2007-04-21 14:11:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)YOU HAVE USED EXPOSURE B PRESSURES, THIS IS
 EXPOSURE C.REVISE PRESSURES AND REVISE ANCHOR
 SCHEDULE AS NECESSARY.FOR INSTANCE, OPENING 5, END
 ZONE, HAS A MINIMUM DESIGN PRESSURE OF -48.16 FOR 50SF,
 END ZONE, EXPOSURE C.SEE HIGHLIGHTED PRODUCT
 APPROVAL, 11INCH SPACING REQUIRED.CHECK ALL
 OPENINGS.