Plan Review Notes
Plan Review Notes For Permit 07030782
Permit Number 07030782
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-31 14:01:34****** UNSAT *****
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE OF FLORIDA
 BUILDING COMMISSION.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLANS NOW INDICATE THE 2002 NEC, ON THE ELECTRICAL
 SHEET.
 PLANS ARE TO REFLECT THE 2006 REVISIONS.
 PLEASE LIST THE FOLLOWING ON SHEETS FOR THIS REVIEWER
 AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE PLANS DO NOT CONTAIN ANY DESIGNER
 OF RECORD, PRINTED NAME , SIGNATURE, DATES SEALS??
 PLEASE COMPLETE. FBC 106.3.5.4, 106.1.2
  
 3) NOTE: PLEASE CORRELATE PLANS WITH THE RISER. PLEASE
 SEE PLANS INDICATE PANEL OUTSIDE YET RISER MENTIONS IN
 GARAGE? PLANS DO NOT SHOW ANY GARAGE?
 215.5, 110.26, 240.24 ETC.
 FBC 106.1.2
  
 4) NOTE: PLEASE INDICATE THE AIC RATING FOR THE MAIN
 CIRCUIT BREAKER.
 110.9. (SHOWN FOR PANEL AND BRANCH BREAKERS, NOT FOR
 MAIN)
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE MISSING KITCHEN COUNTER SPACE
 RECEPTACLES PER 210.52C1-5
  
 6) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS DISPOSAL, YET
 PLANS DO NOT SHOW RECEPTACLE FOR THIS.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE MISSING GFI DESIGNATION FROM
 SEVERAL DEVICES. PLEASE SEE 210.8A1, A2, A3, A6 ETC.
 BATH(S), OUTSIDE, KITCHEN COUNTER SPACES ETC,,
  
 8) NOTE: PLEASE SEE MISSING EGRESS LIGHTING CONTROL FOR
 INSIDE AND OUTSIDE STAIRS. (3-WAYS).
 PLEASE SEE 210.70, LS 101 7.8
  
 9) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.52 AND
 DINING ROOM RECEPTACLES WHICH ARE REQUIRED ON ONE OR
 MORE OF THE SMALL APPLIANCE CIRCUITS.
  
 10) NOTE: PLEASE SEE THE LOAD CALCULATIONS DO NOT
 CORRELATE WITH THE CIRCUITS ON THE PANEL SCHEDULE,
 THERE ARE SEVERAL ITEMS WHICH ARE EITHER ON LOAD
 CALCULATIONS AND NOT ON PANEL SCHEDULE OR SEVERAL ITEMS
 ON THE PANEL SCHEDULE WHICH IS NOT IN LOAD
 CALCULATIONS.
 PLEASE SEE FOUR CIRCUITS SHOWN FOR *OVER FEAD DOORS*
 (MISSPELLED ON PLANS) YET THERE ARE NO OVER HEAD GARAGE
 DOORS OR EVEN A GARAGE ON PLANS.
 PLEASE SEE MISSING WATER HEATER, ICE MAKE, ETC ETC.
 FBC 106.1.2
 NEC 408.4, 220 ETC
  
 11) NOTE: PLEASE SEE MISSING AHU FROM PLANS. PLEASE SEE
 MISSING DISCONNECT.
 PLEASE SEE 440.11, 110.26, 240.24.
  
 12) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER
 HEATER.
 422.30, 31.
  
 13) NOTE: PLEASE SEE CHANGE IN THE 2005 NEC FOR LOADS
 FOR WATER HEATERS PER 422.13.
 PLEASE SEE THE FOLLOWING TEXT EXTRACTED FORM THE NEC.
  
 *THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN
 ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120
 GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION
 REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND
 CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE
 WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT
 DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED
 TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT
 RATING. IN ADDITION, FEEDERS AND SERVICES THAT SUPPLY
 WATER HEATER BRANCH CIRCUITS ARE ALSO IMPACTED BY THE
 FACT THAT THIS TYPE OF EQUIPMENT IS CONSIDERED TO BE A
 CONTINUOUS LOAD.*
  
 14) NOTE: PLEASE SEE THE LOAD CALCULATIONS INDICATE
 FOUR A/C SYSTEMS?
 PLEASE COORDINATE WITH PLANS AND PANEL SCHEDULE AS ONLY
 ONE SYSTEM IS SHOWN.
 FBC 106.1.2
  
 15) NOTE: PLEASE SEE NEC 220, AS THE LOAD CALCULATIONS
 INDICATE A LOAD OF 259AMPS??
 PLEASE REVISE.
  
 16) NOTE: PLEASE SEE MOST ROOMS INDICATE THE ENTIRE
 RECEPTACLE BEING SWITCHED, THIS IS OK, HOWEVER THEN A
 RECEPTACLE WOULD BE REQUIRED FOR GENERAL PURPOSE (HOT
 ALL THE TIME).
 IF THIS IS INDEED A HALF-SWITCHED OUTLET THEN PLEASE
 SHOW AS THIS.
  
 17) NOTE: PLEASE SEE 408.4 WHICH REQUIRE ALL CIRCUITS
 TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED.
 THE USE OF *GEN LTS AND GEN RECEPTS* IS NOT PERMITTED.
 PLEASE SEE THE FOLLOWING TECT TAKEN FROM THE NEC.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]