Plan Review Notes
Plan Review Notes For Permit 07030665
Permit Number 07030665
Review Stop G
Sequence Number 1
Notes
Date Text
2007-04-11 10:37:28DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS AND GEN/RES PERMIT
 APPLICATION REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
  
 THE FOLLOWING CORRECTIONS/INFORMATIONREQUIRED FOR GAS
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC, PLEASE
 REFERENCE THE ATTACHED ISOMETRIC TO THE GAS COMMENTS
 REFLECTING THE PROPOSED GAS SYSTEM. CORRESPONDING
 LENGTHS OF ALL CUT SECTIONS OF PIPE MUST BE INDICATED
 ON THE RESUBMITTED DRAWING. THE ONLY INDICATED PIPING
 MEASUREMENT IS FOR THE UNDERGROUND 1/2" PE. WHAT ARE
 THE CORRESPONDING LENGTHS OF THE ABOVE GROUND PIPING?
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: BOTH THE ABOVE AND UNDERGROUND PIPING MATERIALS
 AND SIZES MUST BE INDICATED ON THE DRAWINGS. ON THE
 SUBMITTED GAS CHECKLIST PIPE/TUBING SPECS. COPPER, PE,
 AND GALV. ARE INDICATED AS PIPING MATERIAL BEING USED
 BUT ON THE SUBMITTED DRAWING ONLY PE AND GALV. ARE
 INDICATED AS BEING USED. PLEASE CORRELATE AND CORRECT
 ON THE RESUBMITTAL
  
 3. SUBMIT MANUFACTURE SPECIFICATION SHEETS FOR THE
 GENERATOR THAT VERIFIES THE BTU LOAD OF GENERATOR AT
 100% RUNNING CAPACITY AND VERIFIES THE BTU LOAD OF
 229,000 INDICATED ON THE DRAWINGS.
  
 4. PLEASE SUBMIT TWO COPIES OF THE ABOVE GROUND LP
 TANK ANCHORING DETAIL FOR THE RESUBMITTAL.
  
 5. CLEARLY SHOW THETYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved