Plan Review Notes
Plan Review Notes For Permit 07030833
Permit Number 07030833
Review Stop B
Sequence Number 3
Notes
Date Text
2007-05-30 11:57:27****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 1.)THERE ARE TWO WIND LOAD DESIGN SPECIFICATIONS IN
 THE PERMIT PACKAGE.ONE WAS PRODUCED WITH SOFTWARE,
 THE OTHER WAS PROVIDED BY A STRUCTURAL ENGINEER.
 ENGINEERING IN ACCORDANCE WITH ASCE7-02 IS REQUIRED FOR
 DESIGN PRESSURES FOR BUILDINGS OVER 60' IN HEIGHT,
 FBC1609.1.1.THEREFORE, YOU CANNOT USE THE PRESSURES
 PRODUCED BY THE WIND LOAD SOFTWARE.PLEASE REMOVE THE
 "DESIGN PRESSURE CALCULATION" FROM THE PACKAGE AND USE
 THE PRESSURES SPECIFIED BY THE ENGINEER (WHICH ARE
 HIGHER) FOR THIS PROJECT.
  
 2.)TWO DIFFERENT INSTALLATION SCHEDULES WERE
 PROVIDED.ONE STATES THAT THE SUBSTRATE IS CONCRETE
 BLOCK, THE OTHER STATES POURED CONCRETE.SUBMIT ONLY
 ONE INSTALLATION SCHEDULE, TWO COPIES.TWO SETS
 SUBMITTED OF THE CONCRETE BLOCK SCHEDULE, ONLY ONE FOR
 THE INSTALLATION SCHEDULE WITH THE POURED CONCRETE
 SUBSTRATE.TWO IDENTICAL COMPLETE SETS, COLLATED,
 SHOULD ALWAYS BE SUBMITTED FOR PERMITTING.
  
 3.)THE INSTALLATION SCHEDULES USE THE DESIGN
 PRESSURES PRODUCED BY THE SOFTWARE.YOU MUST USE THE
 DESIGN PRESSURES SPECIFIED BY THE STRUCTURAL ENGINEER,
 WHICH ARE HIGHER.REVISE THE INSTALLATION SCHEDULE
 ACCORDINGLY.
  
 4.)THE INSTALLATION SCHEDULE STATES THAT SHUTTER SPAN
 IS 9'.ON THE PRODUCT APPROVAL, YOU HAVE CIRCLED
 ANCHOR SPACING FOR AN 8'0" SPAN, -60PSF DESIGN
 PRESSURE.THE ENGINEER SPECIFIES -62.27 FOR ONE OF THE
 OPENINGS, SO YOU MUST USE THE -75PSF COLUMN FOR THAT
 OPENING.IF THE SPAN (WHICH SHOULD BE THE BLADE
 LENGTH) IS OVER 8', USE THE 9' COLUMN.PLEASE CLARIFY
 THE SPAN AS THE MOUNTING DETAIL TO BE USED IS NOT
 CLEAR.
  
 5.)THE COLUMN ON THE INSTALLATION SCHEDULE MARKED
 "SHUTTER MOUNTING:CONNECTION TYPE PER PRODUCT
 APPROVAL" IS TO INDICATE WHICH MOUNTING DETAIL YOU ARE
 USING.ON THIS PRODUCT APPROVAL, IT WOULD BE DETAILS A
 THROUGH L.IT IS NOT CLEAR WHICH MOUNTING DETAIL YOU
 ARE USING AS SEVERAL HAVE BEEN CIRCLED ON THE PRODUCT
 APPROVAL.
  
 6.)THE PRODUCT APPROVAL HAS H, FLOOR MOUNTING
 CIRCLED, WITH 8.5 ANCHORING ALSO CIRCLED.THE
 INSTALLATION SCHEDULE DOES NOT SPECIFY 8.5 ANCHOR
 SPACING.ANYTHING CIRCLED ON THE PRODUCT APPROVAL
 SHOULD CORRELATE WITH THE JOB AND INSTALLATION
 SCHEDULE.
  
  