Plan Review Notes For Permit 07030782 |
Permit Number |
07030782 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-30 08:42:18 | *** DENIED *** | | 1) MECHANICAL PLANS ARE SHOWING A PACKAGE A/C SYSTEM TO | | BE INSTALLED, A/C EQUIPMENT LISTING IS CALLING FOR A | | SPLIT SYSTEM (AIR HANDLER AND CONDENSER UNIT), THE TWO | | MUST COINCIDE, PLEASE CORRECT. | | | | 2) PLEASE SUBMIT DETAILED MANUFACTURER'S | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR A/C | | SYSTEM. | | | | 3) THE 8" RETURN AIR TRANSFER DUCT TO BEDROOM #3 NEEDS | | TO BE 10", SEE 2004 FBC/R M1602.4. PLEASE CORRECT. | | | | 4)THE 8" RETURN AIR TRANSFER DUCT TO BEDROOM #2 NEEDS | | TO BE 12", SEE 2004 FBC/R M1602.4. PLEASE CORRECT. | | | | 5)THE 8" RETURN AIR TRANSFER DUCT TO BEDROOM #1 NEEDS | | TO BE 9", SEE 2004 FBC/R M1602.4. PLEASE CORRECT. | | | | ** 2004 FBC/R M1602.4 BALANCED RETURN AIR MAY BE | | ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | ACHIEVE PROPER RETURN AIR BALANCE. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|