Plan Review Notes
Plan Review Notes For Permit 07030665
Permit Number 07030665
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-28 07:55:49 
  
  
 DENIED/INCOMPLETE INFORMATION.
  
 1} PROVIDE A RISER DIAGRAM PER 215.5
 INCLUDING GENERATOR AND RELATED
 EQUIPMENT.
  
 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]