Date |
Text |
2007-04-11 10:37:28 | DENIED |
| REFERENCE: |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS AND GEN/RES PERMIT |
| APPLICATION REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| |
| |
| THE FOLLOWING CORRECTIONS/INFORMATIONREQUIRED FOR GAS |
| PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC, PLEASE |
| REFERENCE THE ATTACHED ISOMETRIC TO THE GAS COMMENTS |
| REFLECTING THE PROPOSED GAS SYSTEM. CORRESPONDING |
| LENGTHS OF ALL CUT SECTIONS OF PIPE MUST BE INDICATED |
| ON THE RESUBMITTED DRAWING. THE ONLY INDICATED PIPING |
| MEASUREMENT IS FOR THE UNDERGROUND 1/2" PE. WHAT ARE |
| THE CORRESPONDING LENGTHS OF THE ABOVE GROUND PIPING? |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: BOTH THE ABOVE AND UNDERGROUND PIPING MATERIALS |
| AND SIZES MUST BE INDICATED ON THE DRAWINGS. ON THE |
| SUBMITTED GAS CHECKLIST PIPE/TUBING SPECS. COPPER, PE, |
| AND GALV. ARE INDICATED AS PIPING MATERIAL BEING USED |
| BUT ON THE SUBMITTED DRAWING ONLY PE AND GALV. ARE |
| INDICATED AS BEING USED. PLEASE CORRELATE AND CORRECT |
| ON THE RESUBMITTAL |
| |
| 3. SUBMIT MANUFACTURE SPECIFICATION SHEETS FOR THE |
| GENERATOR THAT VERIFIES THE BTU LOAD OF GENERATOR AT |
| 100% RUNNING CAPACITY AND VERIFIES THE BTU LOAD OF |
| 229,000 INDICATED ON THE DRAWINGS. |
| |
| 4. PLEASE SUBMIT TWO COPIES OF THE ABOVE GROUND LP |
| TANK ANCHORING DETAIL FOR THE RESUBMITTAL. |
| |
| 5. CLEARLY SHOW THETYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |
| |