2007-05-21 15:45:541. NOTE # 2 ON PAGE FP-1 IS INCORRECT. "STANDPIPE
 SYSTEM SHALL COMPLY WITH NFPA 24". SHOULD READ
 STANDPIPE SYSTEM SHALL COMPLY WITH NFPA 14.
  
 2. PARKING GARAGE FIRE SPRINKLER SYSTEM TO COMPLY WITH
 NFPA 13.
  
 3. ANY FIRE SPRINKLER HEADS DUE TO THEIR INSTALLATION
 HEIGHT OR INSTALLED IN AN AREA WHERE THEY ARE SUBJECT
 TO MECHANICAL DAMAGE SHALL BE PROVIDED WITH HEAD
 GUARDS.
  
 4. NOTE # 3 ON PAGE FP-2 IS NOT COMPLETE.
  
 5. THE ENTIRE FIRE SPRINKLER SYSTEM SHALL BE INSTALLED
 IN AN APPROVED AND WORKMANSHIP MANNER.
  
 6. FIRE SPRINKLER SYSTEM SUBJECT TO FIELD INSPECTION
 AND APPROVAL.
  
 7. SPEC BOOKS DO NOT DECLARE ANY UL LISTING FOR THE 120
 GALLON DIESEL FUEL TANK BEING PROPOSED. PLEASE PROVIDE
 LISTING INFORMATION.
  