Plan Review Notes
Plan Review Notes For Permit 07030640
Permit Number 07030640
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-03 10:51:37PLANS REDLINED.
  
  
 * PLEASE SEE PREVIOUS REQUESTED CODES AND NOTES WERE
 PLACED ON D-1 AND NOT ON ELECTRICAL SHEETS. THIS
 INLCUDES THE NOTES FOR RECESSED LIGHTING REQUIREMENTS
 AND CORRECT ADOPTED CODES FOR DESIGN.( PLEASE PLACE ON
 ELECTRICAL SHEETS).
 * NOTES ON ELECTRICAL SHEETS IN LEGEND STILL INDICATE
 THE 2002 NEC.
 * PLEASE SEE GFI PROTECTION IS REQUIRED FOR "ALL"
 RECEPTS WITHIN 6FT OF LAUNDRY ROOM SINK WHICH ARE 125V
 15 OR 20 AMP. (INCLUDING DEDICATED USE RECEPTS, THIS
 WAS CHANGED IN THE 2005 NEC )
  
 ** PLEASE CORRECT THE ABOVE ALONG WHEN ANY OTHER
 REVISIONS ARE MADE TO PLANS.
  
  
 SOME SHEETS STILL NOT DATED BY THE ARCHITECT.(
 ELECTRICAL SHEETS OK).