2007-05-07 11:50:12 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE 3/0 CONDUCTORS FROM THE GENERATORS 300 AMP
 BREAKER DO NOT COMPLY WITH 310.16. THEY NEED TO BE 300
 MCM MINIMUM. ALSO THOSE FEEDER CONDUCTORS WOULD BE
 REQUIRED THE ENTIRE LENGTH OF THE GENERATOR FEED TO THE
 200 AMP INDOOR PANEL IF THE CURRENT IS NOT LIMITED TO
 200 AMPS AT THE GENERATOR OR THE 300 AMP DISCONNECT
 SHOWN OUTSIDE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  