Plan Review Notes For Permit 07030640 |
Permit Number |
07030640 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-07-25 08:48:25 | PLANS REDLINED. 2ND TIME. | | NEW SHEETS SUBMITTED HOWEVER NO CORRECTIONS WERE MADE | | TO THE ITEMS AS NOTED BELOW FROM PREVIOUS REVIEW. | | | | | | * PLEASE SEE PREVIOUS REQUESTED CODES AND NOTES WERE | | PLACED ON D-1 AND NOT ON ELECTRICAL SHEETS. THIS | | INLCUDES THE NOTES FOR RECESSED LIGHTING REQUIREMENTS | | AND CORRECT ADOPTED CODES FOR DESIGN.( PLEASE PLACE ON | | ELECTRICAL SHEETS). | | * NOTES ON ELECTRICAL SHEETS IN LEGEND STILL INDICATE | | THE 2002 NEC. | | * PLEASE SEE GFI PROTECTION IS REQUIRED FOR "ALL" | | RECEPTS WITHIN 6FT OF LAUNDRY ROOM SINK WHICH ARE 125V | | 15 OR 20 AMP. (INCLUDING DEDICATED USE RECEPTS, THIS | | WAS CHANGED IN THE 2005 NEC ) | | | | ** PLEASE CORRECT THE ABOVE ALONG WHEN ANY OTHER | | REVISIONS ARE MADE TO PLANS. | | | | |
|