEST PROTOCOL.
 DURING THE METHOD B PROTOCOL, FLAMES SHALL NOT SPREAD
 TO THE CEILING AT ANY TIME DURING THE 40 KW EXPOSURE.
 DURING THE 150 KW EXPOSURE, THE TEXTILE WALL COVERING
 SHALL COMPLY WITH THE FOLLOWING:
 1.FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITIES
 OF THE SAMPLES ON THE 8-FOOT BY 12-FOOT (203 MM BY 305
 MM) WALLS.
 2.FLASHOVER, AS DESCRIBED IN NFPA 265, SHALL NOT
 OCCUR.
  
 803.6.2 TEXTILE CEILING FINISH.
 WHERE USED AS A CEILING FINISH, CARPET AND SIMILAR
 TEXTILE MATERIALS SHALL HAVE A CLASS A FLAME SPREAD
 INDEX IN ACCORDANCE WITH ASTM E 84 AND BE PROTECTED BY
 AUTOMATIC SPRINKLERS.
  
 12) THE MATERIALS LIST ON SHEETS A201-A205 INCLUDE
 GLASS IS THIS TRUELY GLASS OR LIGHT TRANSMITTING
 PLASTICS?IF GLASS PROVIDE HOW IT WILL BE SECURED AND
 THE TYPE OF GLASS? IF PLASTICS
 PLEASE PROVIDE THE SPEC IN ACCORDANCE WITH 2606.4.
  
 13) DECORATIONS AND TRIM:805.1 GENERAL.
 IN OCCUPANCIES OF GROUPS A, E, I, R-1 AND DORMITORIES
 IN GROUP R-2, CURTAINS, DRAPERIES, HANGINGS AND OTHER
 DECORATIVE MATERIALS SUSPENDED FROM WALLS OR CEILINGS
 SHALL BE FLAME RESISTANT IN ACCORDANCE WITH SECTION
 805.2 AND NFPA 701 OR NONCOMBUSTIBLE.
 IN GROUPS I-1 AND I-2, COMBUSTIBLE DECORATIONS SHALL BE
 FLAME RETARDANT UNLESS THE DECORATIONS, SUCH AS
 PHOTOGRAPHS AND PAINTINGS, ARE OF SUCH LIMITED
 QUANTITIES THAT A HAZARD OF FIRE DEVELOPMENT OR SPREAD
 IS NOT PRESENT. IN GROUP I-3, COMBUSTIBLE DECORATIONS
 ARE PROHIBITED.
  
 805.1.1 NONCOMBUSTIBLE MATERIALS.
 THE PERMISSIBLE AMOUNT OF NONCOMBUSTIBLE DECORATIVE
 MATERIAL SHALL NOT BE LIMITED.
  
 805.1.2 FLAME-RESISTANT MATERIALS.
 THE PERMISSIBLE AMOUNT OF FLAME-RESISTANT DECORATIVE
 MATERIALS SHALL NOT EXCEED 10 PERCENT OF THE AGGREGATE
 AREA OF WALLS AND CEILINGS.
 EXCEPTION: IN AUDITORIUMS OF GROUP A, THE PERMISSIBLE
 AMOUNT OF FLAME-RESISTANT DECORATIVE MATERIAL SHALL NOT
 EXCEED 50 PERCENT OF THE AGGREGATE AREA OF WALLS AND
 CEILING WHERE THE BUILDING IS EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1 AND THE MATERIAL IS INSTALLED IN
 ACCORDANCE WITH SECTION 803.3 .
  
 805.2 ACCEPTANCE CRITERIA AND REPORTS.
 WHERE REQUIRED TO BE FLAME RESISTANT, DECORATIVE
 MATERIALS SHALL BE TESTED BY AN APPROVED AGENCY AND
 PASS TEST 1 OR 2, AS APPROPRIATE, DESCRIBED IN NFPA 701
 OR SUCH MATERIALS SHALL BE NONCOMBUSTIBLE. REPORTS OF
 TEST RESULTS SHALL BE PREPARED IN ACCORDANCE WITH NFPA
 701 AND FURNISHED TO THE CODE OFFICIAL UPON REQUEST.
 PLASTIC
 805.3 FOAM PLASTIC .
 FOAM PLASTIC USED AS TRIM IN ANY OCCUPANCY SHALL COMPLY
 WITH SECTION 2604.2 .
 PLASTIC
 805.4 PYROXYLIN PLASTIC .
 IMITATION LEATHER OR OTHER MATERIAL CONSISTING OF OR
 COATED WITH A PYROXYLIN OR SIMILARLY HAZARDOUS BASE
 SHALL NOT BE USED IN GROUP A OCCUPANCIES.
  
 805.5 TRIM.
 MATERIAL USED AS INTERIOR TRIM SHALL HAVE A MINIMUM
 CLASS C FLAME SPREAD INDEX AND SMOKE-DEVELOPED INDEX.
 COMBUSTIBLE TRIM, EXCLUDING HANDRAILS AND GUARDRAILS,
 SHALL NOT EXCEED 10 PERCENT OF THE AGGREGATE WALL OR
 CEILING AREA IN WHICH IT IS LOCATED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL
 INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR
 THAT WERE NOT PART OF THIS REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
 )