2007-04-12 08:45:021. ENTIRE PARKING GARAGE IS TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED EXCEPT FOR THE FPL VAULT.
  
 2. THE FIRST FLOOR MECHANICAL ROOM MUST ALSO BE FIRE
 SPRINKLER PROTECTED. PLANS DO NOT ILLUSTRATE FIRE
 SPRINKLER HEADS IN THIS ROOM OR ELECTRICAL ROOM B1.111.
 PRE-ACTION FIRE SPRINKLER SYSTEM NOTED TO BE PLANNED IN
 THE MAIN ELECTRICAL ROOM ACCORDING TO THE NOTES.
  
 3. STANDPIPE SYSTEM FIRE HOSE VALVES SHALL BE EQUIPPED
 WITH 2 1/2 TO 1 1/2 REDUCERS.
  
 4. SPARE SPRINKLER HEADS AND A WRENCH SHALL BE PROVIDED
 FOR THE FIRE SPRINKLER SYSTEM.
  
 5. FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED WITH
 KNOX-BOX LOCKING CAPRS.
  
 6. FIRE SPRINKLER SYSTEM TO BE INSTALLED IN ACCORDANCE
 WITH NFPA 13.
  
 7. STANDPIPE SYSTEM SHALL BE INSTALLED IN ACCORDANCE
 WITH NFPA 14.
  
 8. FIRE PUMP TO BE INSTALLED IN ACCORDANCE WITH NFPA
 20.
  
 9. FIRE SPRINKLER HEADS THAT ARE INSTALLED OUTSIDE
 SHALL BE WAX COATED OR CORROSION RESISTANT.
  
 10. CUT SHEETS NEEDED FOR THE FIRE PUMP, BACKFLOW
 PREVENTION DEVICE, FIRE SPRINKLER HEADS, AND ALL OTHER
 APPURTENANT EQUIPMENT.
  
 11. TEMPORARY STANDPIPE SYSTEMS SHALL BE REQUIRED WHEN
 EACH BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX