2007-05-21 15:45:54 | 1. NOTE # 2 ON PAGE FP-1 IS INCORRECT. "STANDPIPE | | SYSTEM SHALL COMPLY WITH NFPA 24". SHOULD READ | | STANDPIPE SYSTEM SHALL COMPLY WITH NFPA 14. | | | | 2. PARKING GARAGE FIRE SPRINKLER SYSTEM TO COMPLY WITH | | NFPA 13. | | | | 3. ANY FIRE SPRINKLER HEADS DUE TO THEIR INSTALLATION | | HEIGHT OR INSTALLED IN AN AREA WHERE THEY ARE SUBJECT | | TO MECHANICAL DAMAGE SHALL BE PROVIDED WITH HEAD | | GUARDS. | | | | 4. NOTE # 3 ON PAGE FP-2 IS NOT COMPLETE. | | | | 5. THE ENTIRE FIRE SPRINKLER SYSTEM SHALL BE INSTALLED | | IN AN APPROVED AND WORKMANSHIP MANNER. | | | | 6. FIRE SPRINKLER SYSTEM SUBJECT TO FIELD INSPECTION | | AND APPROVAL. | | | | 7. SPEC BOOKS DO NOT DECLARE ANY UL LISTING FOR THE 120 | | GALLON DIESEL FUEL TANK BEING PROPOSED. PLEASE PROVIDE | | LISTING INFORMATION. | | | | APPROVED PROVISO: | | | | MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX |
|